ICS點擊此處添加ICS號

點擊此處添加中國標(biāo)準(zhǔn)文獻(xiàn)分類號

T/CEC

中國電力企業(yè)聯(lián)合會團體標(biāo)準(zhǔn)

T/CEC-XXXX

Technicalspecificationofexternalcircuit-breaker

forelectricitymeters

電能表用外置斷路器技術(shù)規(guī)范

點擊此處添加與國際標(biāo)準(zhǔn)一致性程度的標(biāo)識

(征求意見稿)

XXXX-XX-XX發(fā)布XXXX-XX-XX實施

發(fā)布

T/CEC—XXXX

T/CEC—XXXX

Technicalspecificationofcircuit-breakersforelectricitymeters

1Scope

Thisstandardstatestheclassification,typeofstructure,technicalrequirements,testmethodsandsoonof

theexternalcircuit-breakersforelectricitymeters(hereinafterreferredtoascircuit-breaker).

Thisstandardappliestoa.c.circuit-breakerforoperationat50Hz,60Hzor50/60Hz,hacingarated

voltagenotexceedingAC400?V,aratedcurrentnotexceeding125?A,andratedshort-circuitbreaking

capacitynotlessthan6000?A.

2Normativereferences

Thefollowingdocumentsareindispensablefortheapplicationthisdocument.Fordatedreference,only

theeditioncitedapplies.Forundatedreferences,thelatesteditionofthereferenceddocument(includingany

amendments)applies.

GB/T1804—2000GeneraltolerancesTolerancesforlinearandangulardimensionswithoutindividual

toleranceindications

GB10963.1—2005Electricalaccessories-Circuit-breakersforovercurrentprotectionforhouseholdand

similarinstallation-Part1:Circuit-breakersfora.c.operation

GB14048.1-2012Low-voltageswitchgearandcontrolgear--Part1:Generalrules

GB/T17626.2—2006Electromagneticcompatibility(EMC)--Testingandmeasurement

techniques--Electrostaticdischargeimmunitytest

GB/T17626.4—2008Electromagneticcompatibility-Testingandmeasurementtechniques--Electrical

fasttransient/burstimmunitytest

GB/T17626.5—2006Electromagneticcompatibility-Testingandmeasurementtechniques--Surge

immunitytest

GB17701—2008Circuit-breakerforequipment

GB/T19334—2003Dimensionoflow-voltageswitchgearandcontrolgear--Standardizedmountingon

railsformechanicalsupportofelectricaldevicesinswitchgearandcontrolgearinstallations

GB/T20645—2006Specificenvironmentalcondition--Technicalrequirementsoflow-voltage

apparatusesforplateau

GB/T26572—2011Requirementsofconcentrationlimitsforcertainrestrictedsubstancesinelectrical

andelectronicproducts

IEC62055-31:2005Electricitymetering--Paymentsystems--Part31:Particularrequirements--Static

paymentmetersforactiveenergy(classes1and2))

3Termsanddefinitions

1

T/CEC—XXXX

Forthepurposeofthisdocument,thetermsanddefinitionsgiveninGB14048.1—2012,aswellasthe

followingapply.

3.1

circuit-breaker

Mechanicalswitchingdevice,capableofmaking,carryingandbreakingcurrentsundernormalcircuit

conditionsandalsomaking,carryingforaspecifiedtimeandbreakingcurrentsunderspecifiedabnormal

circuitconditions(suchasshort-circuitcondition).

[SOURCE:GB14048.1,2.2.11]

3.2

externalcircuit-breakerforelectricitymeters

Thecircuit-breaker,installedexternallyandcooperatedwiththeelectricitymetertocontrolitsopening

andclosingoperation.

3.3

automaticopeningandclosingoperation

Openingandclosingoperationofthecircuit-breakerthat,bymeansofremotecontrolsignalsfrommaster

stationorotherequipment.

