安徽省建設(shè)工程消防設(shè)計審查驗收工作
疑難問題解答
(2023版征求意見稿)
安徽省住房和城鄉(xiāng)建設(shè)廳
安徽省工程勘察設(shè)計協(xié)會
二〇二三年十月
目錄
第一章建筑專業(yè)·······················································1
1.1建筑分類和耐火等級··········································1
1.2總平面布局······················································3
1.3防火分區(qū)·························································5
1.4平面布置·························································6
1.5安全疏散和避難················································7
1.6建筑構(gòu)造·······················································14
1.7滅火救援設(shè)施·················································16
第二章給排水專業(yè)···················································21
2.1消防水源及消防設(shè)計流量··································21
2.2消防水池和泵房及消防水箱·······························22
2.3消火栓給水系統(tǒng)·············································24
2.4自動滅火系統(tǒng)·················································25
2.5消防排水·······················································28
2.6其他·····························································29
第三章暖通專業(yè)······················································31
3.1防煙系統(tǒng)·······················································31
3.2排煙系統(tǒng)·······················································33
3.3系統(tǒng)控制·······················································38
3.4其他·····························································39
第四章電氣專業(yè)······················································40
4.1火災(zāi)自動報警系統(tǒng)···········································40
4.2消防聯(lián)動控制系統(tǒng)···········································43
4.3消防應(yīng)急照明和疏散指示系統(tǒng)····························45
4.4消防電源及系統(tǒng)布線········································48
4.5其他·····························································48
第五章結(jié)構(gòu)專業(yè)······················································50
5.1基本規(guī)定·······················································50
5.2鋼筋混凝土結(jié)構(gòu)··············································50
5.3鋼結(jié)構(gòu)··························································50
5.4隔震結(jié)構(gòu)·······················································51
5.5既有建筑加固改造··········································51
第六章室內(nèi)裝修······················································52
第七章政策、程序···················································53
7.1住房和城鄉(xiāng)建設(shè)部有關(guān)消防問題答復(fù)···················53
7.2其它·····························································61
第一章建筑專業(yè)
1.1建筑分類和耐火等級
1.1.1什么是“人員密集場所”?
答復(fù):依據(jù)《中華人民共和國消防法》第七十三條:“人員密集場所”是指公眾聚集場
所,醫(yī)院的門診樓、病房樓,學(xué)校的教學(xué)樓、圖書館、食堂和集體宿舍,養(yǎng)老院,福利院,
托兒所,幼兒園,公共圖書館的閱覽室,公共展覽館、博物館的展示廳,勞動密集型企業(yè)的
生產(chǎn)加工車間和員工集體宿舍,旅游、宗教活動場所等。
上述中的“公眾聚集場所”,是指賓館、飯店、商場、集貿(mào)市場、客運車站候車室、客
運碼頭候船廳、民用機場航站樓、體育場館、會堂以及公共娛樂場所等。
上述中的“公共娛樂場所”,依據(jù)《人員密集場所消防安全管理》GB/T40248-2021中
第3.1條,是指具有文化娛樂、健身休閑功能并向公眾開放的室內(nèi)場所,包括影劇院、錄像
廳、禮堂等演出、放映場所,舞廳、卡拉OK等歌舞娛樂場所,具有娛樂功能的夜總會、音樂
茶座、酒吧和餐飲場所,游藝、游樂場所和保齡球館、旱冰場、桑拿等娛樂、健身、休閑場
所和互聯(lián)網(wǎng)上網(wǎng)服務(wù)營業(yè)場所。
1.1.2消防技術(shù)標準中的“人員密集場所”如何理解?
答復(fù):消防技術(shù)標準中的“人員密集場所”應(yīng)按規(guī)范條文及其條文說明所特指的具體內(nèi)
容理解執(zhí)行。舉例如下:
1.《火通規(guī)》第3.1.3條、3.2.1條、3.2.2條、3.2.3條,規(guī)定火災(zāi)危險性為甲類廠房、
甲類倉庫等與“人員密集場所”的防火間距要求時,“人員密集場所”是指《中華人民共和
國消防法》中所表述的內(nèi)容。
2.《火通規(guī)》第4.1.4條,建筑平面布置中關(guān)于燃油或燃氣鍋爐房、柴油發(fā)電機房等與
“人員密集的場所”的布置,要求燃油或燃氣鍋爐房、柴油發(fā)電機房等不應(yīng)貼鄰建筑中“人
員密集的場所”,條文說明中重點強調(diào)“應(yīng)避開會議室、多功能廳、餐廳、營業(yè)廳、教室等
人員聚集的場所”。如某辦公樓依據(jù)《消防法》不屬于“人員密集場所”,但辦公樓中人數(shù)
較多的“多功能廳、大會議室、大餐廳”等人員聚集的區(qū)域或場所,就屬于“人員密集的場
所”。
3.《建規(guī)》第5.5.19條“人員密集的公共場所、觀眾廳的疏散門不應(yīng)設(shè)置門檻,其凈寬
度不應(yīng)小于1.40m,且緊靠門口內(nèi)外各1.40m范圍內(nèi)不應(yīng)設(shè)置踏步。......”規(guī)定對疏散門
的要求及其周邊踏步的距離時,條文說明中明確“人員密集的公共場所”主要指營業(yè)廳、觀
眾廳,禮堂、電影院、劇院和體育場館的觀眾廳,公共娛樂場所中出入大廳、舞廳,候機(車、
船)廳及醫(yī)院的門診大廳等面積較大、同一時間聚集人數(shù)較多的場所。
1.1.3兩棟建筑之間的區(qū)域是否可以架設(shè)雨篷?
1
答復(fù):應(yīng)以批準的總圖為依據(jù),并滿足消防技術(shù)標準的相關(guān)要求。
1.1.4兒童活動場所如何判定?
答復(fù):依據(jù)《火通規(guī)》第4.3.4條條文說明,“兒童活動場所”是指供12周歲及以下嬰
幼兒和少兒活動的場所,包括幼兒園、托兒所中供嬰幼兒生活和活動的房間,設(shè)置在建筑內(nèi)
的兒童游樂廳、兒童樂園、兒童培訓(xùn)班、早教中心等兒童游樂、學(xué)習(xí)和培訓(xùn)等活動的場所,
不包括小學(xué)學(xué)校的教室等教學(xué)場所。
1.1.5設(shè)置在住宅首層或首層及二層的物業(yè)、社區(qū)用房、居委會、衛(wèi)生服務(wù)站、商店、郵政
所、儲蓄所、理發(fā)店等(小區(qū)配套用房),可否按商業(yè)服務(wù)網(wǎng)點考慮?
答復(fù):符合《火通規(guī)》第4.3.2條第4款及《建規(guī)》第2.1.4條、5.4.11條,位于住宅
首層或首層及二層,且建筑面積小于300m2的物業(yè)、社區(qū)用房、居委會、衛(wèi)生服務(wù)站、商店、
郵政所、儲蓄所、理發(fā)店等服務(wù)用房或小型營業(yè)用房可按商業(yè)服務(wù)網(wǎng)點考慮。
1.1.6原底部設(shè)置商業(yè)服務(wù)網(wǎng)點的住宅建筑,現(xiàn)將其中兩個及以上網(wǎng)點分隔單元改造合并為
一家其它功能的營業(yè)性用房,合并后建筑面積大于300m2的營業(yè)性用房是否仍是商業(yè)服務(wù)網(wǎng)
點?
答復(fù):依據(jù)《建規(guī)》第5.4.11條“商業(yè)服務(wù)網(wǎng)點中每個分隔單元之間應(yīng)采用耐火極限不
低于2.00h且無門、窗、洞口的防火隔墻相互分隔”,兩個及兩個以上網(wǎng)點分隔單元合并后
建筑面積大于300m2的營業(yè)性用房不再是商業(yè)服務(wù)網(wǎng)點,應(yīng)按公共建筑的相關(guān)要求執(zhí)行。
1.1.7部分位于住宅建筑投影范圍之外符合商業(yè)服務(wù)網(wǎng)點要求的建筑能否判定為商業(yè)服務(wù)網(wǎng)
點?
答復(fù):可以。
1.1.8商業(yè)服務(wù)網(wǎng)點的疏散距離有何要求?
