目次
1總則········································································1
2術(shù)語········································································2
3基本規(guī)定···································································5
4建筑與圍護結(jié)構(gòu)熱工····················································6
4.1一般規(guī)定································································6
4.2建筑設(shè)計································································6
4.3圍護結(jié)構(gòu)熱工設(shè)計······················································9
4.4圍護結(jié)構(gòu)熱工性能的權(quán)衡判斷········································13
5供暖通風(fēng)與空氣調(diào)節(jié)··················································15
5.1一般規(guī)定·······························································15
5.2冷源與熱源····························································16
5.3供暖、空調(diào)冷熱水輸配系統(tǒng)··········································27
5.4通風(fēng)及空調(diào)風(fēng)系統(tǒng)·····················································33
5.5末端系統(tǒng)·······························································37
5.6監(jiān)測、控制與計量·····················································37
6給水排水·································································40
6.1一般規(guī)定·······························································40
6.2給水排水系統(tǒng)··························································40
6.3熱水系統(tǒng)·······························································41
7電氣·······································································44
7.1一般規(guī)定·······························································44
7.2供配電系統(tǒng)····························································44
7.3電氣產(chǎn)品選擇與控制··················································44
7.4照明····································································45
7.5電能監(jiān)測與計量·······················································46
8可再生能源利用························································47
8.1一般規(guī)定·······························································47
8.2太陽能系統(tǒng)····························································47
8.3地源熱泵系統(tǒng)··························································48
8.4空氣源熱泵系統(tǒng)·······················································49
附錄A管道與設(shè)備絕熱厚度···········································51
本標(biāo)準(zhǔn)用詞說明·····························································54
引用標(biāo)準(zhǔn)名錄································································55
附:條文說明································································57
1總則
1.0.1為了貫徹國家和河北省節(jié)能降碳的政策要求,促進河北省公