(Operationofopeningorclosingthecircuitbreakerbyremotecontrolsignalsfromthemasterstationor

otherequipment)

3.4

automaticopeningandclosingtime

Timemeasuredfromtheinstantatwhichthecircuit-breakerreceivestheopeningorclosingsignaltothe

instantwhenopeningorclosingoperationisaccomplished.

3.5

innershaftdrivemode

Drivingmodethatenableseachpoletooperatetogetherbymeansofintegralshaftinthecircuitbreaker.

3.6

power-ondelaytime

Theintervaltimebetweenthepowering-upandreadyforresponsetocontrolsignal.

(Thedurationfromtheinstantofpower-ontotheinstantatwhichthebreakerisreadytorespondtoa

controlsignal)

3.7

synchronoustime

2

T/CEC—XXXX

Thetimeperiodamongeachpoleofthecircuit-breakertocompleteitsopeningorclosingoperation.

(Timedifferenceamongallpolesofabreakertocompleteitsopeningorclosingoperation.)

4Classificationandperformancerequirements

4.1Classification

4.1.1

Accordingtothenumberofpoles

Accordingtothenumberofpoles:

a)1P+N,two-polecircuit-breakerswithoneprotectedpole;

b)2P,two-polecircuit-breakerswithtwoprotectedpoles;

c)3P,three-polecircuit-breakerswiththreeprotectedpoles;

d)3P+N,four-polecircuit-breakerswiththreeprotectedpoles;

e)4P,four-polecircuit-breakerswithfourprotectedpoles.

Note:Thepolewhichisnotaprotectedpolecanbe“switchedneutral”.

4.1.2

Accordingtoinstallationmethods(Accordingtothemethodofmounting)

a)Surface-type;

b)Flush-type;

c)Panelboardtype,alsoreferredtoasdistributionboardtype.

Note:Thesetypesmaybeintendedtoberailmounted.

4.1.3

(Accordingtothemethodofcontrol)

Accordingtothemethodofcontrol:

a)Manualcontrol,tocloseandopenmanually

b)Semi-automaticcontrol,toclosemanuallyandopenautomatically,

c)Automaticcontrol,tocloseandopenautomatically,

d)Semi-automaticorRemoteautomaticcontrolselectionmode,Havingmodeswitchforselectionof

manualorautomaticmode.Wheninmanualmode,functioningasinremotesemi-automaticcontrol

mode.Wheninautomaticmode,functioningasinremoteautomaticcontrolmode.

4.1.4

Accordingtotheinstantaneoustrippingcurrent

a)B-type;

b)C-type;

c)D-type.

Note:Theselectionofaparticulartypecandependontheinstallationrules.

3

T/CEC—XXXX

4.2.1Characteristicsrequirements

4.2.2Controlsignalvoltage

TheratedcontrolsignalvoltageshallbeAC220V.

4.2.2Ratedvoltage(Ue)

PreferredvaluesofratedvoltagearegiveninTable1.

Table1Preferredvaluesofratedvoltage

Ratedvoltageofcircuit-breakersRatedvoltageof

Circuit-breakerforuseinsystems230?V、circuit-breakersforusein

Circuitsupplyingthecircuit-breaker

s230/400?V、400?Vsystems240?V

VV

Singlephase(phasetoneutralorphase

230/

tophase)

Three-phasefour-wire230/

SinglepoleSingle-phase(phasetoneutral)

orthreephase,usingthreesingle-pole

230/400/

circuit-breakers(three-wireor

four-wire)

Singlephase(phasetoneutralor

230/

phasetophase)

Singlephase(phasetophase)400240

Two-pole

Singlephase(phasetophase,

/240

three-wire)

Threephase(four-wire)230/

Three-phase(three-wireor

Three-pole400240

four-wire)

Four-poleThree-phase(four-wire)400/

Note1:InIEC60038,thenetworkvoltagevalueof230/400?Vhasbeenstandardized.Thisvaluewillprogressively

supersedethevaluesof220/380?Vand240/415?V.

Note2:Whereverinthisstandardthereisareferenceto230?Vor400?V,theycanbereadas220?Vor240?V,380?Vor

415?V,respectively.