答復(fù):商業(yè)服務(wù)網(wǎng)點疏散距離應(yīng)按《建規(guī)》第5.4.11條執(zhí)行。
1.1.9月子護理中心按何要求進行防火設(shè)計?
答復(fù):無治療功能的休養(yǎng)性質(zhì)的月子護理中心,應(yīng)按照旅館建筑的要求進行消防設(shè)計,
但疏散距離應(yīng)按醫(yī)療建筑的病房部分要求執(zhí)行。
1.1.10教學(xué)實訓(xùn)樓如何進行防火設(shè)計?
答復(fù):教學(xué)實訓(xùn)樓屬于教學(xué)建筑,應(yīng)按教學(xué)建筑進行設(shè)計。
1.1.11汽車4S店的車輛銷售區(qū)、維修區(qū)和停車區(qū)等組合或貼鄰建造時,應(yīng)符合哪些規(guī)定?
答復(fù):汽車銷售區(qū)可按公共建筑的商業(yè)營業(yè)廳進行設(shè)計,汽車維修區(qū)和停車區(qū)應(yīng)分別按
《車規(guī)》中有關(guān)修車庫和汽車庫的規(guī)定設(shè)計,汽車銷售區(qū)與其他區(qū)應(yīng)分別劃分防火分區(qū)。
1.1.12保齡球館、臺球、棒球、蹦床、飛鏢、真人CS、室內(nèi)電動卡丁車場等場所是否屬于
2
歌舞娛樂放映游藝場所?
答復(fù):保齡球、臺球、棒球、蹦床、飛鏢、真人CS、室內(nèi)電動卡丁車場等場所屬于公共
娛樂場所,但不屬于歌舞娛樂放映游藝場所。
1.1.13足療店消防設(shè)計如何定性?
答復(fù):依據(jù)《建規(guī)》國家標準管理組《關(guān)于足療店消防設(shè)計問題的復(fù)函》(建規(guī)字〔2019〕
1號)文件,足療店的業(yè)態(tài)特點與桑拿浴室休息室或具有桑拿服務(wù)功能客房基本相同,其消
防設(shè)計應(yīng)按照歌舞娛樂放映游藝場所的要求執(zhí)行。
1.1.14汗蒸房是否屬于歌舞娛樂放映游藝場所?
答復(fù):汗蒸房屬于歌舞娛樂放映游藝場所,消防設(shè)計應(yīng)滿足《汗蒸房消防安全整治要求》
(公消〔2017〕83號)的要求。
1.1.15廠房內(nèi)能否設(shè)置廚房、食堂、浴室、報告廳?
答復(fù):廠房內(nèi)不應(yīng)設(shè)置廚房、食堂、浴室、報告廳等與生產(chǎn)無直接關(guān)系的其他用房。
1.1.16車輛檢測車間是按廠房還是車庫的要求進行設(shè)計?
答復(fù):車輛檢測車間可按《建規(guī)》中廠房的要求執(zhí)行。
1.1.17對于臺階式地坪,怎樣計算建筑高度?
答復(fù):對于臺階式地坪,當不滿足《建規(guī)》附錄A分別計算各自建筑高度的條件時,應(yīng)
按滿足建筑消防救援要求的消防車道(高層建筑應(yīng)為消防車登高操作場地)相應(yīng)建筑室外設(shè)
計地面起計算建筑高度;當沿建筑的兩條長邊均設(shè)置消防車道時,可按較高或較低建筑室外
設(shè)計地面(高層建筑應(yīng)為消防車登高操作場地)起計算建筑高度。
1.1.18滿足防火間距要求的相鄰建筑通過連廊連接時,定性為一棟建筑還是幾棟建筑?開向
連廊的門是否可采用普通門?開向連廊的門是否可作為第二安全出口?民用建筑之間的連廊
上設(shè)有使用功能的房間時是否允許?
答復(fù):1.當幾棟建筑防火間距滿足《建規(guī)》要求并通過連廊連接時,可以視為幾棟獨立
的建筑。
2.當采取除防火門外的其他防止火災(zāi)蔓延的措施時,開向連廊的門可以采用普通門。
3.當滿足《建規(guī)》第6.6.4條要求時,建筑開向連廊的門可以作為第二安全出口。
4.連廊僅用于人員通行,不允許設(shè)有使用功能的房間。
1.2總平面布局
1.2.1甲類倉庫與廠外道路的防火間距不應(yīng)小于20m,按道路(機動車道)路邊計算還是按
道路紅線計算?
答復(fù):應(yīng)按照道路紅線計算。
3
1.2.2當兩座建筑采取防火加強措施可以減小防火間距或貼鄰時,兩座建筑外墻開口之間的
距離如何確定?
答復(fù):當兩座建筑采取防火加強措施可以減小防火間距或貼鄰時,兩座建筑外墻開口之
間的防火間距應(yīng)滿足下表的要求。
外墻夾角角度兩座建筑開口之間的距離
兩座建筑外墻夾角≥180度時水平距離應(yīng)不小于2m(附圖1.2.2-1)
180>外墻夾角>90度時水平距離應(yīng)不小于4m(附圖1.2.2-1)
外墻夾角≤90度時水平距離不應(yīng)小于相應(yīng)的防火間距要求(附1.2.2-2)
當上述兩側(cè)門窗中,其中一側(cè)采用甲級防火門窗時(固定或火災(zāi)時可自行關(guān)閉的乙級防火
窗)間距不限。(附圖1.2.2-3)
附圖1.2.2-1
附圖1.2.2-2附圖1.2.2-3
4
1.2.3民用建筑內(nèi)天井短邊尺寸有什么規(guī)定?
答復(fù):1.低層、多層住宅內(nèi)天井短邊尺寸一般不小于6m,高層住宅不應(yīng)設(shè)計四周完全封
閉的內(nèi)天井。
2.高層公共建筑不宜設(shè)計四周完全封閉的內(nèi)天井。確需設(shè)置內(nèi)天井且短邊尺寸不滿足《建
規(guī)》第5.2.2條時,天井內(nèi)的外窗應(yīng)為火災(zāi)時能自行關(guān)閉的防火窗;當短邊尺寸小于6m時,
外窗應(yīng)為火災(zāi)時能自行關(guān)閉的甲級防火窗。
1.2.4住宅建筑設(shè)置“U型天井”且以敞開連廊聯(lián)系時有何要求?
答復(fù):住宅建筑設(shè)置“U型天井”且以敞開連廊聯(lián)系時,天井的頂部不應(yīng)設(shè)置頂蓋,連
廊有效敞開長度一般不小于6m,確有困難時不應(yīng)小于4m,內(nèi)天井短邊凈尺寸不應(yīng)少于2m。
1.2.5對于具有凸出建筑外墻的不燃性梁、柱構(gòu)件的建筑,防火間距是以凸出建筑外墻的不
燃性梁、柱構(gòu)件外邊計還是主體外墻邊計算?
答復(fù):當凸出外墻的不燃性梁、柱構(gòu)件不影響消防車通行和消防救援要求時,可以忽略
其對防火間距的影響,即可以按照相鄰?fù)鈮γ娴淖罱骄嚯x確定防火間距。
1.2.6對于具有凸出外墻陽臺的建筑,防火間距是以陽臺外邊計算還是以外墻邊計算?
答復(fù):應(yīng)按陽臺外邊計算。
1.2.7建筑設(shè)有室外疏散樓梯,與相鄰建筑的防火間距是從建筑外墻還是樓梯外側(cè)算起?
答復(fù):室外疏散樓梯是豎向安全疏散通道,為保證其安全性,防火間距應(yīng)按樓梯外側(cè)計
算。
1.2.8工業(yè)廠房按《建規(guī)》第3.4.1條注2,兩座廠房滿足一定條件時防火間距不限,是否必
須設(shè)雙墻?
答復(fù):所謂兩座廠房,是結(jié)構(gòu)體系各自獨立的兩座建筑,為防止火災(zāi)蔓延,應(yīng)設(shè)置雙墻。
1.2.9民用建筑與獨立建造的地下車庫的天窗或側(cè)天窗的防火間距如何確定?
