版權(quán)說明:本文檔由用戶提供并上傳,收益歸屬內(nèi)容提供方,若內(nèi)容存在侵權(quán),請進行舉報或認領(lǐng)
文檔簡介
ICS27.010
CCSP46
團體標準
T/CECA-G00XX—202X
戶式空氣源熱泵三聯(lián)供系統(tǒng)技術(shù)規(guī)范
Technicalspecificationforcooling,heatingandhotwaterbyair-sourceheatpump
system
(征求意見稿)
202X-XX-XX發(fā)布202X-XX-XX實施
中國節(jié)能協(xié)會發(fā)布
T/CECA-G00XX—202X
目??次
前??言.............................................................................................................................................................III
1范圍................................................................................................................................................................1
2規(guī)范性引用文件...........................................................................................................................................1
3術(shù)語和定義...................................................................................................................................................1
4設(shè)計參數(shù)及計算...........................................................................................................................................2
4.1一般規(guī)定....................................................................................................................................................2
4.2冷負荷計算................................................................................................................................................2
4.3熱負荷計算................................................................................................................................................3
4.4新風負荷計算............................................................................................................................................3
4.5生活熱水負荷計算....................................................................................................................................4
5系統(tǒng)設(shè)計.......................................................................................................................................................4
5.1一般規(guī)定....................................................................................................................................................4
5.2系統(tǒng)要求....................................................................................................................................................5
5.3輸配系統(tǒng)....................................................................................................................................................6
5.4冷熱水管路系統(tǒng)........................................................................................................................................6
5.5水泵............................................................................................................................................................7
5.6水箱............................................................................................................................................................9
6末端設(shè)計.......................................................................................................................................................9
6.1一般規(guī)定....................................................................................................................................................9
6.2風機盤管....................................................................................................................................................9
6.3地暖............................................................................................................................................................9