共建筑節(jié)能技術(shù)發(fā)展,提高能源利用效率,充分利用可再生能源,
進一步降低公共建筑能耗,結(jié)合河北省氣候特點和具體情況,制定
本標(biāo)準(zhǔn)。本標(biāo)準(zhǔn)公共建筑平均節(jié)能率為72%。
1.0.2本標(biāo)準(zhǔn)適用于河北省新建、擴建和改建的公共建筑節(jié)能設(shè)計。
1.0.3當(dāng)建筑高度超過100m或單棟建筑地上建筑面積大于20萬m2
時,除應(yīng)符合本標(biāo)準(zhǔn)規(guī)定外,還應(yīng)組織專家對其節(jié)能設(shè)計進行專項
論證。
1.0.4公共建筑節(jié)能設(shè)計除應(yīng)符合本標(biāo)準(zhǔn)的規(guī)定外,尚應(yīng)符合國家
和河北省現(xiàn)行有關(guān)標(biāo)準(zhǔn)的規(guī)定。
1
2術(shù)語
2.0.1體形系數(shù)shapefactor
建筑物與室外空氣直接接觸的外表面積與其所包圍的體積的比
值。外表面積不包括地面和不供暖公共空間內(nèi)墻的面積。
2.0.2透光幕墻transparentcurtainwall
可見光可直接透射入室內(nèi)的幕墻。
2.0.3單一立面窗墻面積比singlefacadewindowtowallratio
建筑某一個立面的窗戶洞口面積與該立面的總面積之比,簡稱
窗墻面積比。
2.0.4可見光透射比visibletransmittance
透過透光材料的可見光光通量與投射在其表面上的可見光光
通量之比。
2.0.5太陽得熱系數(shù)(SHGC)solarheatgaincoefficient
通過透光圍護結(jié)構(gòu)(門窗或透光幕墻)的太陽輻射室內(nèi)得熱量
與投射到透光圍護結(jié)構(gòu)(門窗或透光幕墻)外表面上的太陽輻射量
的比值。太陽輻射室內(nèi)得熱量包括太陽輻射通過輻射透射的得熱量
和太陽輻射被構(gòu)件吸收再傳入室內(nèi)的得熱量兩部分。
2.0.6圍護結(jié)構(gòu)熱工性能權(quán)衡判斷buildingenvelopethermal
performancetrade-off
當(dāng)建筑設(shè)計不能完全滿足圍護結(jié)構(gòu)熱工設(shè)計規(guī)定的指標(biāo)要求
時,計算并比較參照建筑和設(shè)計建筑的全年供暖和空氣調(diào)節(jié)能耗,
判定圍護結(jié)構(gòu)的總體熱工性能是否符合節(jié)能設(shè)計要求的方法,簡稱
權(quán)衡判斷。
2.0.7參照建筑referencebuilding
進行圍護結(jié)構(gòu)熱工性能權(quán)衡判斷時,作為計算滿足標(biāo)準(zhǔn)要求的
2
全年供暖和空氣調(diào)節(jié)能耗用的基準(zhǔn)建筑。
2.0.8性能系數(shù)(COP)coefficientofperformance
制冷或制熱工況下,機組以同一單位表示的制冷(熱)量除以
總輸入電功率得出的比值。
2.0.9綜合部分負(fù)荷性能系數(shù)(IPLV)integratedpartloadvalue
基于冷水(熱泵)機組或空調(diào)(熱泵)機組部分負(fù)荷時的性能
系數(shù)值,經(jīng)加權(quán)計算獲得的表示該機組部分負(fù)荷效率的單一數(shù)值。
2.0.10制冷季節(jié)能效比(SEER)seasonalenergyefficiencyratio
在制冷季節(jié)中,空調(diào)機(組)進行制冷運行時從室內(nèi)除去的熱
量總和與消耗的電量總和之比。
2.0.11全年性能系數(shù)(APF)annualperformancefactor
在制冷季節(jié)及制熱季節(jié)中,機組進行制冷(熱)運行時從室內(nèi)
除去的熱量及向室內(nèi)送入的熱量總和與同一期間內(nèi)消耗的電量總和
之比。
2.0.12制冷性能系數(shù)(EER)energyefficiencyratio
在規(guī)定的試驗條件下,制冷設(shè)備的制冷量與其消耗功率之比。
2.0.13飄水率driftratio
單位時間內(nèi)從冷卻塔出風(fēng)口飄出的水量與進塔水量之比。
2.0.14耗電輸熱比(EHR-h)electricityconsumptiontotransferred
heatquantityratio
設(shè)計工況下,集中供暖系統(tǒng)循環(huán)水泵總功耗(kW)與設(shè)計熱負(fù)
荷(kW)的比值。
2.0.15耗電輸冷(熱)比[EC(H)R-a]electricityconsumptionto
transferredcooling(heating)quantityratio
設(shè)計工況下,空調(diào)冷(熱)水系統(tǒng)循環(huán)水泵總功耗(kW)與設(shè)
3
計冷(熱)負(fù)荷(kW)的比值。
2.0.16風(fēng)道系統(tǒng)的單位風(fēng)量耗功率(WS)energyconsumptionper
unitairvolumeofairductsystem
設(shè)計工況下,空調(diào)、通風(fēng)的風(fēng)道系統(tǒng)輸送單位風(fēng)量(m3/h)所
消耗的電功率(W)。
2.0.17照明功率密度(LPD)lightingpowerdensity
單位面積上一般照明的安裝功率(W/m2)(包括光源、鎮(zhèn)流器
或變壓器等附屬用電器件)。
2.0.18太陽能光伏發(fā)電系統(tǒng)solarphotovoltaic(PV)system
利用太陽能電池的光伏效應(yīng)將太陽輻射能直接轉(zhuǎn)換成電能的
發(fā)電系統(tǒng)。
2.0.19光伏與建筑一體化buildingintegratedphotovoltaic(BIPV)