答復(fù):對于設(shè)置屋頂天窗的地下汽車庫,可按《建規(guī)》第6.3.7條的要求執(zhí)行。
1.2.10非機動車坡道在地下出入口處可以不設(shè)門嗎?非機動車坡道地面出入口與相鄰建筑
的防火間距如何確定?
答復(fù):1.用于人員疏散的非機動車坡道在地下出入口處應(yīng)設(shè)置防火門,且應(yīng)滿足《火通
規(guī)》第7.1.10條;非人員疏散用的非機動車坡道在地下出入口處可不設(shè)門。
2.非機動車坡道在地下出入口處設(shè)置防火門時,坡道出地面出入口與地上相鄰建筑的防
火間距參照《建規(guī)》第6.4.5條第5款執(zhí)行。
1.3防火分區(qū)
1.3.1不計入防火分區(qū)面積的開敞式外走廊或陽臺,是否考慮疏散人數(shù)和疏散距離?
5
答復(fù):應(yīng)考慮。
1.3.2防火分區(qū)面積可以按使用面積計算嗎?
答復(fù):防火分區(qū)面積應(yīng)按《民用建筑通用規(guī)范》規(guī)定的建筑面積計算。
1.3.3地下商業(yè)與汽車庫之間如何做防火分隔?
答復(fù):地下商業(yè)與汽車庫之間應(yīng)采用防火墻分隔,不應(yīng)采用防火卷簾、防火水幕分隔。
當?shù)叵律虡I(yè)建筑面積大于20000㎡時,應(yīng)按《建規(guī)》第5.3.5條執(zhí)行。
1.3.4當商店營業(yè)廳內(nèi)設(shè)置餐飲場所時,防火分區(qū)的建筑面積按照商業(yè)還是按照餐飲控制?
答復(fù):當營業(yè)廳內(nèi)設(shè)置輕餐飲(無明火、使用電氣加工、不產(chǎn)生油煙的飲料、輕食店,
如面包鋪、咖啡室、冷餐室等)時,可按商業(yè)營業(yè)廳的防火分區(qū)面積要求劃分。
當營業(yè)廳內(nèi)設(shè)置餐飲場所(非輕餐飲)時,防火分區(qū)的建筑面積需要按照民用建筑的其
他功能的防火分區(qū)要求劃分。
1.4平面布置
1.4.1供教學(xué)、科研建筑中的少量甲、乙類氣體的儲藏間如何設(shè)置?
答復(fù):供教學(xué)、科研的建筑中的實驗室日常使用的少量甲、乙類氣體的儲藏間應(yīng)獨立建
造,確有困難需貼鄰設(shè)置時,應(yīng)符合下列規(guī)定:
1.甲、乙類氣體的總儲存量不應(yīng)大于O.5m3;
2.存放可燃氣體儲罐的儲藏間,應(yīng)設(shè)置在建筑首層靠外墻部位且應(yīng)采用耐火極限不低于
3.00h的無門窗洞口的防火隔墻、耐火極限不低于2.50h的樓板與建筑的其他部位分隔;開
門應(yīng)直通室外。
1.4.2一個防火分區(qū)內(nèi)總建筑面積小于50㎡且有家長陪伴的少量兒童活動的區(qū)域,是否考慮
獨立疏散和防火分隔?
答復(fù):可不考慮。
1.4.3地下室汽車庫內(nèi)設(shè)備用房如何劃分防火分區(qū)?
答復(fù):除僅為汽車庫服務(wù)的設(shè)備用房外,其他設(shè)備用房一般不應(yīng)與汽車庫設(shè)置在同一防
火分區(qū)內(nèi)。當確有困難,其他設(shè)備用房需設(shè)置在汽車庫防火分區(qū)內(nèi)時,應(yīng)符合以下規(guī)定:
1.設(shè)備用房的總建筑面積不超過500㎡,且占汽車庫防火分區(qū)的面積比例不超過1/3時,
可計入汽車庫的防火分區(qū)。
2.同一防火分區(qū)內(nèi)的設(shè)備用房總建筑面積大于等于500㎡時,應(yīng)單獨劃分防火分區(qū)。
1.4.4中庭在起始層與其他區(qū)域是否必須設(shè)置防火分隔?
答復(fù):當中庭的起始層與相連通的區(qū)域總建筑面積不大于規(guī)范規(guī)定的一個防火分區(qū)最大
允許建筑面積時,中庭起始層與其他區(qū)域可不做防火分隔。
6
1.4.5在中庭等位置能否布置兒童游戲設(shè)施?
答復(fù):不應(yīng)設(shè)置。
1.4.6下沉式庭院按功能可分為用于防火分隔的下沉式廣場、用于安全疏散的下沉式庭院和
用于景觀美化或通風(fēng)使用的下沉式庭院等三種類型,如何進行防火設(shè)計?
答復(fù):1.用于防火分隔的下沉式廣場,應(yīng)符合《建規(guī)》第6.4.12條的規(guī)定。
2.用于安全疏散的下沉式庭院,應(yīng)符合《建規(guī)》第6.4.5條相關(guān)規(guī)定。
3.用于景觀美化或通風(fēng)使用的下沉式庭院無特殊防火設(shè)計要求。
1.5安全疏散和避難
1.5.1子母式防火門子扇不具備自動關(guān)閉功能時,能否計入疏散寬度?
答復(fù):防火門凈寬度應(yīng)滿足規(guī)范和設(shè)計要求,當子扇不具備自動關(guān)閉功能時,子扇的寬
度不計入疏散寬度。
1.5.2防煙樓梯間計算疏散距離時,算到防煙樓梯間的門還是前室門?
答復(fù):前室是防煙樓梯間的一部分,計算疏散距離時,可計算到防煙樓梯間前室的門。
1.5.3《宿舍建筑設(shè)計規(guī)范》JGJ36-2016第5.2.5條,宿舍建筑的安全出口不應(yīng)設(shè)置門檻,
其凈寬不應(yīng)小于1.40m,請問宿舍建筑中通向樓層的封閉樓梯間的門是否需要按照凈寬不小
于1.4m控制?
答復(fù):依據(jù)中國建筑標準設(shè)計研究院于2021年11月5日回復(fù)住房和城鄉(xiāng)建設(shè)部建筑設(shè)
計標準化技術(shù)委員會的回復(fù)函《關(guān)于《宿舍建筑設(shè)計規(guī)范》(JGJ36-2016)有關(guān)問題的咨詢
函的回復(fù)函》(中標研發(fā)〔2021〕289號),《宿舍建筑設(shè)計規(guī)范》JGJ36-2016第5.2.5條
中的安全出口是指首層直通室外的安全出口,宿舍建筑中其他樓層封閉樓梯間的門可不按照
凈寬不小于1.4m控制。
1.5.4醫(yī)療建筑中的中心供應(yīng)、藥房等大空間的房間內(nèi)疏散距離如何控制?
答復(fù):醫(yī)療建筑疏散距離按照《建規(guī)》第5.5.17條第1款、第3款的要求執(zhí)行。
1.5.5醫(yī)療建筑中,醫(yī)療流程需要的污物通道是否應(yīng)考慮疏散寬度和疏散距離?
答復(fù):污物通道不作為疏散通道時,可不考慮疏散寬度和疏散距離。
1.5.6醫(yī)院門診大廳及門診樓,商業(yè)建筑中的餐飲場所及電影院,健身房,游泳池,溜冰場
等疏散人數(shù)如何計算?
答復(fù):1.醫(yī)院門診大廳和門診樓的疏散人數(shù)可根據(jù)日門診量、醫(yī)院規(guī)模等參數(shù)確定。
2.商業(yè)建筑中的餐飲場所,其疏散人數(shù)應(yīng)按《建規(guī)》中商業(yè)建筑的相關(guān)規(guī)定執(zhí)行。
3.商業(yè)建筑中的電影院,其疏散人數(shù)可按總固定座位數(shù)的1.1倍計算(參照《建筑設(shè)計
資料集》第三版)。
7
4.健身房的疏散人數(shù)可按4.6㎡/人計算。
5.游泳池、溜冰場的疏散人數(shù)可按照更衣(鞋)柜數(shù)量的1.1倍計算。
1.5.7學(xué)校建筑中非教學(xué)類建筑單體,如食堂、報告廳、宿舍疏散寬度計算是執(zhí)行《建規(guī)》
中5.5.21條還是執(zhí)行《中小學(xué)校設(shè)計規(guī)范》GB50099-2011中8.2.3條?