7電氣系統(tǒng)與智能控制.................................................................................................................................10
7.1一般規(guī)定..................................................................................................................................................10
7.2系統(tǒng)集成控制器......................................................................................................................................10
7.3房間溫度控制器、室內(nèi)溫濕度傳感器、室外溫度傳感器..................................................................10
7.4配電系統(tǒng)..................................................................................................................................................11
7.5控制與監(jiān)測..............................................................................................................................................11
7.6安全防護..................................................................................................................................................11
8安裝施工與調(diào)試驗收.................................................................................................................................11
8.1一般規(guī)定..................................................................................................................................................11
8.2施工準備..................................................................................................................................................12
8.3主設(shè)備安裝..............................................................................................................................................12
8.4末端設(shè)備安裝..........................................................................................................................................12
8.5輸配管路及輔件安裝..............................................................................................................................12
8.6管道系統(tǒng)沖洗、試壓..............................................................................................................................13
8.7管道絕熱..................................................................................................................................................13
8.8電氣系統(tǒng)安裝..........................................................................................................................................13
8.9調(diào)試與驗收..............................................................................................................................................14
附錄A(資料性)間歇供冷民用建筑單位面積冷負荷概算值.........................................................17
I
T/CECA-G00XX—202X
附錄B(資料性)戶式三聯(lián)供系統(tǒng)示意圖.........................................................................................18
II
T/CECA-G00XX—202X
前??言
本文件按照GB/T1.1—2020《標準化工作導則第1部分:標準化文件的結(jié)構(gòu)和起草規(guī)則》的規(guī)定起
草。
請注意本文件的某些內(nèi)容可能涉及專利。本文件的發(fā)布機構(gòu)不承擔識別專利的責任。
本文件由中國節(jié)能協(xié)會提出并歸口。
本文件由中國節(jié)能協(xié)會熱泵專業(yè)委員會負責組織起草。
本文件起草單位:造夢者(浙江)科技有限公司、××××、××××等。
本文件主要起草人:。
III
T/CECA-G00XX—202X
戶式空氣源熱泵三聯(lián)供系統(tǒng)技術(shù)規(guī)范
1范圍
本文件規(guī)定了戶式空氣源熱泵三聯(lián)供系統(tǒng)(以下簡稱戶式三聯(lián)供系統(tǒng))的設(shè)計、施工、系統(tǒng)調(diào)試與
驗收。
本標準適用于單臺機組名義制熱量不大于100kW,以空氣源熱泵三聯(lián)供機組與同等數(shù)量的承壓式儲
能水箱及承壓式換熱熱水水箱組合而成的冷暖兩聯(lián)供加熱水系統(tǒng)。
2規(guī)范性引用文件
下列文件中的內(nèi)容通過文中的規(guī)范性引用而構(gòu)成本文件必不可少的條款。其中,注日期的引用文件,
僅該日期對應(yīng)的版本適用于本文件;不注日期的引用文件,其最新版本(包括所有的修改單)適用于本
文件。
GB/T9237制冷系統(tǒng)及熱泵安全與環(huán)境要求
GB50015-2019建筑給水排水設(shè)計標準
GB50057建筑物防雷設(shè)計規(guī)范
GB50242建筑給水排水及采暖工程施工質(zhì)量驗收規(guī)范
GB50254電氣裝置安裝工程低壓電器施工及驗收規(guī)范
GB50303建筑電氣工程施工質(zhì)量驗收規(guī)范
