1、目 錄一、工程概況················································
2、83;····11、工程簡(jiǎn)介············································
3、183;···12、主要機(jī)械設(shè)備投入情況····································13、主要機(jī)械設(shè)備布置情況······
4、······························1二、編制依據(jù)···················
5、;···································1三、現(xiàn)場(chǎng)施工負(fù)荷計(jì)算·············
6、·······························1四、變壓器容量選擇·················
7、183;······························1五、設(shè)計(jì)配電系統(tǒng)··················
8、;································31、施工用電材料················
9、183;····························32、施工用電線路布設(shè)及實(shí)施方法··················
10、3;············33、照明線路····································
11、83;············64、重復(fù)接地系統(tǒng)····································
12、·········65、現(xiàn)場(chǎng)施工總控制箱、分配電箱及及開關(guān)箱分布圖··············6六、避雷系統(tǒng)······················
13、;······························6七、確定防護(hù)措施··················
14、183;·····························6八、制定安全用電措施和電氣防火措施·················
15、183;·············6九、臨時(shí)用電安全管理制度··································&
16、#183;·····15十、現(xiàn)場(chǎng)施工用電及有關(guān)圖表······································15十一、臨時(shí)用水··&
17、#183;·············································18一、工程概況1、工程簡(jiǎn)介:湖南*體育新城住宅小
18、區(qū)一期工程由長(zhǎng)沙*置業(yè)有限公司開發(fā)。工程位于長(zhǎng)沙市雨花區(qū)*村,*路交*路東南側(cè)。其中2#標(biāo)段由六棟高層建筑群,一棟商鋪和地下車庫(kù)組成。其中B1、B2、B5、B6、棟為11層住宅,A1、A2棟為18層住宅,商鋪A為2層,由中建*局*公司承建施工。具有工程量大,工期緊迫等特點(diǎn)。2、主要設(shè)備投入:由于該工程所具有的特點(diǎn),投入的設(shè)備多,用電總功率比較大。因此,對(duì)整個(gè)工程現(xiàn)場(chǎng)用電應(yīng)該實(shí)行統(tǒng)一管理,統(tǒng)一布設(shè)的用電控制措施。根據(jù)本工程具體情況及施工組織設(shè)計(jì),擬將投入使用的設(shè)備主要有塔式起重機(jī)3臺(tái)、輸送泵2臺(tái)、電焊機(jī)8臺(tái)、對(duì)焊機(jī)1臺(tái)以及其它施工用的小型設(shè)備若干。如:切斷機(jī)、彎曲機(jī)、水泵、振動(dòng)泵、木工機(jī)械等。設(shè)