答復(fù):《建規(guī)》和《中小學(xué)校設(shè)計規(guī)范》GB50099-2011都應(yīng)執(zhí)行。
1.5.8《建規(guī)》表5.5.21-1中建筑層數(shù)和對應(yīng)的系數(shù),是地上4層及4層以上每層的百人疏
散取值系數(shù)都是按照1.00m/百人計算,還是地上1層~2層可以按照0.65m/百人計算?
答復(fù):該條“建筑層數(shù)”是指地上建筑整體的層數(shù)。當建筑為四層及以上時,各層百人
疏散取值系數(shù)均按照1.00m/百人計算。
1.5.9《建規(guī)》第5.5.20條劇場、電影院、禮堂、體育館等場所,表5.5.20-1中樓梯的疏
散寬度計算適用于其他建筑內(nèi)建造的相應(yīng)場所嗎?
答復(fù):《建規(guī)》第5.5.20條表5.5.20-1中樓梯的疏散寬度計算只適用于單獨建造的相
應(yīng)場所。
1.5.10地下室的鍋爐房、消防水泵房采用疏散走道直通室外或安全出口時,疏散距離是否有
限制?
答復(fù):地下鍋爐房、消防水泵房采用疏散走道直通室外或安全出口時,疏散距離不應(yīng)大
于15m,疏散走道與相鄰房間之間應(yīng)采取耐火極限不低于2.00h的防火隔墻和乙級防火門分
隔。
1.5.11民用建筑的地下、半地下室疏散距離如何確定?
答復(fù):1.兒童活動場所、老年人照料設(shè)施中的老年人活動場所、醫(yī)療建筑中的醫(yī)療用房、
教學(xué)建筑的教學(xué)用房、歌舞娛樂放映游藝場所等地下、半地下室疏散距離根據(jù)地上建筑的高
度確定。
2.其他民用建筑的地下、半地下室疏散距離當埋深大于10m或地下室層數(shù)為3層及以上
時,應(yīng)按照《建規(guī)》第5.5.17條有關(guān)相應(yīng)功能的高層建筑疏散距離值確定;當?shù)叵率覍訑?shù)不
超2層且埋深不大于10m時,可按照建規(guī)第5.5.17條有關(guān)相應(yīng)功能的單、多層建筑疏散距離
值確定。
3.當為觀眾廳、展覽廳、多功能廳、餐廳、營業(yè)廳等功能時,可按照《建規(guī)》第5.5.17
條第4款確定。
1.5.12設(shè)置在其他民用建筑內(nèi)的電影院,每個防火分區(qū)是否均應(yīng)設(shè)置1個獨立專用疏散樓
梯?
答復(fù):應(yīng)符合《建規(guī)》5.4.7條的規(guī)定。設(shè)置在其他民用建筑內(nèi)的電影院應(yīng)至少設(shè)置1
個獨立的安全出口和疏散樓梯;當為多個防火分區(qū)時,其每個防火分區(qū)可供使用的專用疏散
8
樓梯不應(yīng)少于一個。
1.5.13住宅建筑開向樓梯間、前室或合用前室的戶門開啟方向是否不限?
答復(fù):依據(jù)《建規(guī)》第6.4.11條,住宅建筑開向樓梯間、前室或合用前室的戶門開啟方
向不限。
1.5.14住宅門廳內(nèi)樓梯間疏散門是否為首層疏散外門?
答復(fù):首層疏散外門指的是直通室外的門,不包括住宅門廳內(nèi)的樓梯間疏散門。
1.5.15工業(yè)廠房和倉庫是否可以借用相鄰防火分區(qū)疏散?
答復(fù):工業(yè)廠房和倉庫地下部分可按《建規(guī)》第3.7.3條、3.8.3條的要求借用相鄰防
火分區(qū)作為第二安全出口,工業(yè)廠房和倉庫地上部分不應(yīng)借用相鄰防火分區(qū)疏散。
1.5.16辦公與酒店、酒店與商店、商店與辦公是否可以共用豎向疏散樓梯?
答復(fù):辦公與酒店、酒店與商店宜設(shè)置各自獨立的疏散樓梯。當確需共用豎向樓梯時,
應(yīng)同時滿足酒店及商店關(guān)于疏散寬度的要求。
商店與辦公的疏散樓梯應(yīng)按照《商店建筑設(shè)計規(guī)范》JGJ48-2014第5.1.4條的要求執(zhí)行。
1.5.17開敞式辦公空間、圖書館的大空間閱覽室、高校實驗樓的大空間實驗室最遠疏散距離
為多少?
答復(fù):可按《建規(guī)》第5.5.17條第4款執(zhí)行。
1.5.18首層擴大前室的疏散距離如何控制?
答復(fù):首層擴大前室的疏散距離一般不應(yīng)大于30m,當大于30m時可設(shè)置避難走道通至
室外。
1.5.19建筑首層利用局部架空層直通室外時,疏散距離如何控制?
答復(fù):首層架空區(qū)域較大、具備良好的自然排煙條件、無可燃物、且僅作為景觀或人員
通行時,疏散距離應(yīng)符合下列規(guī)定:
1.首層疏散外門至架空區(qū)域投影外邊緣的水平距離不應(yīng)超過15m;
2.當公共建筑的架空區(qū)域長度不小于其投影外邊緣周長的50%時,不應(yīng)超過30m。
1.5.20建筑內(nèi)相鄰兩個防火分區(qū)可否共用樓梯間?
答復(fù):除火災(zāi)危險性為甲、乙類的廠房、倉庫外,其他建筑相鄰防火分區(qū)確有困難時可
以共用疏散樓梯間,但應(yīng)符合下列規(guī)定:
1.相鄰的防火分區(qū)數(shù)量不應(yīng)超過2個;
2.每2個防火分區(qū)至少應(yīng)具備3部樓梯;
3.當共用的樓梯間采用防煙樓梯間時,應(yīng)分別設(shè)置前室(附圖1.5.20);
4.兩個防火分區(qū)開向樓梯間或樓梯間前室的門均應(yīng)采用甲級門。
9
附圖1.5.20
1.5.21丙類廠房和丙、丁類倉庫內(nèi)設(shè)置的辦公室、休息室安全疏散距離是否按民用建筑的要
求確定?
答復(fù):應(yīng)按民用建筑的相關(guān)要求確定。
1.5.22一部剪刀樓梯間能否作為廠房、倉庫一個防火分區(qū)的2個安全出口?地下車庫、多層
公共建筑可否設(shè)置剪刀樓梯間?
答復(fù):1.一部剪刀樓梯間不能作為廠房、倉庫建筑同一個防火分區(qū)的2個安全出口。
2.地下車庫、多層公共建筑可以設(shè)置剪刀樓梯間,但應(yīng)符合下列規(guī)定:
1)一個防火分區(qū)的一部剪刀樓梯間僅用于計算疏散寬度,不得僅設(shè)一部剪刀樓梯間作為
2個安全出口;
2)設(shè)置在地下車庫、多層地上公共建筑兩個防火分區(qū)處的共用剪刀樓梯間,作為各自防
火分區(qū)的安全出口時,應(yīng)采用防煙樓梯間并分別設(shè)置防煙前室。
1.5.23排屋、別墅的戶內(nèi)樓梯可否采用敞開樓梯?該樓梯地下與地上部分在首層是否可不作
防火分隔?疏散距離如何控制?
答復(fù):排屋、別墅的戶內(nèi)樓梯可采用敞開樓梯,該樓梯地下與地上部分在首層可不作防
火分隔,戶內(nèi)任一點到室外出口的距離不應(yīng)超過30m。
1.5.24廠房或倉庫的疏散樓梯間是否必須在首層直通室外?丁、戊類多層廠房可否采用敞開
樓梯間?丁、戊類多層廠房的疏散樓梯間是否需要在首層直通室外嗎?
答復(fù):廠房或倉庫的疏散樓梯間應(yīng)直通室外,確有困難可采用擴大的封閉樓梯間或擴大
前室直通室外。丁、戊類多層廠房疏散樓梯間可以采用敞開樓梯間。4層及以下的丁、戊類
多層廠房可將疏散樓梯間離直通室外的門設(shè)置在不超過15m處。
10
1.5.25歌舞娛樂放映游藝場所中的大空間部位的疏散距離能否套用《建規(guī)》第5.5.17條第
4款?