在建筑上安裝光伏系統(tǒng),并通過專門設(shè)計,實現(xiàn)光伏系統(tǒng)與建
筑的結(jié)合。
2.0.20太陽能熱利用系統(tǒng)solarthermalsystem
將太陽輻射能轉(zhuǎn)化為熱能,為建筑供熱水,供熱水及供暖,或
供熱水、供暖或(及)供冷的系統(tǒng)。分為太陽能熱水系統(tǒng)、太陽能
供暖系統(tǒng)以及太陽能供暖空調(diào)等復(fù)合應(yīng)用系統(tǒng)。
2.0.21地源熱泵系統(tǒng)ground-sourceheatpumpsystem
以巖土體、地下水或地表水為低溫?zé)嵩?,由水源熱泵機組、地
熱能交換系統(tǒng)、建筑物內(nèi)系統(tǒng)組成的供熱空調(diào)系統(tǒng)。
2.0.22空氣源熱泵系統(tǒng)airsourceheatpumpsystem
以空氣作為低溫?zé)嵩矗煽諝庠礋岜脵C組、輸配系統(tǒng)和建筑物
內(nèi)系統(tǒng)組成的供熱空調(diào)系統(tǒng)。根據(jù)建筑物內(nèi)系統(tǒng)不同,分為空氣源
熱泵熱風(fēng)系統(tǒng)和空氣源熱泵熱水系統(tǒng)。
4
3基本規(guī)定
3.0.1公共建筑應(yīng)進行節(jié)能設(shè)計,采用下列方法降低建筑能耗:
1根據(jù)河北省不同地區(qū)的氣候特征,在保證室內(nèi)熱環(huán)境質(zhì)量的
前提下,通過建筑與圍護結(jié)構(gòu)熱工設(shè)計,控制建筑物的全年供暖和
空氣調(diào)節(jié)能耗;
2通過供暖系統(tǒng)的節(jié)能設(shè)計,提高供暖系統(tǒng)的熱源效率和輸送
效率;
3通過建筑遮陽、自然通風(fēng)和空調(diào)系統(tǒng)的節(jié)能設(shè)計,降低夏季
的空調(diào)能耗;
4通過自然采光、給水排水及電氣系統(tǒng)的節(jié)能設(shè)計,降低建筑
物給水排水、照明和電氣系統(tǒng)的能耗;
5通過充分利用可再生能源,進一步降低建筑物一次能源的消耗。
3.0.2建設(shè)項目的可行性研究報告、建設(shè)方案和初步設(shè)計文件應(yīng)包
含建筑能耗、可再生能源利用及建筑碳排放分析報告。施工圖設(shè)計
應(yīng)明確建筑節(jié)能措施及可再生能源利用系統(tǒng)運營管理的技術(shù)要求。
3.0.3外墻保溫系統(tǒng)應(yīng)與基層墻體可靠連接,在基層正常變形以及
承受自重、風(fēng)荷載和室外氣候的長期反復(fù)作用下,不應(yīng)產(chǎn)生裂縫、
空鼓。外墻保溫系統(tǒng)在正常使用中或發(fā)生地震時不應(yīng)發(fā)生脫落,并
應(yīng)符合相關(guān)標(biāo)準(zhǔn)的規(guī)定。
3.0.4外墻保溫系統(tǒng)應(yīng)考慮環(huán)境因素,采取可靠防腐措施,在使用
過程中應(yīng)對外墻保溫系統(tǒng)定期檢測、維護。
3.0.5在滿足本標(biāo)準(zhǔn)及國家現(xiàn)行有關(guān)標(biāo)準(zhǔn)的前提下,鼓勵采用新技
術(shù)、新工藝、新材料、新產(chǎn)品。
5
4建筑與圍護結(jié)構(gòu)熱工
4.1一般規(guī)定
4.1.1公共建筑分類應(yīng)符合下列規(guī)定:
1單棟建筑面積大于300m2的建筑,或單棟建筑面積小于或等
于300m2但總建筑面積大于1000m2的建筑群,應(yīng)為甲類公共建筑;
2單棟建筑面積小于或等于300m2的建筑,應(yīng)為乙類公共建筑。
4.1.2河北省分為三個建筑熱工設(shè)計區(qū)屬,應(yīng)按表4.1.2確定。
表4.1.2河北省主要城鎮(zhèn)建筑熱工設(shè)計區(qū)屬
氣候區(qū)屬代表性城鎮(zhèn)
寒冷B區(qū)(2B)邯鄲邢臺衡水石家莊滄州保定廊坊泊頭
寒冷A區(qū)(2A)唐山樂亭秦皇島張家口承德懷來青龍
嚴(yán)寒C區(qū)(1C)圍場豐寧隆化沽源康保張北尚義赤城崇禮蔚縣
4.1.3建筑規(guī)劃應(yīng)充分利用場地的自然資源條件,充分利用日照并
避開冬季主導(dǎo)風(fēng)向,組織好自然通風(fēng)。
4.1.4建筑物的主朝向宜選擇南北向或接近南北向,建筑體形宜規(guī)
整緊湊,避免過多的凹凸變化。
4.1.5建筑總平面布置和建筑物內(nèi)部的平面設(shè)計,在保證使用功能
的同時,應(yīng)考慮熱環(huán)境的合理分區(qū),合理確定能源設(shè)備機房的位置,
盡可能縮短冷、熱水系統(tǒng)和風(fēng)系統(tǒng)等的輸送距離。
4.2建筑設(shè)計
4.2.1公共建筑體形系數(shù)應(yīng)符合表4.2.1的規(guī)定。
6
表4.2.1公共建筑體形系數(shù)限值
單棟建筑面積A(m2)建筑體形系數(shù)
300<A≤800≤0.50
A>800≤0.40
4.2.2嚴(yán)寒地區(qū)甲類公共建筑各單一立面窗墻面積比(包括透光幕
墻)均不宜大于0.60;寒冷地區(qū)甲類公共建筑各單一立面窗墻面積
比(包括透光幕墻)均不宜大于0.70。
4.2.3透光圍護結(jié)構(gòu)應(yīng)符合下列規(guī)定:
1當(dāng)單一立面窗墻面積比小于0.40時,透光材料的可見光透射
比不應(yīng)小于0.60;當(dāng)單一立面窗墻面積比大于等于0.40時,透光材
料的可見光透射比不應(yīng)小于0.40;
2真空玻璃應(yīng)符合現(xiàn)行國家標(biāo)準(zhǔn)《真空玻璃》GB/T38586的規(guī)
定。
4.2.4單一立面窗墻面積比的計算應(yīng)符合下列規(guī)定:
1凸凹立面朝向應(yīng)按其所在立面的朝向計算;
2樓梯間和電梯間的外墻和外窗均應(yīng)參與計算;
3外凸窗的頂部、底部和側(cè)墻的面積不應(yīng)計入外墻面積;