19、備的選擇以及功率的大小詳見后表第七章(總功率857KW)。為安全順利地施工,對(duì)上述這些用電較大的設(shè)備采取分線路供電方法進(jìn)行用電控制。3、主要設(shè)備布置:根據(jù)現(xiàn)場(chǎng)施工要求,于擬建建筑物B-1#樓、B-5#樓之間設(shè)TC5013B塔式起重機(jī)一臺(tái);B-2#樓、B-6#樓之間設(shè)TC5610B塔式起重機(jī)一臺(tái);A-1#樓、A-2#樓之間設(shè)TC5013B塔式起重機(jī)一臺(tái);B-5#樓擬建一鋼筋加工車間;一臺(tái)砼輸送泵分置于B-5#樓北面處;一臺(tái)砼輸送泵分置于A-2#樓北面處;用電平面布置圖附后。二、編制依據(jù) 依據(jù)中華人民共和國(guó)行業(yè)標(biāo)準(zhǔn)JGJ46-2005施工現(xiàn)場(chǎng)臨時(shí)用電安全技術(shù)規(guī)范,公司的工程技術(shù)手冊(cè)及有關(guān)的質(zhì)量、環(huán)
20、境、安全程序文件。三、現(xiàn)場(chǎng)施工負(fù)荷計(jì)算P1為用電高峰期塔吊、攪拌機(jī)、砼輸送泵、物料提升機(jī)、插入式振搗器、平板振動(dòng)器、鋼筋切斷機(jī)、鋼筋彎曲機(jī)、鋼筋調(diào)直機(jī)、木工機(jī)械、高壓泵功率之和;P2為用電高峰期電焊機(jī),電渣壓力焊、對(duì)焊機(jī)功率之和。P1=431.8 KW P2=344 KW P3=60 KW P4=50 KWP總=1.05×(K1P1/cosØ+K2P2+K3P3+K4P4)=1.05×0.6×431.8/0.75+0.6×344+0.8×60+1.0×50=682.332KVA式中:P總工地總用電量(KVA);P1電動(dòng)機(jī)額定
21、功率(kW);P2電焊機(jī)額定容量(kVA);P3室內(nèi)照明容量(kW);P4室外照明容量(kW);cosØ電動(dòng)機(jī)的平均功率因素,建筑工地最高峰取0.750.78。K1電動(dòng)機(jī)系數(shù),一般310臺(tái)取0.7,1130臺(tái)取0.6,30臺(tái)以上取0.5。本工程取K1=0.6。K2電焊機(jī)系數(shù),一般310臺(tái)取0.6;10臺(tái)以上取0.5。本工程取K2=0.6。K3室內(nèi)照明需用系數(shù),一般取K3=0.8;K4室外照明需用系數(shù),一般取K4=1.0。四、變壓器容量選擇在施工現(xiàn)場(chǎng)的南面業(yè)主已提供一臺(tái)500KVA的箱式變壓器,根據(jù)該工程即將投入使用的設(shè)備(見附表一),計(jì)算出高峰期總用電量為658.64KVA。由此可知
22、業(yè)主提供的500KVA變壓器使用時(shí)不滿足施工現(xiàn)場(chǎng)動(dòng)力及照明用電需求。因此需要對(duì)施工現(xiàn)場(chǎng)用電進(jìn)行分線設(shè)計(jì),以滿足施工需求。五、設(shè)計(jì)現(xiàn)場(chǎng)施工配電系統(tǒng) 1、施工用電材料準(zhǔn)備施工用電材料準(zhǔn)備應(yīng)根據(jù)施工用電線路的具體位置及走向,現(xiàn)場(chǎng)實(shí)際用電(動(dòng)力及照用電)的情況,以及設(shè)備功率的大小和數(shù)量。準(zhǔn)確的計(jì)算出所用材料的規(guī)格、型號(hào)和數(shù)量。合理地選用電氣材料,以確保施工現(xiàn)場(chǎng)安全用電,并滿足施工的需要。主要電氣材料計(jì)劃見附表2。2、施工用電布設(shè)及實(shí)施方法1)施工現(xiàn)場(chǎng)臨時(shí)配電采用TNS系統(tǒng),即專用變壓器中性點(diǎn)接地。三相五線制供電系統(tǒng)。由甲方提供變壓器和成套配電柜向現(xiàn)場(chǎng)供電。現(xiàn)場(chǎng)共設(shè)八條動(dòng)力用電回路以及一條備用回路。材料