Note3:Whereverinthisstandardthereisareferenceto240?V,theycanbereadas200?V.

4.2.3Ratedinsulationvoltage(Ui)

Theratedinsulationvoltageshallnotbelessthan500?V.

4.2.4Ratedimpulsewithstandvoltage(Uimp)

Theratedimpulsewithstandvoltageshallnotbelessthan6?kV.

4.2.5Ratedcurrent(In)

Preferredvaluesofratedcurrentare:40?A,63?A,80?A,100?Aand125?A.

4

T/CEC—XXXX

4.2.6Ratedfrequency(fn)

Standardvaluesofratedfrequencyare50?Hzand60?Hz.

4.2.7Ratedshort-circuitcapacity(Icn)

Theratedshort-circuitbreakingcapacityshallnotbelessthan6000?A.

4.2.8Automaticclosingtime(tc)

tc≤3?s。

4.2.9Synchronoustime

Thesynchronoustimeofacircuit-breakershallmeettherequirementsofitsproductspecification.

4.2.10Power-ondelaytime(te)

Thepower-updelaytimeofcircuit-breakersshouldbesatisfiedwiththerequirementsoftheproduct

specification.

(Thepower-ondelaytimeofacircuitbreakershallmeettherequirementsofitsproductspecification.)

4.2.11Ratedcontrolsignalvoltage(Uc)

TheratedcontrolsignalvoltageshallbeAC220?V.

4.2.12Controlsignalcurrent(Ic)

Ic≤1?mA。

4.2.13Closingphaseleakagecurrent(IL1)

Steady-statecurrentlossperphaseshallbelessthan0.2?mAwhenthecontrolunitsareattheclosed

position.

4.2.14Openingphaseleakagecurrent(IL2)

Steady-statecurrentlossperphaseshallbevlessthan0.2?mAwhenthecontrolunitsareattheopen

position.

4.2.15Powerloss

Themaximumpermissiblevaluesperpoleofcircuit-breakersareindicatedinTable2.

Table2–Maximumpowerlossperpole

RangeofratedcurrentInMaximumpowerlossperpole

AW

32<In≤406.5

40<In≤508

50<In≤6311.5

5

T/CEC—XXXX

63<In≤10013.5

100<In≤12518

4.2.16Pollutiondegree

Circuit-breakerstothisstandardareintendedforenvironmentwithpollutiondegree2,i.e.normallyonly

non-conductivepollutionoccurs;occasionally,however,atemporaryconductivitycausedbycondensation

maybeexpected.

5Constructionalrequirements

5.1General

Circuit-breakersshallbesodesignedandconstructedthat,innormaluse,theirperformanceisreliableand

withoutdangertotheuserorsurroundings.Complianceischeckedbycarryingoutalltherelevanttests

specified.

5.2Appearance

Metalpartsofthecircuitbreakershallbeadequatelyplatedandcoatedagainstrusting.Metalpartsshall

nothavecracks,pittingorpeeling.Thesurfaceoftheplasticpartsshallbesmoothwithoutblisters,cracks,

dents,orotherdefects.

Externalpartswhichareaccessiblewhenoperatingthecircuit-breakershallbemadeofinsulating

material.

Dimensionsofcircuit-breakersarespecifiedinAnnexA

5.3Operatingmechanism

Theoperatingmechanismofacircuitbreakershallmeetthefollowingrequirements:

a)Theoperatingpartsmustbeflexibleandreliable,anditshallhaveatrip-freemechanism;

b)Forautomaticcontrolapoweroperatingmechanismshallbeprovided;

c)Themovingcontactscancometorestonlyintheclosedoropenposition,eveniftheoperating

memberistrippedinanintermediateposition

d)Thecircuitbreakershallbeprovidedwithanoperatinghandleformanuallyopeningandclosing,the

operatinghandlemustbesecuredreliably;

e)Goodinsulationbetweenoperatinghandleandlivepartsshouldberealizedtoensuresafety;

f)Themovingcontactsofallpolesofmultipolecircuitbreakersshallbesomechanicallycoupledthat

allpoles,excepttheswitchedneutral,makeandbreaksubstantiallytogether,evenifanoverload

occursononeprotectedpoleonly.

