漏電開關(guān)模擬試驗(yàn)記錄.doc_第1頁
漏電開關(guān)模擬試驗(yàn)記錄.doc_第2頁
漏電開關(guān)模擬試驗(yàn)記錄.doc_第3頁
漏電開關(guān)模擬試驗(yàn)記錄.doc_第4頁
漏電開關(guān)模擬試驗(yàn)記錄.doc_第5頁
已閱讀5頁,還剩2頁未讀, 繼續(xù)免費(fèi)閱讀

下載本文檔

版權(quán)說明:本文檔由用戶提供并上傳,收益歸屬內(nèi)容提供方,若內(nèi)容存在侵權(quán),請(qǐng)進(jìn)行舉報(bào)或認(rèn)領(lǐng)

文檔簡介

漏電開關(guān)模擬試驗(yàn)記錄表C6-36編號(hào)06-C6-001工程名稱行政司樓維修改造工程試驗(yàn)器具漏電流測試器試驗(yàn)日期2009-10-28安裝部位型號(hào)設(shè)計(jì)要求實(shí)際測試動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)B1AL1C65N-C/2P+Vigi20A,30mA301002680B1AL1C65N-C/2P+Vigi16A,30mA301002690B1AL2C65N-C/2P+Vigi16A,30mA301002689B1AL3C65N-C/2P+Vigi20A,30mA301002697B1AL3C65N-C/2P+Vigi16A,30mA301002698B1AL4C65N-C/2P+Vigi20A,30mA301002685B1AL4C65N-C/2P+Vigi16A,30mA301002686B1AL5C65N-C/2P+Vigi16A,30mA301002682B1AL6C65N-C/2P+Vigi16A,30mA301002690B1AL6C65N-C/2P+Vigi16A,30mA301002697B1AL6C65N-C/2P+Vigi16A,30mA301002696B1AL7C65N-C/2P+Vigi16A,30mA301002693B1AL7C65N-C/2P+Vigi16A,30mA301002693B1AL7C65N-C/2P+Vigi16A,30mA3010026951AL1C65N-C/2P+Vigi20A,30mA3010026851AL1C65N-C/2P+Vigi16A,30mA301002691測試結(jié)論 經(jīng)對(duì)配電箱內(nèi)漏電開關(guān)測試,所有漏電保護(hù)裝置的動(dòng)作電流和動(dòng)作時(shí)間均符合設(shè)計(jì)及施工驗(yàn)收規(guī)范。簽字欄建設(shè)(監(jiān)理)單位施工單位北京城建亞泰建筑裝飾分公司專業(yè)技術(shù)負(fù)責(zé)人專業(yè)質(zhì)檢員專業(yè)工長本表由施工單位填寫,建設(shè)單位、施工單位各保存一份。漏電開關(guān)模擬試驗(yàn)記錄表C6-36編號(hào)06-C6-002工程名稱行政司樓維修改造工程試驗(yàn)器具漏電流測試器試驗(yàn)日期2009-10-28安裝部位型號(hào)設(shè)計(jì)要求實(shí)際測試動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)1AL1C65N-C/2P+Vigi16A,30mA3010026821AL1C65N-C/2P+Vigi16A,30mA3010026901AL1C65N-C/2P+Vigi16A,30mA3010026991AL1C65N-C/2P+Vigi16A,30mA3010026971AL1C65N-C/2P+Vigi16A,30mA3010026981AL2C65N-C/2P+Vigi20A,30mA3010026841AL2C65N-C/2P+Vigi16A,30mA3010026861AL2C65N-C/2P+Vigi16A,30mA3010026831AL2C65N-C/2P+Vigi16A,30mA3010026901AL2C65N-C/2P+Vigi16A,30mA3010026971AL3C65N-C/2P+Vigi20A,30mA3010026961AL3C65N-C/2P+Vigi16A,30mA3010026951AL3C65N-C/2P+Vigi16A,30mA3010026931AL3C65N-C/2P+Vigi16A,30mA3010026951AL3C65N-C/2P+Vigi16A,30mA3010026861AL3C65N-C/2P+Vigi16A,30mA301002691測試結(jié)論 經(jīng)對(duì)配電箱內(nèi)漏電開關(guān)測試,所有漏電保護(hù)裝置的動(dòng)作電流和動(dòng)作時(shí)間均符合設(shè)計(jì)及施工驗(yàn)收規(guī)范。簽字欄建設(shè)(監(jiān)理)單位施工單位北京城建亞泰建筑裝飾分公司專業(yè)技術(shù)負(fù)責(zé)人專業(yè)質(zhì)檢員專業(yè)工長本表由施工單位填寫,建設(shè)單位、施工單位各保存一份。