答復(fù):不可以,應(yīng)按《建規(guī)》第5.5.17條第1款執(zhí)行。
1.5.26開敞式辦公區(qū)按《建規(guī)》要求直線距離滿足37.5m(設(shè)噴淋),《建筑設(shè)計防火規(guī)范
圖示》18J811-1另有行走距離不大于45m要求,應(yīng)以哪個距離為準?
答復(fù):設(shè)計時距離不應(yīng)大于37.5m。依據(jù)《人員密集場所消防安全管理》GB/T40248-2021
第8.3.3條,行走距離不應(yīng)大于45m,適用于建成后實際使用中的消防安全管理。
1.5.27醫(yī)院潔凈手術(shù)室、ICU的疏散門可否采用電動感應(yīng)推拉門?
答復(fù):可以采用。
1.5.28地下室的封閉樓梯間在首層的疏散門可以開向首層樓梯間擴大前室嗎?
答復(fù):除規(guī)范明確要求地上、地下樓梯間需獨立設(shè)置的情況外,地下室的封閉樓梯間在
首層的疏散門可以開向首層樓梯間擴大的前室。(附圖1.5.28)
附圖1.5.28
1.5.29廠房內(nèi)設(shè)置自動噴水滅火系統(tǒng)時,廠房內(nèi)的疏散距離可否增加?
答復(fù):不可以。
1.5.30按《火通規(guī)》第7.2.1條、第7.4.1條規(guī)定設(shè)置1部疏散樓梯時,建筑首層與其余各
層的出口和疏散樓梯均各自獨立且采取防火分隔措施時,首層建筑面積可否不限?
答復(fù):可不限。
1.5.31地上建筑面積不大于200㎡的設(shè)備間可否設(shè)置1個疏散門?
答復(fù):應(yīng)符合《火通規(guī)》第7.4.2條的規(guī)定。
1.5.32高層建筑內(nèi),僅供地下室疏散樓梯使用的首層疏散外門是否可不按高層公共建筑首層
疏散外門寬度要求設(shè)置?
答復(fù):應(yīng)按《火通規(guī)》第7.1.4條執(zhí)行。
11
1.5.33餐廳與宿舍組合建造時,餐廳之上的宿舍疏散樓梯間是否需要與底部的餐廳分開?
答復(fù):學(xué)校餐廳與宿舍組合建造時,宿舍疏散樓梯間應(yīng)獨立設(shè)置;其他一般員工宿舍按
《宿舍建筑設(shè)計規(guī)范》第5.2.2條執(zhí)行。
1.5.34建筑內(nèi)部設(shè)有噴淋,但外廊未設(shè)噴淋,外廊的疏散距離是否可以增加25%?
答復(fù):不可以。
1.5.35每層需設(shè)2個安全出口的高層住宅,“三合一前室”是否允許?單元核心筒是否允
許“前室套前室”進行疏散?什么情況下,住宅核心筒需增設(shè)環(huán)形和半環(huán)形疏散走道?
答復(fù):依據(jù)《建規(guī)》第2.1.14條、5.5.2條、5.5.25條、5.5.26條、5.5.27條、5.5.28
條、6.4.11條以及《火通規(guī)》第7.3.1條的規(guī)定,住宅交通核心筒的設(shè)置應(yīng)滿足以下要求:
1.當符合《建規(guī)》5.5.28條規(guī)定時,允許“三合一”前室;
2.不允許“前室套前室”進行疏散(附圖1.5.35-1);但兩個前室可以用通道相連,當
采用通道連接2個前室時,電梯廳和消防電梯前室可視為通道(附圖1.5.35-2、附圖
1.5.35-3)。
3.開向同一前室的戶門不應(yīng)超過3戶(附圖1.5.35-4);當超過3戶時,應(yīng)從不同方
向進入前室。(附圖1.5.35-5);
4.前室作為公共區(qū)域應(yīng)滿足2個安全出口的要求,應(yīng)從公共區(qū)域連通(附圖1.5.35-6);
5.當符合只需要設(shè)置一個安全出口的條件且超過3戶時,可以通過在走道上增設(shè)防火門
的方式滿足“同一前室的戶門不應(yīng)超過3戶”的要求。
示意單元核心筒如下:
附圖1.5.36-1附圖1.5.36-2
(不允許,此單元核心筒屬于“前室套前室”)(允許,兩個樓梯間前室可以通過走道連通)
12
附圖1.5.36-3附圖1.5.36-4
(允許,兩個樓梯間前室可以通過消防電梯前室連通)(不允許,開向同一前室的戶門不應(yīng)大于3戶)
附圖1.5.36-5附圖1.5.36-6
(允許,滿足不同方位進入前室,且A+B+C≥5m)(不允許,2個安全出口未在公共區(qū)域連通)
13
1.6建筑構(gòu)造
1.6.1防火玻璃墻與防火窗有何區(qū)別?
答復(fù):防火玻璃隔墻,是指防火玻璃非承重隔墻,是由防火玻璃、鑲嵌框架和防火密封
材料組成,在一定時間內(nèi),滿足耐火穩(wěn)定性、完整性和隔熱性要求的非承重隔墻。防火玻璃
隔墻的應(yīng)用,應(yīng)符合現(xiàn)行《防火玻璃非承重隔墻通用技術(shù)條件》要求。
防火窗包括隔熱防火窗和非隔熱防火窗。隔熱防火窗(A類)是指在規(guī)定時間內(nèi),能同
時滿足耐火隔熱性和耐火完整性要求的防火窗。非隔熱防火窗(C類)是指在規(guī)定時間內(nèi),
能滿足耐火完整性要求的防火窗。
1.6.2工業(yè)建筑樓梯間一側(cè)為外墻,此外墻的燃燒性能和耐火極限是否應(yīng)滿足《建規(guī)》表3.2.1
條要求,還是滿足《建規(guī)》第3.2.12條要求?
答復(fù):工業(yè)建筑樓梯間內(nèi)隔墻按照《建規(guī)》第3.2.1條的要求執(zhí)行;樓梯間外墻與相鄰
房間交界處設(shè)置寬度不小于1.0m且耐火極限不低于2.0小時的防火隔墻時,樓梯間外墻可滿
足《建規(guī)》第3.2.12條的要求。
1.6.3建筑一層采用擴大封閉樓梯間或擴大的防煙樓梯間前室,直通室外的疏散門(普通門)
是否可作為自然通風(fēng)口?
答復(fù):疏散門不能作為自然通風(fēng)口。
1.6.4人防地下室樓梯間及前室、合用前室、消防電梯前室內(nèi)允許設(shè)置人防防爆波活門嗎?
答復(fù):允許。
1.6.5人防的地下車庫人防門能否代替甲級防火門?
答復(fù):不能。
1.6.6管道井、電纜井、電表箱能否設(shè)置在住宅建筑的敞開樓梯間內(nèi)?
答復(fù):可以。
1.6.7住宅高度小于33m的敞開樓梯間內(nèi)設(shè)管道井,其地下樓梯間內(nèi)是否可以開管井門?
答復(fù):不可以。
1.6.8消防控制室、消防水泵房開向建筑內(nèi)的門是乙級防火門嗎?
答復(fù):依據(jù)《民用建筑電氣設(shè)計標準》GB51348-2019續(xù)表23.4.2和《消防給水及消火
栓系統(tǒng)技術(shù)規(guī)范》GB50974-2014第5.5.12條第3款,消防控制室及消防水泵房開向建筑內(nèi)
的門應(yīng)為甲級防火門。
1.6.9《建規(guī)》第6.4.10條,疏散走道在防火分區(qū)處應(yīng)設(shè)置常開甲級防火門,但醫(yī)療建筑中
如手術(shù)部、ICU、檢驗科、消毒供應(yīng)室等科室流程需要獨立管理時,常開門影響使用,采用常
閉甲級門是否可以?
答復(fù):可以。
14
1.6.10醫(yī)療建筑的藥庫、檢驗科的實驗室是否需要按照《建規(guī)》第6.2.2條的要求采取防火
分隔措施?