g)Theswitchedneutralpole,ifavailable,shallnotcloseafterandshallnotopenbeforetheprotected

poles;

h)Ifapolehavinganappropriateshortcircuitmakingandbreakingcapacityisusedasaneutralpole,

andthecircuitbreakerisindependentofmanualoperation,allpolesincludetheneutralpolemay

operatesubstantiallytogether;

6

T/CEC—XXXX

i)Exceptinmanualcontrolmode,whenreceivingatripcommand,theacircuitbreakershall

openautomaticallyandthemovingcontactsshallstayintheopenposition,andcouldn’tbeclosed

manually;

j)Abreakerunderclosingcommandshallallowmanuallyopenorclose.Afteropening,itshallstayin

openpositionincaseofapower-offandreenergizing;

Foracircuitbreakersupportingautomaticcontrolmode,theautomaticclosingmoduleshallemployatotally

enclosedconstructionwithinnershaftdriving,torealizeautomaticclosingfunctionandtoensuremoving

contactsstayintheopenpositionwhenmanuallyclosingabreakwhichisinopenstate.

5.4Isolationprotection

Eachpoleofcircuit-breakersshallreliablybreakintheopenposition.Circuit-breakersshallprovidein

theopenpositionanisolationdistanceinaccordancewiththerequirementsnecessarytosatisfytheisolating

function.Indicationoftheopenandclosedpositionofthemaincontactsshallbeprovidedbybothofthe

followingmeans:

a)thepositionoftheactuator;

b)aseparatemechanicalindicator.

5.5(Mechanicalindicatorandactuator)

Indicationoftheopenandclosedpositionofthemaincontactsshallbeprovided.

Itshallbepossibletoswitchthecircuit-breakeronandoffbyhand.Amechanicalindicatorisusedto

indicatethepositionofthecontacts,thisshallshowthesymbol“|”(or“closed”,“ON”,“red”)fortheclosed

positionandthesymbol“○”(or“open”,“OFF”,“green”)fortheopenposition(OFF).

Indicationofthecontactpositionshallbereliable.

Circuit-breakersshallbedesignedsothattheactuator,frontplateorcovercanonlybecorrectlyfittedina

mannerwhichensurescorrectindicationofthecontactposition.

5.6Modeselectionswitch

Forcircuit-breakerswithsemi-automaticandautomaticcontrolmode,amodeswitchshallbeprovidedin

thefronttoselectsemi-automaticcontrolmodeandremoteautomaticcontrolmode.

Modeswitchshallbedesignedonthefrontalsideofthecircuit-breaker,andwiththeidentificationof

“Automatic”and“Manual”forindicatingthemodeatpresent.

Protectionmeasuresshallbetakentopreventthemodeswitchfromtamperinganditshallnotbe

possibletoselectamodewithouttheaidofatool.

5.7Screws,current-carryingpartsandconnections

5.7.1Screwsandconnections

Connections,whetherelectricalormechanical,shallwithstandthemechanicalstressesoccurringin

normaluse.

5.7.2Electricalconnections

Electricalconnectionsshallbesodesignedthatcontactpressureisnottransmittedthroughinsulating

materialotherthanceramic,puremicaorothermaterialwithcharacteristicsnolesssuitable,unlessthereis

7

T/CEC—XXXX

sufficientresilienceinthemetallicpartstocompensateforanypossibleshrinkageoryieldingoftheinsulating

material.

5.7.3Current-carryingpartsandconnections

Current-carryingpartsincludingpartsintendedforprotectiveconductorsshallbemadeof

——copper;

——analloycontainingatleast58%copperforpartsworkedcold,oratleast50%copperforother

parts;

——othermetalorsuitablycoatedmetal,nolessresistanttocorrosionthancopperandhaving

mechanicalpropertiesnolesssuitable.