4外墻上的凸窗,當(dāng)頂部和側(cè)面為不透光構(gòu)造時,凸窗面積應(yīng)
按窗洞口面積計算;當(dāng)頂部或側(cè)面為透光構(gòu)造時,凸窗面積應(yīng)按透
光部分實際面積計算。
4.2.5寒冷地區(qū)建筑的東、南、西向外窗(包括透光幕墻)宜采取
遮陽措施,當(dāng)設(shè)置外遮陽時應(yīng)兼顧通風(fēng)及冬季日照。
4.2.6甲類公共建筑的屋面透光部分面積不應(yīng)大于屋面總面積的
20%。
4.2.7建筑立面朝向的劃分應(yīng)符合下列規(guī)定:
7
1北向應(yīng)為北偏西60°至北偏東60°;
2南向應(yīng)為南偏西30°至南偏東30°;
3西向應(yīng)為西偏北30°至西偏南60°(包括西偏北30°和西偏南
60°);
4東向應(yīng)為東偏北30°至東偏南60°(包括東偏北30°和東偏南
60°)。
4.2.8單一立面外窗(包括透光幕墻)的有效通風(fēng)換氣面積應(yīng)符合
下列規(guī)定:
1甲類公共建筑外窗(包括透光幕墻)應(yīng)設(shè)可開啟窗扇,其有
效通風(fēng)換氣面積不宜小于所在房間外墻面積的10%;
2乙類公共建筑外窗(包括透光幕墻)的有效通風(fēng)換氣面積不
宜小于窗面積的30%;
3當(dāng)主要功能房間外窗(包括透光幕墻)的有效通風(fēng)換氣面積
不滿足上述要求時,應(yīng)設(shè)置通風(fēng)換氣裝置。
4.2.9外窗(包括透光幕墻)的有效通風(fēng)換氣面積應(yīng)為開啟扇面積
和窗開啟后的空氣流通界面面積的較小值。
4.2.10嚴(yán)寒地區(qū)建筑的外門應(yīng)設(shè)置門斗;寒冷地區(qū)建筑面向冬季主
導(dǎo)風(fēng)向的外門應(yīng)設(shè)置門斗,其他外門宜設(shè)置門斗或應(yīng)采取其他減少
冷風(fēng)滲透的措施。
4.2.11建筑中庭應(yīng)充分利用自然通風(fēng)降溫,必要時應(yīng)設(shè)置機械通風(fēng)
裝置。
4.2.12建筑設(shè)計應(yīng)充分利用天然采光。天然采光不能滿足照明要求
的場所,宜采用導(dǎo)光、反光等裝置將自然光引入室內(nèi),作為人工照
明的補充。
4.2.13地下車庫等公共空間宜設(shè)置導(dǎo)光管等天然采光設(shè)施。導(dǎo)光管
8
采光系統(tǒng)在漫射光條件下的系統(tǒng)效率應(yīng)大于0.50,其設(shè)計計算應(yīng)符
合現(xiàn)行行業(yè)標(biāo)準(zhǔn)《導(dǎo)光管采光系統(tǒng)技術(shù)規(guī)程》JGJ/T374的規(guī)定。
4.2.14電梯應(yīng)具備節(jié)能運行功能。兩臺及以上電梯集中排列時,應(yīng)
設(shè)置群控措施。電梯應(yīng)具備無外部召喚且轎廂內(nèi)一段時間無預(yù)置指
令時,自動轉(zhuǎn)為節(jié)能運行模式的功能。
4.2.15自動扶梯、自動人行步道應(yīng)具備空載時暫?;虻退龠\轉(zhuǎn)的功
能。
4.3圍護結(jié)構(gòu)熱工設(shè)計
4.3.1不同地區(qū)甲類公共建筑圍護結(jié)構(gòu)熱工性能應(yīng)分別符合表
4.3.1-1、表4.3.1-2和表4.3.1-3的規(guī)定。
表4.3.1-1嚴(yán)寒C區(qū)甲類公共建筑圍護結(jié)構(gòu)熱工性能限值
傳熱系數(shù)K[W/(m2?K)]
圍護結(jié)構(gòu)部位
體形系數(shù)≤0.300.30<體形系數(shù)≤0.50
屋面≤0.30≤0.25
外墻(包括非透光幕墻)≤0.38≤0.35
底面接觸室外空氣的架空或外挑樓板≤0.38≤0.35
地下車庫(或非供暖房間)與供暖房間之間的
≤0.70≤0.70
樓板
非供暖樓梯間與供暖房間之間的隔墻≤1.00≤1.00
窗墻面積比≤0.40≤2.00≤1.70
單一立面外窗0.40<窗墻面積比≤0.50≤1.70≤1.60
(包括透光幕0.50<窗墻面積比≤0.70≤1.50≤1.50
墻)0.70<窗墻面積比≤0.80≤1.40≤1.30
窗墻面積比>0.80≤1.30≤1.20
9
續(xù)表4.3.1-1
傳熱系數(shù)K[W/(m2?K)]
圍護結(jié)構(gòu)部位
體形系數(shù)≤0.300.30<體形系數(shù)≤0.50
屋面透光部分(屋面透光部分面積≤20%)≤2.00
圍護結(jié)構(gòu)部位保溫材料層熱阻R[(m2?K)/W]
周邊地面≥1.10
供暖地下室與土壤接觸的外墻≥1.50
變形縫(兩側(cè)墻內(nèi)保溫時)≥1.20
注:地下室外墻熱阻系指土壤以內(nèi)各層材料的熱阻之和。
表4.3.1-2寒冷地區(qū)甲類公共建筑圍護結(jié)構(gòu)熱工性能限值
傳熱系數(shù)K[W/(m2?K)]
圍護結(jié)構(gòu)部位
體形系數(shù)≤0.300.30<體形系數(shù)≤0.50
屋面≤0.40≤0.35
外墻(包括非透光幕墻)≤0.50≤0.45
底面接觸室外空氣的架空或外挑樓板≤0.50≤0.45
地下車庫(或非供暖房間)與供暖房間之間的≤1.00≤1.00
非供暖樓梯間與供樓暖板房間之間的隔墻≤1.20≤1.20
窗墻面積比≤0.30≤2.00≤1.90
0.30<窗墻面積比≤0.40≤2.00≤1.80
單一立面外窗0.40<窗墻面積比≤0.50≤1.90≤1.70
(包括透光幕0.50<窗墻面積比≤0.60≤1.80≤1.60
墻)0.60<窗墻面積比≤0.70≤1.70≤1.60
0.70<窗墻面積比≤0.80≤1.50≤1.40
窗墻面積比>0.80≤1.30≤1.30
屋面透光部分(屋面透光部分面積≤20%)≤2.40
≤2.40
10
續(xù)表4.3.1-2
圍護結(jié)構(gòu)部位保溫材料層熱阻R[(m2?K)/W]
周邊地面≥0.60