23、全部使用五芯電纜線。電纜不得直接掛于外架鋼管和其它金屬物上。詳見第九章附表和用電總平面圖。a地下室施工時(shí),供電回路電源線用絕緣子固定沿基坑側(cè)壁引向現(xiàn)場(chǎng)用電處。地下室照明供電,應(yīng)選用電氣電壓36V或24V,照明變壓器容量應(yīng)考慮選擇大于實(shí)際照明容量的20%。b地下室施工完后地面電纜線可沿建筑物排水溝暗敷,局部采用埋地處理。c上主體時(shí),樓層上作業(yè)面施工用電可采用五根單芯銅線沿建筑物管道井或其它預(yù)留井用絕緣子敷設(shè)并逐層上升至頂層。d各樓層裝修期間,每隔一層安裝一分配電箱以供施工用電,電源可由五根單芯銅線上引出。e線路BL1:此線路由西南向配電屏引出,下屬施工現(xiàn)場(chǎng)TC5610B開關(guān)箱KX1,總用電負(fù)荷為
24、40KW。查表用公式:I =KP/ UcosØ=0.7×(1.1×40)/ ×0.38×0.7=66.9(A)式中:I線路容許電流(A)K需要系數(shù)P電力負(fù)荷U線路電壓cosØ功率因數(shù), 查表可知,此線路需選用YC-3×35+2×16(2)的銅芯電纜。線路BL2、BL3、BL4、BL5、BL6、BL7、BL8、BL9、BL10、BL11、BL12、BL13 、BL14同樣可用以上公式得知線徑大小。詳見附后用電系統(tǒng)圖2)配電房的設(shè)置a現(xiàn)甲方在施工現(xiàn)場(chǎng)北向已提供箱式變壓器(因地處鬧市區(qū),不考慮安裝備用發(fā)電機(jī))。b配電間內(nèi)
25、應(yīng)按規(guī)范設(shè)置齊全,設(shè)專人值班。c配電間的配電屏所有構(gòu)架的保護(hù)接零即線接入供電局的接地體上。3、照明線路)施工現(xiàn)場(chǎng)的照明線路全部要求相線進(jìn)開關(guān)。)照明電源一定要有漏電保護(hù)裝置。)室內(nèi)普通板把開關(guān)和電源插座安裝高度為.)室內(nèi)拉線開關(guān)和洗手間的電源插座安裝高度為.。)室內(nèi)照明燈具安裝高度為.。4、重復(fù)接地系統(tǒng): 在TN-S系統(tǒng)中,PE線由供電局變壓器中性點(diǎn)引出,但在各回路主控制箱、分配箱及配電屏處和線路終端點(diǎn)、設(shè)備集中點(diǎn)處要作重復(fù)接地。接地體可根據(jù)土質(zhì)情況設(shè)置,也可利用建筑物質(zhì)基礎(chǔ)的接地系統(tǒng)。其電阻不得大于10歐姆。5、現(xiàn)場(chǎng)施工總控制箱、分配箱及開關(guān)箱51、總原則:1)多級(jí)配電、多級(jí)保護(hù)。(三級(jí)配電
26、、兩級(jí)保護(hù))。2)一機(jī)一閘一漏電一電箱。3)三相五線制。(PE線與工作零線分開)52、漏電開關(guān)配置:最末級(jí)保護(hù)器額定漏電電流必須小于或等于30mA,額定漏電動(dòng)作時(shí)間不大于0.1S。前級(jí)保護(hù)器漏電電流及時(shí)間相應(yīng)增加。漏電保護(hù)器應(yīng)裝設(shè)在配電箱電源隔離開關(guān)的負(fù)荷側(cè)和開關(guān)箱電源隔離開關(guān)的負(fù)荷側(cè)。53、電箱標(biāo)識(shí)及內(nèi)容分布見附圖:1)電箱面須有編號(hào)、責(zé)任人、用途。2)總配電箱應(yīng)裝設(shè)總隔離開關(guān)和分路隔離開關(guān)、總?cè)蹟嗥骱头致啡蹟嗥鳎ɑ蚩傋詣?dòng)開關(guān)和分路自動(dòng)開關(guān)),以及漏電保護(hù)器。若漏電保護(hù)器同時(shí)具備過負(fù)荷和短路保護(hù)功能,則可不設(shè)分路熔斷器或分路自動(dòng)開關(guān)。3)電箱應(yīng)裝設(shè)總隔離開關(guān)和分路隔離開關(guān)以及總?cè)蹟嗥骱头秩蹟?/p>