Note:

Incaseofusingferrousalloysorsuitablycoatedferrousalloys,compliancetoresistancetocorrosionis

checkedbyatestofresistancetorusting.Therequirementsofthissubclausedonotapplytocontacts,

magneticcircuits,heaterelements,bimetals,shunts,partsofelectronicdevicesortoscrews,nuts,washers,

clampingplates,similarpartsofterminalsandpartsofthetestcircuit.

5.8Terminalsforexternalconductors

Terminalsforexternalconductorsshallbesuchthattheconductorsmaybeconnectedsoastoensurethat

thenecessarycontactpressureismaintainedpermanently.Connectionarrangementsintendedforbusbar

connectionareadmissible,providedtheyarenotusedfortheconnectionofcables.Sucharrangementsmaybe

ofthebolt-ontype.Theterminalsshallbereadilyaccessibleundertheintendedconditionsofuse.

Circuit-breakersshallbeprovidedwithterminalswhichshallallowtheconnectionofcopperconductors

havingnominalcross-sectionalareasasshowninTable3.

Table3Connectablecross-sectionsofcopperconductorsforscrew-typeterminals

RatedcurrentInCross-sectionalareaofthewireS

Amm2

32<In≤5010

50<In≤6316

63<In≤8025

80<In≤10035

100<In≤12550

Foracurrentratingnotspecified,ifrequired,complianceischeckedbyrelevantnationalstandards.

Itisrequiredthat,forcurrentratingsuptoandincluding50A,terminalsbedesignedtoclampsolidconductorsandrigid

strandedconductors,flexibleconductorsmayalsobeused.

Themeansforclampingtheconductorsintheterminalsshallnotservetofixanyothercomponent.

Terminalsshallhaveadequatemechanicalstrength.Screwsandnutsforclampingtheconductorsshall

haveametricISOthreadorathreadcomparableinpitchandmechanicalstrength.

Terminalsshallbesodesignedthattheyclamptheconductorwithoutunduedamagetotheconductor.

Terminalsshallbesodesignedthattheyclamptheconductorreliablyandbetweenmetalsurfaces.

Terminalsshallbesodesignedorpositionedthatneitherarigidsolidconductornorawireofastranded

conductorcanslipoutwhiletheclampingscrewsornutsaretightened.

8

T/CEC—XXXX

Terminalsshallbesofixedorlocatedthat,whentheclampingscrewsornutsaretightenedorloosened,

theterminalsshallnotworkloosefromtheirfixingstocircuit-breakers.

Clampingscrewsornutsofterminalsintendedfortheconnectionofprotectiveconductorsshallbe

adequatelysecuredagainstaccidentalloosening.

Pillarterminalsshallallowfullinsertionandreliableclampingoftheconductor.

Complianceischeckedbyinspectionafterarigidconductorofthelargestcross-sectionalareaspecified

fortherelevantratedcurrentinTable3hasbeenfullyinsertedandfullyclampedbyapplyingthetorques

accordingtoTable4.

Table4–Screwthreaddiameterandappliedtorque

ScrewthreaddiameterTorque

mmNm

ⅠⅡⅢ

≤2.80.20.40.4

>2.8~≤3.00.250.50.5

>3.0~≤3.20.30.60.6

>3.2~≤3.60.40.80.8

>3.6~≤4.10.71.21.2

>4.1~≤4.70.81.81.8

>4.7~≤5.30.82.02.0

>5.3~≤6.01.22.53.0

>6.0~≤8.02.53.56.0

>8.0~≤10.0—4.010.0

>10.0~≤12.0——14.0

>12.0~≤15.0——19.0

>15.0~≤20.0——25.0

>20.0~≤24.0——36.0

>24.0——50.0

Note1.ColumnIappliestoscrewswithoutheadsifthescrew,whentightened,doesnotprotrudefromthehole,andto

otherscrewswhichcannotbetightenedbymeansofascrewdriverwithabladewiderthanthediameterofthescrew.