供暖、空調(diào)地下室外墻(與土壤接觸的墻)≥0.90
變形縫(兩側(cè)墻內(nèi)保溫時)≥0.90
注:地下室外墻熱阻系指土壤以內(nèi)各層材料的熱阻之和。
表4.3.1-3寒冷地區(qū)甲類公共建筑外窗(包括透光幕墻)太陽得熱系數(shù)限值
圍護結(jié)構(gòu)部位太陽得熱系數(shù)SHGC(東、南、西向/北向)
0.20<窗墻面積比≤0.30≤0.48/—
單一立面0.30<窗墻面積比≤0.50≤0.40/—
外窗(包括0.50<窗墻面積比≤0.60≤0.35/—
透光幕墻)0.60<窗墻面積比≤0.80≤0.30/0.40
窗墻面積比>0.80≤0.25/0.40
屋面透光部分(屋面透光部分面積≤20%)≤0.35
注:1當(dāng)設(shè)置了展開或關(guān)閉后可以全部遮蔽窗戶的活動式外遮陽時,應(yīng)認(rèn)定滿足本條太陽得熱
系數(shù)限值要求。
2有建筑遮陽時,透光圍護結(jié)構(gòu)太陽得熱系數(shù)為包括遮陽(不含內(nèi)遮陽)的綜合太陽得熱
系數(shù),計算方法應(yīng)符合現(xiàn)行國家標(biāo)準(zhǔn)《建筑節(jié)能與可再生能源利用通用規(guī)范》GB55015的規(guī)定。
4.3.2乙類公共建筑的圍護結(jié)構(gòu)熱工性能應(yīng)符合表4.3.2-1和表
4.3.2-2的規(guī)定。
表4.3.2-1乙類公共建筑屋面、外墻、樓板熱工性能限值
傳熱系數(shù)K[W/(m2·K)]
圍護結(jié)構(gòu)部位
嚴(yán)寒C區(qū)寒冷地區(qū)
屋面≤0.45≤0.55
外墻(包括非透光幕墻)≤0.50≤0.60
11
續(xù)表4.3.2-1
傳熱系數(shù)K[W/(m2·K)]
圍護結(jié)構(gòu)部位
嚴(yán)寒C區(qū)寒冷地區(qū)
底面接觸室外空氣的架空或外挑樓板≤0.50≤0.60
地下非供暖房間和供暖房間之間的樓板≤0.70≤1.00
表4.3.2-2乙類公共建筑外窗(包括透光幕墻)熱工性能限值
圍護結(jié)構(gòu)部位傳熱系數(shù)K[W/(m2?K)]太陽得熱系數(shù)SHGC
外窗(包括透光幕墻)嚴(yán)寒C區(qū)寒冷地區(qū)寒冷地區(qū)
單一立面外窗
≤≤
(包括透光幕墻)2.202.50—
屋面透光部分
≤2.20≤2.50≤0.40
(屋面透光部分面積≤20%)
4.3.3建筑圍護結(jié)構(gòu)熱工性能參數(shù)計算應(yīng)符合下列規(guī)定:
1外墻的傳熱系數(shù)應(yīng)為包括結(jié)構(gòu)性熱橋在內(nèi)的平均傳熱系數(shù),
應(yīng)按現(xiàn)行國家標(biāo)準(zhǔn)《建筑節(jié)能與可再生能源利用通用規(guī)范》GB
55015的規(guī)定執(zhí)行;
2外窗(包括透光幕墻)的傳熱系數(shù)應(yīng)按現(xiàn)行行業(yè)標(biāo)準(zhǔn)《建筑
門窗玻璃幕墻熱工計算規(guī)程》JGJ/T151的規(guī)定執(zhí)行。
4.3.4外墻保溫系統(tǒng)宜采用建筑保溫與結(jié)構(gòu)一體化技術(shù)。
4.3.5凸窗的設(shè)置應(yīng)符合下列規(guī)定:
1嚴(yán)寒地區(qū)不應(yīng)設(shè)置凸窗,寒冷地區(qū)除南向房間外不應(yīng)設(shè)置凸
窗;
2當(dāng)寒冷地區(qū)南向房間設(shè)置凸窗時,凸窗凸出(從外墻面至凸
窗外表面)不應(yīng)大于400mm;凸窗的傳熱系數(shù)限值應(yīng)比普通窗傳熱
系數(shù)限值降低15%,其不透明的頂板、底板及側(cè)板的傳熱系數(shù)不應(yīng)
大于外墻的傳熱系數(shù)。
12
4.3.6建筑外門、外窗、幕墻的氣密性分級應(yīng)符合現(xiàn)行國家標(biāo)準(zhǔn)《建
筑幕墻、門窗通用技術(shù)條件》GB/T31433中的規(guī)定,并應(yīng)滿足下列
要求:
1外窗的氣密性不應(yīng)低于7級;
2幕墻的氣密性不應(yīng)低于3級;
3外門的氣密性不應(yīng)低于4級。
4.3.7外窗(門)安裝時,外窗(門)與基層墻體之間的縫隙應(yīng)滿
足下列要求:
1應(yīng)采用高效保溫材料填堵密實,不得采用水泥砂漿補縫;
2應(yīng)采用耐久性良好的密封材料密封。
4.3.8外窗(門)洞口室外部分的側(cè)墻面應(yīng)做保溫處理,并應(yīng)保證
窗(門)洞口室內(nèi)部分的側(cè)墻面的內(nèi)表面溫度高于室內(nèi)空氣設(shè)計溫、
濕度條件下的露點溫度,減小附加熱損失。外窗(門)安裝時宜設(shè)
置節(jié)能型附框。
4.3.9當(dāng)公共建筑入口大堂采用全玻幕墻時,全玻幕墻中非中空玻
璃的面積不應(yīng)超過該建筑同一立面透光面積(門窗和玻璃幕墻)的
15%,且應(yīng)按同一立面透光面積(含全玻幕墻面積)加權(quán)計算平均
傳熱系數(shù)。
4.3.10外墻與屋面的熱橋部位,如外墻圈梁、構(gòu)造柱、窗過梁、挑
檐、雨篷、空調(diào)室外機擱板、女兒墻和裝飾線等,應(yīng)采取可靠的阻
斷熱橋或保溫措施,并按照現(xiàn)行國家標(biāo)準(zhǔn)《民用建筑熱工設(shè)計規(guī)范》
GB50176的規(guī)定進行內(nèi)表面溫度計算并滿足其要求。
4.4圍護結(jié)構(gòu)熱工性能的權(quán)衡判斷
4.4.1當(dāng)甲類公共建筑不滿足以下規(guī)定時,應(yīng)通過圍護結(jié)構(gòu)熱工性
13
能權(quán)衡判斷滿足要求:
1設(shè)計建筑的外墻傳熱系數(shù)或外窗傳熱系數(shù)不滿足表4.3.1-1、
表4.3.1-2的要求;
2設(shè)計建筑的外窗太陽得熱系數(shù)不滿足表4.3.1-3的要求;