GB50411建筑節(jié)能工程施工質(zhì)量驗收標準
GB50736民用建筑供暖通風與空氣調(diào)節(jié)設(shè)計規(guī)范
GB50738通風與空調(diào)工程施工規(guī)范
JGJ142輻射供暖供冷技術(shù)規(guī)程
JGJ242住宅建筑電氣設(shè)計規(guī)范
RISN-TG039-2021戶式空氣源熱泵冷暖兩聯(lián)供工程技術(shù)導則
T/CECA-G0094-2020商業(yè)或工業(yè)用及類似用途的熱泵熱水集成系統(tǒng)設(shè)計、安裝與驗收規(guī)范
3術(shù)語和定義
T/CECA-G0094-2020界定的以及下列術(shù)語和定義適用于本文件。
3.1
空氣源熱泵三聯(lián)供機組cooling,heatingandhotwaterbyair-sourceheatpumpsystem
以空氣為冷、熱源,采用電動機驅(qū)動的蒸氣壓縮制冷循環(huán),既能在夏季制取空調(diào)用冷水和生活熱水,
也能在冬季制取供暖用熱水和生活熱水的熱泵機組。
3.2
承壓式儲能水箱pressureenergystoragehotwatertank
模塊承壓系統(tǒng)中,與空氣源熱泵機組循環(huán)加熱的承壓式水箱。
3.3
1
T/CECA-G00XX—202X
承壓式換熱熱水水箱pressurethermalexchanginghotwatertank
模塊承壓系統(tǒng)中,負責貯存熱水內(nèi)置盤管換熱的承壓式水箱。
3.4
換季三通閥Seasonalthree-wayvalve
系統(tǒng)中,在水箱一二次測,為提高制冷、熱效率,用于供回水口切換的閥門裝置。
3.5
一次泵系統(tǒng)primarywaterpumpingdistributionsystem
冷熱源側(cè)和負荷側(cè)共用一個循環(huán)泵組的水系統(tǒng)。
3.6
二次泵系統(tǒng)secondarywaterpumpingdistributionsystem
冷熱源側(cè)和負荷側(cè)分為兩個環(huán)路,并單獨配置循環(huán)泵組的水系統(tǒng)。
4設(shè)計參數(shù)及計算
4.1一般規(guī)定
4.1.1人員長期逗留區(qū)域室內(nèi)設(shè)計參數(shù)應(yīng)符合表1的規(guī)定。
表1人員長期逗留區(qū)域室內(nèi)設(shè)計參數(shù)
溫度相對濕度風速
參數(shù)熱舒適度等級
℃%m/s
I級22~24≥30≤0.2
供熱工況
II級18~22—≤0.2
I級24~2640~60≤0.25
供冷工況
II級26~28≤70≤0.3
注1:I級熱舒適度較高,II級熱舒適度一般。
注2:熱舒適度等級劃分見4.1.3。
4.1.2人員短期逗留區(qū)域室內(nèi)設(shè)計參數(shù)的供冷工況溫度宜比人員長期逗留區(qū)域高1℃~2℃,供熱
工況溫度宜比人員長期逗留區(qū)域低1℃~2℃,供冷工況的風速宜不大于0.5m/s,供熱工況的風速宜
不大于0.3m/s。
4.1.3供暖與空調(diào)室內(nèi)熱舒適性應(yīng)按GB/T18049的有關(guān)規(guī)定執(zhí)行,熱舒適度等級應(yīng)按表2劃分。
表2熱舒適度等級
熱舒適度等級PMVPPD
I級-0.5≤PMV≤0.510%
II級-1≤PMV<-0.5,0.5<PMV≤127%
注:PMV為預(yù)計平均熱感覺指數(shù),PPD為預(yù)計不滿意者的百分數(shù)。
4.2冷負荷計算
4.2.1戶式三聯(lián)供系統(tǒng)冷負荷計算應(yīng)符合GB50736的規(guī)定,宜采用專業(yè)軟件進行計算。
2
T/CECA-G00XX—202X
4.2.2按各房間冷負荷選用末端設(shè)備。間歇使用戶式三聯(lián)供系統(tǒng)的房間,間歇系數(shù)應(yīng)選取1.5~2.0。
4.2.3按戶內(nèi)總冷負荷選用冷熱源設(shè)備。戶內(nèi)總冷負荷應(yīng)按下列情況確定:
a)當系統(tǒng)設(shè)有自控時,將同時使用的各個房間逐時冷負荷累加,得出建筑物冷負荷的逐時值,取
其中的最大值;
b)當基礎(chǔ)數(shù)據(jù)不全時,可將各房間冷負荷按公式(1)進行概算后累加:
式中:
?L=?L×?×?#……1
QL——冷負荷,單位為瓦(W);
2
qL——單位面積冷負荷概算值,單位為瓦每平方米(W/m),見附錄A;
S——供冷區(qū)域面積,單位為平方米(m2);
A——同時使用系數(shù),當所有房間的空調(diào)需同時使用時取1.0,當無法確定同時使用的各房
間時取0.5~0.7。
4.2.4若設(shè)置新風系統(tǒng),產(chǎn)生的新風冷負荷應(yīng)計入戶內(nèi)總冷負荷,按4.4計算。
4.2.5戶內(nèi)總冷負荷應(yīng)考慮風機、風管、水泵、管道和水箱溫升導致的附加冷負荷。
4.3熱負荷計算
4.3.1戶式三聯(lián)供系統(tǒng)熱負荷計算應(yīng)符合GB50736的規(guī)定,宜采用專業(yè)軟件進行計算。
4.3.2民用建筑的戶內(nèi)供暖總熱負荷應(yīng)包含:
a)外圍護結(jié)構(gòu)的傳熱耗熱量;
b)由外門、窗縫隙滲入室內(nèi)的冷空氣耗熱量;
c)當外門開啟時經(jīng)外門進入室內(nèi)的冷空氣耗熱量;
d)戶間傳熱量。
4.3.3結(jié)合開機率等確定冬季間歇供暖戶內(nèi)供暖總熱負荷,宜為冬季連續(xù)供暖戶內(nèi)供暖總熱負荷的
1.05倍~1.20倍。
4.3.4若設(shè)置新風系統(tǒng),產(chǎn)生的新風負荷應(yīng)計入戶內(nèi)供暖總熱負荷,按4.4計算。
4.3.5輻射面的傳熱量計算應(yīng)符合JGJ142的有關(guān)規(guī)定。
4.4新風負荷計算
4.4.1采用戶式三聯(lián)供系統(tǒng)的建筑,其新風補充方式主要有:
a)門、窗的自然滲透;
b)新風未經(jīng)處理,由小型風機直接送風;
c)新風經(jīng)新風空氣處理機組處理后送入室內(nèi);
d)新風經(jīng)熱回收裝置處理后送入室內(nèi)。
4.4.2新風負荷的計算應(yīng)符合下列規(guī)定。
a)新風未經(jīng)處理直接進入室內(nèi),其負荷全部由房間末端設(shè)備負擔時,新風負荷按公式(2)計算:
式中:
??=0.28×?v×?a×|?w??n|………………2
Qf——新風負荷,單位為瓦(W);
3
qv——新風量,單位為立方米每小時(m/h);
3
ρa——新風密度,單位為千克每立方米(kg/m);
hw——室外計算參數(shù)的比焓,單位為千焦每千克(kJ/kg);
hn——室內(nèi)計算參數(shù)的比焓,單位為千焦每千克(kJ/kg)。
3
T/CECA-G00XX—202X
b)當新風經(jīng)新風空氣處理機組處理到室內(nèi)空氣等焓值時,新風負荷全部由新風空氣處理機組負擔,
房間末端設(shè)備不負擔新風負荷;當沒有處理到室內(nèi)空氣等焓值,還需要房間末端設(shè)備進一步處
理至室內(nèi)空氣狀態(tài)焓值時,這部分新風負荷由房間末端設(shè)備負擔,可按公式(2)計算,此時
室外計算參數(shù)的比焓按新風空氣處理機組后的新風焓值。
c)新風經(jīng)熱回收裝置處理后,一般達不到室內(nèi)空氣狀態(tài)等焓值。這部分新風送入房間,并通過專
門的新風空氣處理機組處理時,新風負荷由該空氣處理機組負擔;未設(shè)置新風空氣處理機組時,
新風負荷由房間末端設(shè)備負擔;可按公式(2)計算,此時室外計算參數(shù)的比焓按熱回收裝置
后新風焓值。
4.5生活熱水負荷計算
4.5.1空氣源熱泵三聯(lián)供機組產(chǎn)水量應(yīng)滿足GB/T23137-2020相關(guān)規(guī)定。
4.5.2空氣源熱泵三聯(lián)供機組產(chǎn)水能力按下列規(guī)定:
a)當使用承壓式換熱熱水水箱時,給水定額流量應(yīng)綜合考慮衛(wèi)生器具的同時使用系數(shù),滿足不
低于各衛(wèi)生器具同時使用流量之和,設(shè)計水箱所需換熱量按公式(3)計算:
T………………(3)
式中:
?i=