漏電開關(guān)模擬試驗(yàn)記錄表C6-36編號(hào)06-C6-003工程名稱行政司樓維修改造工程試驗(yàn)器具漏電流測試器試驗(yàn)日期2009-10-28安裝部位型號(hào)設(shè)計(jì)要求實(shí)際測試動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)1AL4C65N-C/2P+Vigi20A,30mA3010026801AL4C65N-C/2P+Vigi16A,30mA3010026951AL4C65N-C/2P+Vigi16A,30mA3010026991AL4C65N-C/2P+Vigi16A,30mA3010026971AL4C65N-C/2P+Vigi16A,30mA3010026981AL4C65N-C/2P+Vigi16A,30mA3010026851AL4C65N-C/2P+Vigi16A,30mA3010026862AL1C65N-C/2P+Vigi20A,30mA3010026832AL1C65N-C/2P+Vigi16A,30mA3010026942AL1C65N-C/2P+Vigi16A,30mA3010026972AL1C65N-C/2P+Vigi16A,30mA3010026962AL1C65N-C/2P+Vigi16A,30mA3010026932AL1C65N-C/2P+Vigi16A,30mA3010026952AL2C65N-C/2P+Vigi20A,30mA3010026952AL2C65N-C/2P+Vigi16A,30mA3010026852AL2C65N-C/2P+Vigi16A,30mA301002695測試結(jié)論 經(jīng)對(duì)配電箱內(nèi)漏電開關(guān)測試,所有漏電保護(hù)裝置的動(dòng)作電流和動(dòng)作時(shí)間均符合設(shè)計(jì)及施工驗(yàn)收規(guī)范。簽字欄建設(shè)(監(jiān)理)單位施工單位北京城建亞泰建筑裝飾分公司專業(yè)技術(shù)負(fù)責(zé)人專業(yè)質(zhì)檢員專業(yè)工長本表由施工單位填寫,建設(shè)單位、施工單位各保存一份。漏電開關(guān)模擬試驗(yàn)記錄表C6-36編號(hào)06-C6-004工程名稱行政司樓維修改造工程試驗(yàn)器具漏電流測試器試驗(yàn)日期2009-10-28安裝部位型號(hào)設(shè)計(jì)要求實(shí)際測試動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)2AL2C65N-C/2P+Vigi16A,30mA3010026882AL2C65N-C/2P+Vigi16A,30mA3010026992AL2C65N-C/2P+Vigi16A,30mA3010026852AL5C65N-C/2P+Vigi16A,30mA3010026962AL5C65N-C/2P+Vigi16A,30mA3010026982AL5C65N-C/2P+Vigi16A,30mA3010026852AL5C65N-C/2P+Vigi16A,30mA3010026862AL5C65N-C/2P+Vigi16A,30mA3010026882AL5C65N-C/2P+Vigi16A,30mA3010026972AL4C65N-C/2P+Vigi20A,30mA3010026972AL4C65N-C/2P+Vigi16A,30mA3010026962AL4C65N-C/2P+Vigi16A,30mA3010026942AL4C65N-C/2P+Vigi16A,30mA3010026932AL4C65N-C/2P+Vigi16A,30mA3010026952AL4C65N-C/2P+Vigi16A,30mA3010026852AL4C65N-C/2P+Vigi16A,30mA301002692測試結(jié)論 經(jīng)對(duì)配電箱內(nèi)漏電開關(guān)測試,所有漏電保護(hù)裝置的動(dòng)作電流和動(dòng)作時(shí)間均符合設(shè)計(jì)及施工驗(yàn)收規(guī)范。簽字欄建設(shè)(監(jiān)理)單位施工單位北京城建亞泰建筑裝飾分公司專業(yè)技術(shù)負(fù)責(zé)人專業(yè)質(zhì)檢員專業(yè)工長本表由施工單位填寫,建設(shè)單位、施工單位各保存一份。