3設(shè)計建筑屋面透光部分面積不滿足本標(biāo)準(zhǔn)第4.2.6條的要求。
4.4.2進行權(quán)衡判斷的設(shè)計建筑的外墻傳熱系數(shù)和外窗傳熱系數(shù)基
本要求不應(yīng)大于表4.4.2的限值。權(quán)衡判斷方法應(yīng)按現(xiàn)行國家標(biāo)準(zhǔn)
《建筑節(jié)能與可再生能源利用通用規(guī)范》GB55015的規(guī)定執(zhí)行。
表4.4.2甲類公共建筑圍護結(jié)構(gòu)熱工性能基本要求
氣候區(qū)屬外墻傳熱系數(shù)K[W/(m2·K)]
嚴(yán)寒C區(qū)0.45
寒冷地區(qū)0.55
單一立面外窗(包括透光幕墻)傳熱系數(shù)K
氣候區(qū)屬窗墻面積比
[W/(m2·K)]
窗墻面積比≤0.40≤2.30
嚴(yán)寒C區(qū)0.40<窗墻面積比≤0.60≤2.00
窗墻面積比>0.60≤1.70
窗墻面積比≤0.40≤2.40
寒冷地區(qū)0.40<窗墻面積比≤0.70≤2.00
窗墻面積比>0.70≤1.70
4.4.3參照建筑的形狀、大小、朝向、內(nèi)部的空間劃分、使用功能
應(yīng)與設(shè)計建筑完全一致。設(shè)計建筑中不符合本標(biāo)準(zhǔn)第4.3.1條的規(guī)定
時,參照建筑應(yīng)按本標(biāo)準(zhǔn)的規(guī)定取值;參照建筑的其他參數(shù)應(yīng)與設(shè)
計建筑一致。
14
5供暖通風(fēng)與空氣調(diào)節(jié)
5.1一般規(guī)定
5.1.1公共建筑的施工圖設(shè)計階段,必須進行熱負(fù)荷計算和逐項逐
時的冷負(fù)荷計算。
5.1.2供暖和空調(diào)的室內(nèi)設(shè)計計算溫、濕度及新風(fēng)量取值應(yīng)符合現(xiàn)
行國家標(biāo)準(zhǔn)《民用建筑供暖通風(fēng)與空氣調(diào)節(jié)設(shè)計規(guī)范》GB50736、
《室內(nèi)空氣質(zhì)量標(biāo)準(zhǔn)》GB/T18883及現(xiàn)行行業(yè)標(biāo)準(zhǔn)《公共建筑室內(nèi)
空氣質(zhì)量控制設(shè)計標(biāo)準(zhǔn)》JGJ/T461的規(guī)定。
5.1.3公共建筑的供暖方式應(yīng)根據(jù)建筑等級、供暖期天數(shù)、能源消
耗量和運行費用等因素,經(jīng)技術(shù)經(jīng)濟綜合分析比較后確定。對于嚴(yán)
寒地區(qū)設(shè)置空氣調(diào)節(jié)系統(tǒng)的公共建筑,不宜采用熱風(fēng)末端作為唯一
的供暖方式。
5.1.4冷熱媒溫度的選取應(yīng)符合現(xiàn)行國家標(biāo)準(zhǔn)《民用建筑供暖通風(fēng)
與空氣調(diào)節(jié)設(shè)計規(guī)范》GB50736的規(guī)定。在經(jīng)濟技術(shù)合理時,冷媒
溫度宜高于常用設(shè)計溫度,熱媒溫度宜低于常用設(shè)計溫度。
5.1.5當(dāng)利用通風(fēng)可以排除室內(nèi)的余熱、余濕或其他污染物時,宜
采用自然通風(fēng)、機械通風(fēng)或復(fù)合通風(fēng)的通風(fēng)方式。
5.1.6符合下列情況之一時,宜采用分散設(shè)置的空調(diào)裝置或系統(tǒng):
1全年所需供冷時間短或采用集中供冷系統(tǒng)不經(jīng)濟;
2需設(shè)空氣調(diào)節(jié)的房間布置分散;
3設(shè)有集中供冷、供暖系統(tǒng)的建筑中,使用時間和要求不同的
房間。
5.1.7采用溫濕度獨立控制空調(diào)系統(tǒng)時,應(yīng)符合下列要求:
15
1應(yīng)根據(jù)氣候特點,經(jīng)技術(shù)經(jīng)濟分析論證,確定高溫冷水的制
備方式和新風(fēng)除濕方式;
2宜考慮全年對天然冷源和可再生能源的應(yīng)用措施;
3不宜采用再熱空氣處理方式。
5.1.8使用時間不同的空氣調(diào)節(jié)區(qū)不應(yīng)劃分在同一個定風(fēng)量全空氣
風(fēng)系統(tǒng)中。溫度、濕度等要求不同的空氣調(diào)節(jié)區(qū)不宜劃分在同一個
空氣調(diào)節(jié)風(fēng)系統(tǒng)中。
5.1.9空調(diào)制冷系統(tǒng)的各種設(shè)備應(yīng)采用高效、節(jié)能的產(chǎn)品。在技術(shù)
經(jīng)濟合理時,宜采用高效制冷機房。
5.2冷源與熱源
5.2.1供暖空調(diào)冷源與熱源應(yīng)根據(jù)建筑規(guī)模、用途、建設(shè)地點的能
源條件、結(jié)構(gòu)、價格以及國家及河北省節(jié)能減排和環(huán)保政策的相關(guān)
規(guī)定,通過綜合論證確定,并應(yīng)符合下列規(guī)定:
1有可供利用的廢熱或工業(yè)余熱的區(qū)域,熱源宜采用廢熱或工
業(yè)余熱。當(dāng)廢熱或工業(yè)余熱的溫度較高、經(jīng)技術(shù)經(jīng)濟論證合理時,
冷源宜采用吸收式冷水機組。
2在技術(shù)經(jīng)濟合理的情況下,冷、熱源宜利用太陽能、地源熱
泵、空氣源等可再生能源。當(dāng)采用可再生能源受到氣候等原因的限
制無法保證時,應(yīng)設(shè)置輔助冷、熱源。
3不具備本條第1、2款的條件,且當(dāng)?shù)責(zé)崃?yīng)政策鼓勵用
熱時,集中空調(diào)系統(tǒng)及供暖系統(tǒng)的供熱熱源可采用城市或區(qū)域熱網(wǎng);
城市電網(wǎng)夏季供電充足的地區(qū),空調(diào)系統(tǒng)的冷源宜采用電動壓縮式
機組。
4夏季室外空氣設(shè)計露點溫度較低的地區(qū),宜采用間接蒸發(fā)冷
16