答復(fù):藥庫、檢驗科的實驗室應(yīng)按照規(guī)范要求進行防火分隔,藥房的發(fā)藥區(qū)、檢驗科的
標本采集接收區(qū)確有困難時可以不與周邊分隔,但發(fā)藥區(qū)與藥庫之間、檢驗科的標本采集接
收區(qū)與實驗區(qū)之間應(yīng)有防火分隔。
1.6.11疏散樓梯間、前室或合用前室、普通電梯機房、消防電梯機房、消防控制室、消防水
泵房、風(fēng)機房、空調(diào)機房等直接開向室外或室外平臺的疏散門可否采用普通門?
答復(fù):1.以上部位在與相鄰房間開口間距滿足要求的前提下,疏散門可以采用普通門。
2.疏散樓梯間、前室或合用前室采用機械加壓送風(fēng)方式進行防煙時,需要維持正壓值,
可采用能自行關(guān)閉的防火門(耐火性能不作要求)或能自行關(guān)閉后具有良好密閉性能的普通
門。
1.6.12采用自然通風(fēng)方式的樓梯間、前室,其設(shè)置的可開啟外窗面積如何計算?
答復(fù):可開啟外窗面積應(yīng)考慮窗框因素,一般可按洞口面積的80%計算。
1.6.13住宅外墻為封閉陽臺時,該陽臺是否要滿足窗檻墻1.2m的高度要求?
答復(fù):封閉陽臺外墻的上、下層和同層相鄰戶開口之間應(yīng)執(zhí)行《建規(guī)》第6.2.5條。
1.6.14防火門連窗是否能等同防火門?
答復(fù):防火門連窗一般屬于超大防火門,整體防火性能難以滿足防火要求,超大消防產(chǎn)
品有著嚴格的制造要求及配備標準,尺寸寬度超2.1m、高度超2.3m的防火門難以取得消防
產(chǎn)品合格證。如采取超大規(guī)格時,應(yīng)對防火門檢驗認證并取得消防產(chǎn)品合格證。
1.6.15教學(xué)樓、宿舍等人員密集場所的封閉樓梯間是否可以采用常開防火門?
答復(fù):可以,但應(yīng)滿足《建規(guī)》第6.5.1條的要求。
1.6.16建筑內(nèi)的廚房中有明火操作間,其與相鄰上、下層開口間距按規(guī)范1.2m設(shè)置后,還
需要增設(shè)不小于1.0m寬的防火挑檐嗎?
答復(fù):應(yīng)在建筑外墻上、下層開口之間設(shè)置高度不小于1.2m的實體墻,或在外墻開口上
方應(yīng)設(shè)置寬度不小于1.0m、長度不小于開口寬度的防火挑檐。
1.6.17樓梯間首層直通室外的門洞口是否需要執(zhí)行《建規(guī)》第6.4.1條第1款的規(guī)定,門洞
口與兩側(cè)其他房間的門窗洞口距離不小于1.0m?第6.4.1條第1款條是否包含風(fēng)井百葉洞
口?
答復(fù):均應(yīng)符合《火通規(guī)》第7.1.8條第8款的規(guī)定。
1.6.18學(xué)校建筑敞開走廊區(qū)域上下層之間要考慮1.2m的窗檻墻高度嗎?
答復(fù):不需要。
15
1.6.19凸出于建筑室外的消防電梯井道和頂部能用防火玻璃嗎?
答復(fù):不允許。
1.6.20穿過建筑物進入內(nèi)院的消防車道兩側(cè)是否應(yīng)采用防火墻?
答復(fù):除為滿足《建規(guī)》第5.2.2條相鄰建筑間距要求必須設(shè)置防火墻外,其他無須設(shè)
置防火墻,但消防車道兩側(cè)外墻不應(yīng)設(shè)置影響消防車通行或人員安全疏散的設(shè)施。
1.6.21《建規(guī)》第5.4.10條中“為住宅服務(wù)的地上車庫應(yīng)設(shè)置獨立的疏散樓梯或安全出口”
中的車庫是否包括非機動車庫?
答復(fù):包括。
1.7滅火救援設(shè)施
1.7.1消防車道轉(zhuǎn)彎半徑和回車場地應(yīng)如何設(shè)計?
答復(fù):高層、多層建筑的消防車道轉(zhuǎn)彎半徑和回車場地應(yīng)符合《建規(guī)》第7.1.8條、第
7.1.9條的規(guī)定,轉(zhuǎn)彎半徑應(yīng)分別不小于12m、9m;對于建筑高度超過100m的建筑,需考慮
重型消防車救援作業(yè)的需求。重型消防車的消防車道轉(zhuǎn)彎半徑(內(nèi)徑)不小于18m,消防車
回車場不應(yīng)小于18mx18m。可采用作圖法畫出一條滿足轉(zhuǎn)彎半徑的4m寬消防車道進行校核。
(附圖1.7.1)
附圖1.7.1
1.7.2消防車道與建筑之間的距離如何控制?
答復(fù):1.兼做消防救援場地的消防車道與多層建筑外墻之間的距離不宜小于5m,當確有
困難時,應(yīng)接近5m。
2.消防車道距離建筑外墻的最大距離,一般不大于30m。
1.7.3當在消防救援面范圍內(nèi)有裙房時,消防車登高操作場地與建筑外墻的距離是算至裙房
16
外墻還是算至高層主體消防登高面外墻?
答復(fù):消防車登高操作場地距建筑外墻的距離算至高層主體外墻面。
1.7.4是否可采用隱形消防車道和消防車登高操作場地?
答復(fù):不可以。消防車道及消防車登高操作場地應(yīng)采用硬化路面,并有明確標識。
1.7.5高層住宅在“U型天井”和敞開外廊一側(cè)的消防車登高操作場地與外墻的距離如何計
算?門廳或裙房的雨篷如何控制?
答復(fù):對于設(shè)有內(nèi)天井和敞開外廊的住宅,應(yīng)優(yōu)先以朝向消防車登高操作場地的前室或
樓梯間外窗作為消防救援口,并以此救援口所在外墻作為裙房4m范圍控制線(含雨篷)(附
圖1.7.5-1)。當確有困難時,可將敞開外廊作為救援口,但外廊距離登高場地不應(yīng)超10m,
且以敞開外廊作為裙房4m范圍控制線,但凹進的敞開外廊寬度不應(yīng)小于6m。(附圖1.7.5-2)
附圖1.7.5-1
(電梯廳窗戶滿足救援要求時,消防車登高操作場地與建筑外墻的距離應(yīng)以最外側(cè)墻面計算)
17
附圖1.7.5-2
(電梯廳無窗或窗戶不滿足救援要求時,消防車登高操作場地與建筑外墻的距離可按外廊處
計算)
1.7.6多層建筑的雨篷進深是否不限?
答復(fù):多層建筑的雨篷進深可不限,但不應(yīng)影響消防救援。
1.7.7消防車是否可利用不規(guī)則(T型,Y字型等)的場地作為消防回車場地?
答復(fù):消防車可利用不規(guī)則(可為T字型,Y字型等)的場地,滿足消防回車場要求(從
交叉口起算的車道長度不應(yīng)小于12m)時,可以作為消防回車場地,具體參見附圖1.7.7-1。
但進入端車道寬度不應(yīng)小于7.0m,從交叉點起算的車道長度不應(yīng)小于相應(yīng)轉(zhuǎn)彎半徑長度。(附
圖1.7.7-2)
附圖1.7.7-1
18
附圖1.7.7-2
1.7.8住宅建筑端頭底部設(shè)置商業(yè)服務(wù)網(wǎng)點時,消防車登高操作場地未覆蓋建筑長邊,如何
處理?
答復(fù):1.當住宅建筑高度不超50m時,端頭底部設(shè)置的商業(yè)服務(wù)網(wǎng)點與住宅的交接部位
長度不應(yīng)大于10m,且消防車登高可到達該單元的公共樓梯間或每戶,該住宅可視作滿足消
防車登高操作場地要求。有條件時應(yīng)在網(wǎng)點外側(cè)或住宅另一面增設(shè)不小于10mx15m的消防車
登高操作場地,具體參見附圖1.7.8。
2.當住宅建筑高度超50m時,應(yīng)按照《火通規(guī)》第3.4.6條和《建規(guī)》的相關(guān)要求執(zhí)行。
附圖1.7.8
1.7.9消防車登高操作場地是否可以利用城市道路?