27、器(或總自動(dòng)開關(guān)和分路自動(dòng)開關(guān))。4)每臺(tái)用電設(shè)備應(yīng)有各自專用的開關(guān)箱,必須實(shí)行“一機(jī)一閘”,嚴(yán)禁用同一個(gè)開關(guān)電器直接控制二臺(tái)及二臺(tái)以上用電設(shè)備(含插座)。5)開關(guān)箱內(nèi)的開關(guān)電器必須能在任何情況下都可以使用電設(shè)備的電源隔離。6)電箱內(nèi)設(shè)置明顯分?jǐn)帱c(diǎn)的隔離開關(guān)控制。7)電箱左下角須有PE接線排。8)箱體、箱蓋以及其它設(shè)備保護(hù)接地也須用黃綠雙色線與電網(wǎng)中PE線作可靠連接。9)箱內(nèi)各回路有用途標(biāo)識(shí)。10)接線端子上采用線鼻子壓接,不應(yīng)繞接。11)箱內(nèi)須畫電路圖。12)分配電箱和開關(guān)箱的距離不得超過30M,開關(guān)箱與用電設(shè)備水平距離不得超過3M。六、避雷系統(tǒng)工程施工現(xiàn)場(chǎng)臨時(shí)用電采用TN-S系統(tǒng),在1、2
28、、3配電屏及三臺(tái)塔吊配電箱處均采用重復(fù)接地,接地裝置利用現(xiàn)有在建工程接地裝置,即樁基鋼筋。采用40×4扁鋼焊接連通,搭焊長(zhǎng)度不小于2倍扁鋼寬度,各段之間應(yīng)可靠焊接,保證電氣連接。變電所、配電室、塔吊的防雷接地共用系統(tǒng)接地裝置。接地電阻不得大于4。電動(dòng)機(jī)的金屬底座、配電箱、開關(guān)箱的金屬體均應(yīng)與保護(hù)地線連接,配電室的進(jìn)線和出線處應(yīng)將架絕緣子鐵腳與配電室的接地裝置相連接作防雷接地,以防雷電波侵入。七、防護(hù)措施1、安全用電技術(shù)措施 1) 保證正確可靠的接地與接零必須按設(shè)計(jì)要求設(shè)置接地與接零,杜絕疏漏。所有接地、接零處必須保證可靠的電氣連接。保護(hù)PE必須采用綠/黃雙色線,嚴(yán)格與相線、工作零線相
29、區(qū)別,杜絕混用。2) 電氣設(shè)備的設(shè)置必須符合JGJ46-2005施工現(xiàn)場(chǎng)臨時(shí)用電安全技術(shù)規(guī)范的要求3) 電氣設(shè)備的安裝必須符合JGJ46-2005施工現(xiàn)場(chǎng)臨時(shí)用電安全技術(shù)規(guī)范的要求4) 電氣設(shè)備的防護(hù)必須符合JGJ46-2005施工現(xiàn)場(chǎng)臨時(shí)用電安全技術(shù)規(guī)范的要求5) 電氣設(shè)備的使用與維修必須符合JGJ46-2005施工現(xiàn)場(chǎng)臨時(shí)用電安全技術(shù)規(guī)范的要求6) 電氣設(shè)備的操作與維修人員必須符合JGJ46-2005施工現(xiàn)場(chǎng)臨時(shí)用電安全技術(shù)規(guī)范的要求2、安全用電組織措施1)建立臨時(shí)用電施工組織設(shè)計(jì)和安全用技術(shù)措施的編制,審核制度并建立相應(yīng)的技術(shù)檔案。2)建立技術(shù)交底制度、向?qū)I(yè)電工、各類用電人員介紹臨時(shí)用