漏電開關(guān)模擬試驗(yàn)記錄表C6-36編號(hào)06-C6-005工程名稱行政司樓維修改造工程試驗(yàn)器具漏電流測試器試驗(yàn)日期2009-10-28安裝部位型號(hào)設(shè)計(jì)要求實(shí)際測試動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)2AL4C65N-C/2P+Vigi16A,30mA3010026822AL4C65N-C/2P+Vigi16A,30mA3010026922AL4C65N-C/2P+Vigi16A,30mA3010026892AL3C65N-C/2P+Vigi20A,30mA3010026972AL3C65N-C/2P+Vigi16A,30mA3010026982AL3C65N-C/2P+Vigi16A,30mA3010026822AL3C65N-C/2P+Vigi16A,30mA3010026862AL3C65N-C/2P+Vigi16A,30mA3010026822AL3C65N-C/2P+Vigi16A,30mA3010026902AL3C65N-C/2P+Vigi16A,30mA3010026973AL1C65N-C/2P+Vigi20A,30mA3010026963AL1C65N-C/2P+Vigi16A,30mA3010026943AL1C65N-C/2P+Vigi16A,30mA3010026933AL1C65N-C/2P+Vigi16A,30mA3010026943AL1C65N-C/2P+Vigi16A,30mA3010026853AL1C65N-C/2P+Vigi16A,30mA301002694測試結(jié)論 經(jīng)對(duì)配電箱內(nèi)漏電開關(guān)測試,所有漏電保護(hù)裝置的動(dòng)作電流和動(dòng)作時(shí)間均符合設(shè)計(jì)及施工驗(yàn)收規(guī)范。簽字欄建設(shè)(監(jiān)理)單位施工單位北京城建亞泰建筑裝飾分公司專業(yè)技術(shù)負(fù)責(zé)人專業(yè)質(zhì)檢員專業(yè)工長本表由施工單位填寫,建設(shè)單位、施工單位各保存一份。漏電開關(guān)模擬試驗(yàn)記錄表C6-36編號(hào)06-C6-006工程名稱行政司樓維修改造工程試驗(yàn)器具漏電流測試器試驗(yàn)日期2009-10-28安裝部位型號(hào)設(shè)計(jì)要求實(shí)際測試動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)3AL1C65N-C/2P+Vigi16A,30mA3010026843AL2C65N-C/2P+Vigi20A,30mA3010026943AL2C65N-C/2P+Vigi16A,30mA3010026893AL2C65N-C/2P+Vigi16A,30mA3010026973AL2C65N-C/2P+Vigi16A,30mA3010026983AL2C65N-C/2P+Vigi16A,30mA3010026853AL2C65N-C/2P+Vigi16A,30mA3010026853AL2C65N-C/2P+Vigi16A,30mA3010026823AL2C65N-C/2P+Vigi16A,30mA3010026952AL8C65N-C/2P+Vigi20A,30mA3010026972AL8C65N-C/2P+Vigi20A,30mA3010026962AL8C65N-C/2P+Vigi20A,30mA3010026934AL1C65N-C/2P+Vigi20A,30mA3010026934AL1C65N-C/2P+Vigi16A,30mA3010026954AL1C65N-C/2P+Vigi16A,30mA3010026854AL1C65N-C/2P+Vigi16A,30mA301002692測試結(jié)論 經(jīng)對(duì)配電箱內(nèi)漏電開關(guān)測試,所有漏電保護(hù)裝置的動(dòng)作電流和動(dòng)作時(shí)間均符合設(shè)計(jì)及施工驗(yàn)收規(guī)范。簽字欄建設(shè)(監(jiān)理)單位施工單位北京城建亞泰建筑裝飾分公司專業(yè)技術(shù)負(fù)責(zé)人專業(yè)質(zhì)檢員專業(yè)工長本表由施工單位填寫,建設(shè)單位、施工單位各保存一份。漏電開關(guān)模擬試驗(yàn)記錄表C6-36編號(hào)06-C6-007工程名稱行政司樓維修改造工程試驗(yàn)器具漏電流測試器試驗(yàn)日期2009-10-28安裝部位型號(hào)設(shè)計(jì)要求實(shí)際測試動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)動(dòng)作電流(mA)動(dòng)作時(shí)間(mS)4AL1C65N-C/2P+Vigi16A,30mA3010026834AL2C65N-C/2P+Vigi20A,30mA3010026934AL2C65N-C/2P+Vigi16A,30mA3010026894AL2C65N-C/2P+Vigi16A,30mA3010026974AL2C65N-C/2P+Vigi16A,30mA3010026984AL2C65N-C/2P+Vigi16A,30mA3010026854AL2C65N-C/2P+Vigi16A,30mA3010026862AL7C65N-C/2P+Vigi20A,30mA3010026822AL7C65N-C/2P+Vigi20A,

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。

評(píng)論

0/150

提交評(píng)論