卻冷水機組作為空調(diào)系統(tǒng)的冷源。
5天然氣供應(yīng)充足的地區(qū),當(dāng)建筑的電力負(fù)荷、熱負(fù)荷和冷負(fù)
荷能較好匹配且經(jīng)濟技術(shù)比較合理時,宜采用分布式燃?xì)饫錈犭娙?/p>
聯(lián)供系統(tǒng)。
6全年進行空氣調(diào)節(jié),且各房間或區(qū)域負(fù)荷特性相差較大,需
要長時間地向建筑同時供熱和供冷,經(jīng)技術(shù)經(jīng)濟比較合理時,宜采
用水環(huán)熱泵空調(diào)系統(tǒng)供冷、供熱。
7在執(zhí)行分時電價、峰谷電價差較大的地區(qū),經(jīng)技術(shù)經(jīng)濟比較,
采用低谷電能夠明顯起到對電網(wǎng)“削峰填谷”和節(jié)省運行費用時,
宜采用蓄能系統(tǒng)供冷、供熱。
8具有多種能源的地區(qū),可采用復(fù)合式能源供冷、供熱。
5.2.2鍋爐供暖設(shè)計應(yīng)符合下列規(guī)定:
1單臺鍋爐的設(shè)計容量應(yīng)以保證其具有長時間較高運行效率的
原則確定,實際運行負(fù)荷率不宜低于50%;
2當(dāng)供暖系統(tǒng)的設(shè)計回水水溫小于或等于50℃時,宜采用冷凝
式鍋爐。
5.2.3鍋爐的選型,應(yīng)與當(dāng)?shù)亻L期供應(yīng)的燃料種類相適應(yīng)。燃?xì)饧?/p>
燃生物質(zhì)鍋爐的設(shè)計熱效率不應(yīng)低于表5.2.3規(guī)定的數(shù)值。
表5.2.3鍋爐額定工況下的熱效率(%)
鍋爐額定熱功率Q(MW)
鍋爐類型及燃料種類
Q≤7Q>7
生物質(zhì)8488
天燃?xì)忮仩t94(101a)
注a:燃?xì)饫淠仩t額定工況下的熱效率。
5.2.4集中空調(diào)系統(tǒng)的冷水(熱泵)機組臺數(shù)及單機制冷量(制熱
17
量)選擇,應(yīng)能適應(yīng)負(fù)荷全年變化規(guī)律,滿足季節(jié)及部分負(fù)荷要求。
機組不宜少于兩臺,且同類型機組不宜超過4臺;當(dāng)小型工程僅設(shè)
一臺時,應(yīng)選調(diào)節(jié)性能優(yōu)良的機型,并能滿足建筑最低負(fù)荷的要求。
5.2.5采用分布式能源站作為冷熱源時,宜采用由自身發(fā)電驅(qū)動、
以熱電聯(lián)產(chǎn)產(chǎn)生的廢熱為低位熱源的熱泵系統(tǒng)。
5.2.6采用電機驅(qū)動的蒸汽壓縮循環(huán)冷水(熱泵)機組時,其在名
義制冷工況和規(guī)定條件下的性能系數(shù)(COP)應(yīng)符合下列規(guī)定:
1定頻水冷機組及風(fēng)冷或蒸發(fā)冷卻機組的性能能系數(shù)(COP)
不應(yīng)低于表5.2.6-1的數(shù)值;
2變頻水冷機組及風(fēng)冷或蒸發(fā)冷卻機組的性能能系數(shù)(COP)
不應(yīng)低于表5.2.6-2的數(shù)值。
表5.2.6-1名義制冷工況和規(guī)定條件下定頻冷水(熱泵)機組的制冷性能系數(shù)(COP)
性能系數(shù)COP(W/W)
類型名義制冷量CC(kW)
嚴(yán)寒C區(qū)寒冷地區(qū)
活塞式/渦旋式CC≤5284.305.30
CC≤5284.905.30
螺桿式528<CC≤11635.205.60
水冷CC>11635.505.80
CC≤5285.605.70
離心式528<CC≤11635.906.00
CC>11636.106.20
風(fēng)冷或CC≤502.803.00
活塞式/渦旋式
蒸發(fā)冷卻
CC>503.003.00
18
續(xù)表5.2.6-1
性能系數(shù)COP(W/W)
類型名義制冷量CC(kW)
嚴(yán)寒C區(qū)寒冷地區(qū)
風(fēng)冷或CC≤502.903.00
螺桿式
蒸發(fā)冷卻
CC>502.903.00
表5.2.6-2名義制冷工況和規(guī)定條件下變頻冷水(熱泵)機組的制冷性能系數(shù)(COP)
性能系數(shù)COP(W/W)
類型名義制冷量CC(kW)
嚴(yán)寒C區(qū)寒冷地區(qū)
活塞式/渦旋式CC≤5284.204.20
CC≤5284.474.47
螺桿式528<CC≤11634.754.85
水冷CC>11635.205.23
CC≤5284.704.84
離心式528<CC≤11635.205.20
CC>11635.305.39
CC≤502.502.50
活塞式/渦旋式
風(fēng)冷或CC>502.702.70
蒸發(fā)冷卻
CC≤502.512.60
螺桿式
CC>502.702.79
5.2.7采用電機驅(qū)動的蒸汽壓縮循環(huán)冷水(熱泵)機組時,綜合部
分負(fù)荷性能系數(shù)(IPLV)應(yīng)符合下列規(guī)定:
1定頻水冷機組及風(fēng)冷或蒸發(fā)冷卻機組的綜合部分負(fù)荷性能系
數(shù)(IPLV)不應(yīng)低于表5.2.7-1的數(shù)值;
19
2變頻水冷機組及風(fēng)冷或蒸發(fā)冷卻機組的綜合部分負(fù)荷性能系
數(shù)(IPLV)不應(yīng)低于表5.2.7-2的數(shù)值。
3綜合部分負(fù)荷性能系數(shù)(IPLV)應(yīng)按下式計算:
IPLV=1.2%×A+32.8%×B+39.7%×C+26.3%×D(5.2.7)
式中:A——100%負(fù)荷時的性能系數(shù)(W/W),冷卻水進水溫度
30℃/冷凝器進氣干球溫度35℃;
B——75%負(fù)荷時的性能系數(shù)(W/W),冷卻水進水溫度
26℃/冷凝器進氣干球溫度31.5℃;
C——50%負(fù)荷時的性能系數(shù)(W/W),冷卻水進水溫度
23℃/冷凝器進氣干球溫度28℃;
D——25%負(fù)荷時的性能系數(shù)(W/W),冷卻水進水溫度
19℃/冷凝器進氣干球溫度24.5℃。