30、電施工組織設(shè)計(jì)和安全用電措施的總體意圖。技術(shù)內(nèi)容和注意事項(xiàng),并應(yīng)在技術(shù)資料上履行交底人和被交底人的簽字手續(xù),寫明交底日期。3)建立安全檢測(cè)制度,從臨時(shí)用電工程竣工開始,定期對(duì)臨時(shí)用電工程進(jìn)行檢測(cè) 。主要內(nèi)容:接地電阻值、電氣設(shè)備絕緣電阻值、漏電保護(hù)工作參數(shù)等,以監(jiān)視臨時(shí)用電工程是否安全可靠,并作好檢測(cè)記錄。4)建立電氣維修制度,加強(qiáng)定期和日常維修工作,及時(shí)發(fā)現(xiàn)和清除隱患,并建立維修工作記錄,記錄維修時(shí)間、地點(diǎn)、設(shè)備內(nèi)容、技術(shù)措施、處理結(jié)果、維修人員、驗(yàn)收人員等。5)建立工程拆除制度,建筑工程竣工后,臨時(shí)工程的拆除有統(tǒng)一的組織和指揮。并須規(guī)定拆除時(shí)間、人員、程序、方法 、注意事項(xiàng)和防護(hù)措施等。6
31、)建立安全用電責(zé)任制,對(duì)臨時(shí)用電各部位的操作、監(jiān)護(hù)、維修分片分塊、分機(jī)落實(shí)到人,并輔以必要的獎(jiǎng)罰。7)建立安全教育和培訓(xùn)制度,定期對(duì)專業(yè)電工和各類用電人員進(jìn)行用電安全教育和培訓(xùn),經(jīng)過考核后合格持證上崗,禁止無證上崗或隨意串崗。八、臨時(shí)安全用電管理措施和防火措施1、 臨時(shí)安全用電管理措施1)場(chǎng)臨時(shí)供用電設(shè)施統(tǒng)一由機(jī)電管理部管理。2)本經(jīng)理部設(shè)置一名安全用電技術(shù)負(fù)責(zé)人。3)電氣操作及維修人員必須執(zhí)有電工執(zhí)照。 4)嚴(yán)禁無證人員私自接、拆電氣設(shè)備和線路。5)經(jīng)理部電氣負(fù)責(zé)人必須在作業(yè)前向電工進(jìn)行安全技術(shù)交底。6)工長(zhǎng)必須對(duì)所轄區(qū)域或分項(xiàng)工程的電氣人員在使用電氣設(shè)備做好安全技術(shù)交底。杜絕私自接線和毀壞
32、電氣設(shè)備的行為。7)現(xiàn)場(chǎng)臨時(shí)用電設(shè)施必須經(jīng)驗(yàn)收合格,方可使用,工期長(zhǎng)的每年要驗(yàn)收一次。8)經(jīng)理部每半月要組織一次全現(xiàn)場(chǎng)的安全用電檢查,發(fā)現(xiàn)隱患,要定人定措施定時(shí)間及時(shí)整改。9)電工工作必須在“臨時(shí)用電施工組織設(shè)計(jì)”的指導(dǎo)下進(jìn)行。10)電工在積極配合作業(yè)人員接好維修,值班,臨時(shí)供電工作的同時(shí)要做好電纜,配電箱,設(shè)備的絕緣遙測(cè)及記錄,漏電器(每半月一次)的試驗(yàn)記錄,接地極(重復(fù)接地,防雷接地)的電阻測(cè)試及記錄。做好維修工作記錄和電工值班記錄。工地要做好塔吊重復(fù)接地的隱檢記錄和電纜敷設(shè)方式的隱檢記錄。2、防火措施1) 電氣防火技術(shù)措施2)合理配置、整定、更換各種保護(hù)電器,對(duì)電路和設(shè)備的過載、短路故障
33、進(jìn)行可靠地保護(hù)。3)在電氣裝置和線路周圍不堆放易燃、易爆和強(qiáng)腐蝕介質(zhì);不使用火源。4)在電氣裝置相對(duì)集中的場(chǎng)所,如:變電所、配電室、發(fā)電機(jī)室等配置絕緣滅火器材等,并禁止煙火。5)加強(qiáng)電氣設(shè)備相間和相一地間絕緣,防止閃爍。6) 合理設(shè)置防雷裝置。7)電氣防火組織措施8)建立易燃、易爆物和強(qiáng)腐蝕介質(zhì)管理制度。9)建立電氣防火責(zé)任制,加強(qiáng)電氣防火重點(diǎn)場(chǎng)所煙火管制,并設(shè)置禁止煙火標(biāo)志。10)建立電氣防火教育制度,經(jīng)常進(jìn)行電氣防火知識(shí)教育和宣傳,提高個(gè)類用電人員電氣防火自覺性。11)建立電氣防火檢查制度,發(fā)現(xiàn)問題,及時(shí)處置。12)強(qiáng)化電氣防火領(lǐng)導(dǎo)體制,建立電氣防火隊(duì)伍。九、現(xiàn)場(chǎng)施工用電有關(guān)圖表附表一:主