Note2.ColumnIIappliestootherscrewswhicharetightenedbymeansofascrewdriver.

Note3.ColumnIIIappliestoscrewsandnutswhicharetightenedbymeansotherthanascrewdriver.

Screwsandnutsofterminalsintendedfortheconnectionofexternalconductorsshallbeinengagement

withametalthreadandthescrewsshallnotbeofthetappingscrewtype.

5.9Signalfeedbackmode

ThecontrolsignalisanAC220Vsignal.Thecontrolunitispoweredbythecontrollineorbythephase

linetransientlyduringtheopeningandclosingoperations.Theleakagecurrentofphaseaftertheclosingor

openingoperationshallcomplywiththerequirementsof4.2.13and4.2.14respectively.

ThefeedbacksignalisanAC220Vsignal.Thefeedbacksignalispoweredbythephaselinefor

single-phasecircuit-breakers.Forthree-phasecircuit-breakersthefeedbacksignalispoweredbythreephases

andshallensureproperfeedbackevenunderanyonephaseloss..

9

T/CEC—XXXX

Thecontrolwireandthefeedbacksignalwireshallhaveacross-sectionalareanolessthan0.3?mm2,with

crimpedlugsatbothendstopreventinverseconnection.Specificationsmaybeinaccordancewiththe

manufacturer'sinstructions.

5.10Protectionagainstelectricshock

Circuit-breakersshallbesodesignedthat,whentheyaremountedandwiredasfornormaluse,liveparts

arenotaccessible.Externalparts,otherthanscrewsorothermeansforfixingcoversandlabels,shalleitherbe

ofinsulatingmaterialorbelinedthroughoutwithinsulatingmaterial,unlessthelivepartsarewithinan

internalenclosureofinsulatingmaterial.

Liningsshallbefixedinsuchawaythattheyarenotlikelytobelostduringinstallationofthe

circuit-breakers.Theyshallhaveadequatethicknessandmechanicalstrengthandshallprovideadequate

protectionatplaceswheresharpedgesoccur.

Inletopeningsforcablesorconduitsshalleitherbeofinsulatingmaterialorbeprovidedwithbushingsor

similardevicesofinsulatingmaterial.Suchdevicesshallbereliablyfixedandshallhaveadequatemechanical

strength.

Metallicoperatingmeansshallbeinsulatedfromlivepartsandtheirexposedconductivepartsshallbe

coveredbyinsulatingmaterial.Thisrequirementdoesnotapplytomeansforcouplinginsulatedoperating

meansofseveralpoles.Metalpartsofthemechanismshallnotbeaccessible.

6TechnicalRequirements

6.1Basicrequirements

6.1.1Ambientairtemperaturerange

TheambientairtemperatureshallcomplywiththosespecifiedinTable5.

Table5Ambientairtemperaturerange

No.ConditionTemperaturerange(℃)

1Specifiedoperatingtemperature-25~65

2Limittemperature-40~70

6.1.2Humidityrange

TherelativehumidityoftheairshallcomplywiththosespecifiedinTable6.

Table6RelativeAirHumidity

No.ConditionRelativehumidity

1Annualaverage<75%

10

T/CEC—XXXX

30days(thesedaysaredistributedinanaturalway

295%

throughouttheyear)

3Occasionallyoccuronotherdays85%

6.1.3Atmosphericconditions

63.0?kPa~106.0?kPa(海拔2000?m及以下),特殊訂貨要求除外。高海拔地區(qū)的要求應(yīng)按照標(biāo)準(zhǔn)

GB/T20645—2006中7.2.2的要求進行修正。

63.0kPa~106.0kPa(thealtitudedoesnotexceed2000?m),exceptforspecialorderrequirements.The

requirementsathigheraltitudesshallbemodifiedinaccordancewiththerequirementsof7.2.2of

GB/T20645-2006.

6.1.4In

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

評論

0/150

提交評論