答復(fù):消防車登高操作場地原則上應(yīng)設(shè)置在建筑基地內(nèi),當受基地條件限制需設(shè)置在基
19
地外時,可以利用城鄉(xiāng)道路、廠區(qū)道路等作為消防車登高操作場地,但應(yīng)征得相關(guān)主管部門
的書面認可(如規(guī)劃、城管、市政、綠化等部門),并應(yīng)符合《火通規(guī)》《建規(guī)》的相關(guān)規(guī)
定。
1.7.10間隔布置的消防登高場地是否都需設(shè)置直通室外的樓梯或直通樓梯間的入口?
答復(fù):存在建筑不同方向的間隔布置消防登高操作場地時,每一方向至少應(yīng)有一個場地
設(shè)置直通室外的樓梯或直通樓梯間的入口,且該樓梯間應(yīng)能到達建筑每一樓層,其余場地宜
設(shè)置直通室外的樓梯或直通樓梯間的入口。
1.7.11沿相鄰兩棟高層建筑塔樓之間,布置一塊共用的消防登高救援場地,最小寬度可否按
10m+5m=15m?
答復(fù):可以。
1.7.12在消防登高操作場地與建筑之間能否設(shè)置非機動車坡道?
答復(fù):不宜設(shè)置。確有困難時,不應(yīng)影響消防車登高操作場地的救援。
1.7.13消防車登高操作場地對應(yīng)范圍內(nèi)是否要求設(shè)置通往消防電梯的入口?
答復(fù):在消防車登高操作場地對應(yīng)的范圍內(nèi)宜設(shè)置直通消防電梯的入口。
1.7.14直通消防車登高操作場地的樓梯間入口如何設(shè)置?
答復(fù):消防車登高操作場地對應(yīng)范圍內(nèi)的入口可以采用以下方式:
1.樓梯間直通室外的外門;
2.直通樓梯間或前室的門廳、疏散走道或架空層。
1.7.15消防電梯前室的短邊不應(yīng)小于2.4m,是指前室的全部空間還是指僅和電梯井道相對應(yīng)
部分的空間?
答復(fù):消防電梯前室的短邊不應(yīng)小于2.4m,前室尺寸應(yīng)是與消防電梯井道對應(yīng)的規(guī)則區(qū)
域,其他區(qū)域尺寸不做嚴格限制。
1.7.16消防電梯是否需要在住宅建筑躍層????
答復(fù):住宅建筑躍層所在的樓層不開設(shè)戶門時,消防電梯可不在躍層??俊?/p>
1.7.17住宅配建的地下汽車庫疏散樓梯間與地上住宅部分完全分開,均為獨立的安全出口
時,消防電梯需要在地下室停靠嗎?
答復(fù):消防電梯應(yīng)在地下室??俊?/p>
20
第二章給排水專業(yè)
2.1消防水源及消防設(shè)計流量
2.1.1當市政供水環(huán)網(wǎng)符合兩路消防供水條件時,從環(huán)網(wǎng)的一條供水管上接兩根引入管、中
間設(shè)有分段閥門,是否可以判定為兩路進水?
答復(fù):可以判定為兩路進水。做法可參考下圖,從環(huán)網(wǎng)的一條供水管上接兩根引入管時,
其中引入管4、4’之間必須設(shè)有分段控制閥門。
附圖2.1.1
2.1.2住宅首層及二層設(shè)置了物管用房、居委會辦公室等配套用房時,消防用水量及火災(zāi)延
續(xù)時間如何取值?
答復(fù):設(shè)置在住宅建筑的首層或首層及二層、每個分隔單元建筑面積不大于300㎡的物
管用房、居委會辦公室等配套用房,可按商業(yè)服務(wù)網(wǎng)點定性,消防用水量及火災(zāi)延續(xù)時間按
普通住宅取值。
2.1.3《消水規(guī)》第3.6.2條中的綜合樓如何定義?當住宅與其他使用功能的建筑合建時是
否定義為綜合樓?
答復(fù):《消水規(guī)》第3.6.2條中的綜合樓是由兩種或兩種以上用途的樓層組成的公共建
筑,不包括住宅與其他使用功能的建筑合建的情況。
2.1.4一棟多層廠房內(nèi)同時有甲類和丙類的生產(chǎn)車間,如何計算室內(nèi)外消火栓設(shè)計流量?
答復(fù):當丙類生產(chǎn)車間的建筑面積占比大于5%時,應(yīng)按丙類廠房的總體積進行計算室內(nèi)
外消火栓設(shè)計流量。
2.1.5地上建筑與地下室連接,地上建筑與地下室的安全出口及疏散通道均分開設(shè)置,僅電
梯能通到地下室,確定消防設(shè)計水量時,建筑物的體積應(yīng)該怎么確定,可否地上建筑與地下
室分開計算?
21
答復(fù):該建筑物的體積可以按地上建筑與地下室分開計算。
2.1.6一幢多層建筑,地下一層、地上兩層。地上一、二層為酒店客房,地下室功能為汽車
庫、各類機房及酒店配套辦公,這幢建筑地下室是否不應(yīng)按地下建筑確定消火栓設(shè)計流量,
而是按旅館建筑確定消火栓設(shè)計流量?
答復(fù):汽車庫按《車規(guī)》確定消火栓設(shè)計流量;其他部位根據(jù)建筑總體積(不含汽車庫),
按旅館建筑確定消火栓設(shè)計流量;消火栓系統(tǒng)的設(shè)計流量取汽車庫和旅館兩者大值。
2.1.7某住宅與商業(yè)合建建筑(建筑高度77.4m),其底部設(shè)有三層商業(yè)(層高4.8m,三層
商業(yè)建筑面積共計4000㎡,商業(yè)部分體積19200m3)。問:1.該建筑室內(nèi)外火災(zāi)延續(xù)時間、
消火栓系統(tǒng)設(shè)計流量如何確定?2.是否要設(shè)自動噴水滅火系統(tǒng)?
答復(fù):1.根據(jù)《建規(guī)》第5.4.10條第3款規(guī)定,室外消火栓火災(zāi)延續(xù)時間為3.0h,室
內(nèi)消火栓火災(zāi)延續(xù)時間為2.0h;室外消火栓設(shè)計流量需根據(jù)該建筑總體積計算,室內(nèi)消火栓
系統(tǒng)設(shè)計流量可按住宅建筑和公共建筑分別計算取大值。
2.根據(jù)《火通規(guī)》第8.1.9條規(guī)定,商業(yè)部分應(yīng)設(shè)自動噴水滅火系統(tǒng),住宅的公共部位
及戶內(nèi)均可不設(shè)自動噴水滅火系統(tǒng)。
2.1.8《消水規(guī)》第5.2.1條第5款,工業(yè)建筑室內(nèi)消防給水設(shè)計流量當小于或等于25L/s
時,不應(yīng)小于12m3,大于25L/s時,不應(yīng)小于18m3?!跋澜o水設(shè)計流量”是指單體建筑的
室內(nèi)消火栓設(shè)計流量,還是指包含室內(nèi)消火栓和自動噴水滅火系統(tǒng)、水幕、水炮等自動滅火
系統(tǒng)的設(shè)計流量?
答復(fù):室內(nèi)消防給水設(shè)計流量包含室內(nèi)消火栓和自動噴水滅火系統(tǒng)、水幕、水炮等自動
滅火系統(tǒng)的設(shè)計流量。
2.1.9《消水規(guī)》表3.5.2中沒有提及的幼兒園、老年人照料設(shè)施等單多層建筑,室內(nèi)消火
栓用水量如何選取?
答復(fù):幼兒園、老年人照料設(shè)施按“病房樓、門診樓等”取值。
2.2消防水池和泵房及消防水箱
2.2.1某建筑室外消防設(shè)計流量30L/s,室外消防用水量儲存于消防水池內(nèi),僅設(shè)消防水池
取水口,所有建筑均在消防水池取水口150m保護半徑內(nèi),取水口數(shù)量滿足室外消防用水量要
求,周邊的場地滿足消防車救援要求,這樣的做法是否可以?