34、要機(jī)械設(shè)備及照明用電一覽表序號(hào)設(shè)備名稱規(guī)格型號(hào)功率(KW)單位數(shù)量總功率(KW)啟動(dòng)方式1塔吊TC5610B40臺(tái)140交接啟動(dòng)2塔吊TC5013B40臺(tái)280交接啟動(dòng)3砼輸送泵HBT50C60臺(tái)2120Y降壓交接啟動(dòng)4插入式振搗器50mm/30mm2.5根820開關(guān)直接啟動(dòng)5平板振動(dòng)器2.2臺(tái)24.4開關(guān)直接啟動(dòng)6電焊機(jī)18臺(tái)8144開關(guān)直接啟動(dòng)7對(duì)焊機(jī)VNI100100臺(tái)1100交接啟動(dòng)8鋼筋切斷機(jī)QJ4012.2臺(tái)24.4開關(guān)直接啟動(dòng)9鋼筋彎曲機(jī)NJ4013臺(tái)26交接啟動(dòng)10電渣壓力焊VNI-10050臺(tái)2100開關(guān)直接啟動(dòng)11調(diào)直機(jī)7.5臺(tái)215交接啟動(dòng)12木工機(jī)械7套428開關(guān)直接啟動(dòng)13砂漿攪拌機(jī)350L7.5臺(tái)215交接啟動(dòng)14高壓泵40揚(yáng)程9臺(tái)436交接啟動(dòng)15高壓泵60揚(yáng)程9臺(tái)218交接啟動(dòng)16室外照明6017物料提升機(jī)7.564518工人生活區(qū)6019辦公室50附表二:主要電氣材料計(jì)劃名稱型 號(hào)單 位數(shù) 量備 注電纜VV-3×185+2
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 肝性腦病護(hù)理
- 成人有創(chuàng)機(jī)械通氣氣道內(nèi)吸引技術(shù)操作護(hù)理團(tuán)標(biāo)解讀
- 情緒管理報(bào)告范文
- 二零二五年度智能交通系統(tǒng)客戶引薦提成協(xié)議
- 二零二五年度機(jī)關(guān)炊事員健康體檢聘用合同
- 美容美發(fā)店員工入股分紅及管理權(quán)移交合同(2025年)
- 二零二五年度生物醫(yī)藥產(chǎn)業(yè)抵押貸款合同
- 二零二五年度跨境運(yùn)輸汽車指標(biāo)租賃管理協(xié)議
- 二零二五年度家庭房產(chǎn)贈(zèng)與及后續(xù)維護(hù)服務(wù)合同
- 二零二五年度航空航天知識(shí)產(chǎn)權(quán)使用授權(quán)合同
- 2025年湖南環(huán)境生物職業(yè)技術(shù)學(xué)院?jiǎn)握新殬I(yè)技能測(cè)試題庫(kù)一套
- 2025年廣東省深圳法院招聘書記員招聘144人歷年高頻重點(diǎn)模擬試卷提升(共500題附帶答案詳解)
- 新版統(tǒng)編版一年級(jí)道德與法治下冊(cè)全冊(cè)教案(完整版)教學(xué)設(shè)計(jì)含教學(xué)反思
- 2025年春季學(xué)期學(xué)校德育工作計(jì)劃安排表(完整版)
- 二手人防車位使用權(quán)轉(zhuǎn)讓協(xié)議書
- 新版醫(yī)療機(jī)構(gòu)消毒技術(shù)規(guī)范
- 報(bào)價(jià)單(報(bào)價(jià)單模板)
- 境外公共安全管理.ppt
- 貴人登天門吉時(shí)速查表(精編版)
- 小組成員職責(zé)分工
- 箱涵箱通施工監(jiān)理細(xì)則
評(píng)論
0/150
提交評(píng)論