表5.2.7-1定頻冷水(熱泵)機組綜合部分負(fù)荷性能系數(shù)(IPLV)
綜合部分負(fù)荷性能系數(shù)(IPLV)
類型名義制冷量CC(kW)
嚴(yán)寒C區(qū)寒冷地區(qū)
活塞式/渦旋式CC≤5285.005.00
CC≤5285.455.45
螺桿式528<CC≤11635.755.85
水冷CC>11635.956.20
CC≤5285.505.60
離心式528<CC≤11635.505.60
CC>11635.956.10
20
續(xù)表5.2.7-1
綜合部分負(fù)荷性能系數(shù)(IPLV)
類型名義制冷量CC(kW)
嚴(yán)寒C區(qū)寒冷地區(qū)
CC≤503.103.20
活塞式/渦旋式
風(fēng)冷或CC>503.353.40
蒸發(fā)冷卻
CC≤502.903.10
螺桿式
CC>503.103.20
表5.2.7-2變頻冷水(熱泵)機組綜合部分負(fù)荷性能系數(shù)(IPLV)
綜合部分負(fù)荷性能系數(shù)(IPLV)
類型名義制冷量CC(kW)
嚴(yán)寒C區(qū)寒冷地區(qū)
活塞式/渦旋式CC≤5285.646.30
CC≤5286.276.30
螺桿式528<CC≤11636.616.73
水冷CC>11636.847.13
CC≤5286.706.96
離心式528<CC≤11637.157.28
CC>11637.747.93
CC≤503.503.60
活塞式/渦旋式
風(fēng)冷或CC>503.603.70
蒸發(fā)冷卻
CC≤503.503.60
螺桿式
CC>503.603.70
5.2.8當(dāng)采用單元式空氣調(diào)節(jié)機時,其性能系數(shù)應(yīng)符合表5.2.8的規(guī)定。
21
表5.2.8單元式空調(diào)機的性能系數(shù)
類型性能系數(shù)
≤≤
單冷型7000WCC14000W3.80
(,)
SEERWh/Wh>
風(fēng)冷式單元式空CC14000W3.00
調(diào)機
≤≤
熱泵型7000WCC14000W3.10
(APF,Wh/Wh)
CC>14000W3.00
7000W≤CC≤14000W3.70
水冷式單元式空調(diào)機(IPLV,W/W)
CC>14000W4.30
風(fēng)冷式3.60
水冷式4.00
計算機和數(shù)據(jù)處理機房
用單元式空調(diào)機乙二醇經(jīng)濟冷卻式3.70
(AEER,W/W)
風(fēng)冷雙冷源式3.40
水冷雙冷源式3.90
通訊基站用單元式空氣調(diào)節(jié)機(COP,W/W)3.00
恒溫恒濕型單元式空氣調(diào)節(jié)機(AEER,W/W)3.70
5.2.9當(dāng)采用風(fēng)管送風(fēng)式空調(diào)機組時,其性能系數(shù)應(yīng)符合表5.2.9-1、
表5.2.9-2的規(guī)定。
表5.2.9-1風(fēng)管送風(fēng)式空調(diào)(熱泵)機組的性能系數(shù)
類型名義制冷量CC(W)性能系數(shù)
CC≤71003.80
風(fēng)
單冷型7100<CC≤140003.60
冷
(SEER,W/W)
式14000<CC≤280003.40
CC>280003.00
22
續(xù)表5.2.9-1
類型名義制冷量CC(W)性能系數(shù)
CC≤71003.40
風(fēng)
熱泵型7100<CC≤140003.20
冷
(APF,W/W)
式14000<CC≤280003.00
CC>280002.80
水冷式CC≤140004.00
(IPLV,W/W)
CC>140003.80
表5.2.9-2直接蒸發(fā)式全新風(fēng)空氣處理機組能效等級指標(biāo)值
類型名義制冷量CC(W)性能系數(shù)
CC≤45003.20
4500<CC≤71003.00
小焓差
7100<CC≤140002.80
風(fēng)冷式
CC>140002.60
(EER,W/W)
CC≤45003.00
4500<CC≤71002.80
大焓差
7100<CC≤140002.60
CC>14000
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 韓式護欄施工方案
- 第二單元 讓機器認(rèn)識我第3節(jié)“認(rèn)出”一個人 教學(xué)設(shè)計 2023-2024學(xué)年川教版(2019)初中信息技術(shù)八年級上冊
- 合同范本買賣合同
- 專職老師聘用合同范本
- 增強學(xué)生自主學(xué)習(xí)意識的方法計劃
- 班主任與學(xué)校管理層的溝通計劃
- 歌唱與律動小班音樂教育探討計劃
- 可持續(xù)發(fā)展在年度計劃中的應(yīng)用
- 法務(wù)部合規(guī)管理工作回顧與展望計劃
- 九年級體育 教學(xué)實錄(素質(zhì)練習(xí)1) 人教新課標(biāo)版
- 2025年湖南益陽市生態(tài)環(huán)境局招聘10人歷年高頻重點模擬試卷提升(共500題附帶答案詳解)
- 2025年江蘇省職業(yè)院校技能大賽高職組(人力資源服務(wù))參考試題庫資料及答案
- 2025年社區(qū)工作人員招聘考試復(fù)習(xí)題100道及參考答案
- 2024陜西延長石油物流集團有限公司社會招聘筆試參考題庫附帶答案詳解
- 2025年黑龍江旅游職業(yè)技術(shù)學(xué)院單招職業(yè)傾向性測試題庫完整
- 2025年湖南高速鐵路職業(yè)技術(shù)學(xué)院單招職業(yè)適應(yīng)性測試題庫1套
- 《錢三強-杰出課件》
- 山東2025年山東大學(xué)輔導(dǎo)員招聘筆試歷年參考題庫附帶答案詳解
- 羽毛球運動體育健身
- (正式版)HG∕T 21633-2024 玻璃鋼管和管件選用規(guī)定
- 護林員系統(tǒng)培訓(xùn)
評論
0/150
提交評論