答復(fù):不可以。
2.2.2當消防水池儲存室外消防用水量時,若消防水池分為獨立兩格,且兩格水池在泵房內(nèi)
側(cè)設(shè)有連通管(且連通管徑滿足流量要求),是否還需要按每格水池獨立設(shè)取水口?消防車
取水口個數(shù)是否要按室外消防用水量計算?
答復(fù):每格消防水池均需獨立設(shè)置取水口。取水口數(shù)量可不按室外消防用水量計算。
22
2.2.3如按設(shè)計流量的150%確定水泵額定流量,是否可選用恒壓切線泵作為消防泵?
答復(fù):恒壓切線泵不符合《消水規(guī)》第5.1.6條第4款要求,不可選用。
2.2.4當屋頂設(shè)有庫房、設(shè)備用房需設(shè)置兩個消火栓保護時,如果屋頂消防水箱最低有效水
位無法高于屋頂消防消火栓的栓口高度,采用增加消火栓系統(tǒng)增壓、穩(wěn)壓設(shè)備的揚程,是否
滿足《消水規(guī)》第5.2.2條要求?
答復(fù):不滿足。
2.2.5《消水規(guī)》中5.1.12條“消防水泵應(yīng)采取自灌式吸水”以及4.3.9條“消防水池的出
水管應(yīng)保證消防水池的有效容積能被全部利用”。問題:消防水池有效容積的最低有效水位
如何判定?是應(yīng)不低于水泵吸水口還是水泵的排氣孔?
答復(fù):對于臥式、立式消防水泵,消防水池滿足自灌式啟泵的最低有效水位應(yīng)高于泵殼
頂部排氣孔,排氣孔的高度根據(jù)所選消防水泵樣本資料確定。
2.2.6濕式報警閥設(shè)置在屋面消防水箱間內(nèi)(此時報警閥出水管高于消防水箱最低有效水
位),同時消防水箱最低有效水位高于最不利噴淋頭,此設(shè)計是否滿足《消水規(guī)》第5.2.2
條中“高位消防水箱的設(shè)置位置應(yīng)高于其所服務(wù)的水滅火設(shè)施”的要求?
答復(fù):不滿足,高位消防水箱的最低有效水位應(yīng)高于其所服務(wù)的水滅火設(shè)施,包括報警
閥的出水管。
2.2.7《消水規(guī)》第4.3.9-2條要求消防水池應(yīng)有最高和最低報警水位,但設(shè)計無具體做法
要求,如何處理?
答復(fù):消防水池水位見下圖(附圖2.2.7)。
附圖2.2.7
23
2.3消火栓給水系統(tǒng)
2.3.1室外消防采用臨時高壓給水系統(tǒng)時,是否需要設(shè)置穩(wěn)壓設(shè)施?
答復(fù):室外消防采用臨時高壓給水系統(tǒng)時應(yīng)設(shè)置穩(wěn)壓設(shè)施,并宜采用穩(wěn)壓泵穩(wěn)壓。
2.3.2消火栓箱能否在防火墻或防火隔墻上暗裝?
答復(fù):消火栓箱不應(yīng)在防火墻上暗裝;不宜在防火隔墻上暗裝,暗裝時開洞部位墻體的
耐火極限應(yīng)符合《建規(guī)》第5.1.2條的規(guī)定。
2.3.3汽車庫內(nèi)布置有連續(xù)的車位,導(dǎo)致消火栓必須得在連續(xù)車位區(qū)域內(nèi)時,能否將消火栓
箱布置在柱子背面?
答復(fù):汽車庫消火栓的位置應(yīng)方便使用和維護。當消火栓箱布置在柱子背面時,應(yīng)確保
消火栓箱門的開啟,栓門的開啟角度不應(yīng)小于160°,且應(yīng)設(shè)置指示消火栓箱位置的永久標
識。
2.3.4當高層住宅建筑的室內(nèi)消火栓箱內(nèi)配置了消防軟管卷盤時,住宅戶內(nèi)是否可不設(shè)置輕
便消防水龍?
答復(fù):住宅戶內(nèi)可不設(shè)置輕便消防水龍。
2.3.5某二層商業(yè)建筑,每個分隔單元設(shè)置內(nèi)樓梯且建筑面積不大于300㎡,是否可以每層
設(shè)置1只消火栓?
答復(fù):在滿足兩股充實水柱到達室內(nèi)任何部位的情況下,每個分隔單元可以每層設(shè)置1
只消火栓。
2.3.6《消水規(guī)》第7.4.6條要求室內(nèi)消火栓的布置應(yīng)滿足同一平面有2支消防水槍的2股
充實水柱同時達到任何部位的要求。配電房等不宜用水滅火的部位是否需滿足此條要求?
答復(fù):應(yīng)滿足。
2.3.7《消水規(guī)》第7.4.6條規(guī)定室內(nèi)消火栓的布置應(yīng)滿足同一平面有2支消防水槍的2股
充實水柱同時達到任何部位的要求。是否可以考慮水龍帶0.9的折減系數(shù),即最大有效長度
22.5米且水槍可入門統(tǒng)一標準考慮?
答復(fù):可以,行走距離按不大于22.5m確定,入門后水槍充實水柱應(yīng)能同時達到房間內(nèi)
任何部位。
2.3.8同一平面不同防火分區(qū)的消火栓,是否可以跨防火分區(qū)使用?
答復(fù):室內(nèi)消火栓可跨防火分區(qū)使用,不能跨防火卷簾使用。
2.3.9臨時高壓消防給水系統(tǒng)向多棟建筑供水時,消防水泵接合器是否需要每幢樓單獨設(shè)置,
且消防車從接合器往火災(zāi)樓棟供水是否只能進入本樓管網(wǎng),且消火栓管網(wǎng)進水管處是否需要
設(shè)置止回閥?
24
答復(fù):相鄰建筑之間設(shè)置的消防水泵接合器可以共用;消火栓管網(wǎng)進水管處不需設(shè)置止
回閥。
2.3.10高層建筑樓頂風(fēng)機房、電梯機房、水箱間等消防設(shè)施如何設(shè)置?
答復(fù):1.屋頂?shù)娘L(fēng)機房、電梯機房、樓梯間、水箱間等輔助用房占屋面面積不大于1/4
時,可不設(shè)置消火栓保護,但應(yīng)配置建筑滅火器;大于1/4時,應(yīng)按照《消水規(guī)》的要求設(shè)
置消防滅火設(shè)施。
2.一類高層公共建筑、建筑高度大于100m的住宅建筑的通風(fēng)、正壓送風(fēng)機房、排煙機房
等應(yīng)設(shè)置自動滅火系統(tǒng)。
3.排煙系統(tǒng)與通風(fēng)空氣調(diào)節(jié)系統(tǒng)共用的系統(tǒng),其排煙風(fēng)機與排風(fēng)風(fēng)機的合用機房應(yīng)設(shè)置
自動噴水滅火系統(tǒng)。
2.3.11《消水規(guī)》第6.2.1-2
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當內(nèi)容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 車床租賃與加工定制及售后服務(wù)合同
- 超詳細!環(huán)保設(shè)備制造與銷售合同
- 場記培訓(xùn)機構(gòu)實習(xí)合同范本
- 旅游景區(qū)餐具采購與旅游產(chǎn)品開發(fā)合同
- 老人睡眠障礙護理課件
- 美術(shù)說課課件模版
- 廣西礦難事故
- 安全生產(chǎn)責(zé)任制格式
- 美德故事班會課件
- 國家安全及保密教育 活動方案
- 改變觀念提高效率課件
- 立責(zé)于心履責(zé)于行全面落實企業(yè)安全生產(chǎn)主體責(zé)任課件
- 建筑工程模板施工工藝技術(shù)要點講義豐富課件
- 醫(yī)療垃圾廢物處理課件
- 位置度公差以及其計算
- DBJ03-107-2019 房屋建筑和市政工程施工危險性較大的分部分項工程安全管理規(guī)范
- 《煤的發(fā)熱量測定方法》ppt課件
- 三寶、四口、五臨邊安全培訓(xùn)PPT課件
- 護理崗位管理與績效考核-PPT課件
- 李墨林按摩療法(李墨林)237頁
- 幕墻施工安全技術(shù)交底
評論
0/150
提交評論