1、ICS 29.240.30F 21Record No. J5222006Electric Power Industry Standard of the Peoples Republic of ChinaPDL / T 5340 2006Technical Code for Designing of Telecommunication Lines Against Danger Effects from DC Power Transmission LinesIssue Date: May 6, 2006ImpIementation Date: October 1, 2006Issued by th

2、e NationaI DeveIopment and Reform Commission of the PeopIes RepubIic of ChinaElectric Power Industry Standard of the Peoples Republic of ChinaPDL / T 5340 2006Technical Code for Designing of Telecommunication Lines Against Danger Effects from DC Power Transmission LinesTranslation sponsored by: Chin

3、a Electric Power Planning & Engineering Association Translated by: SUNTHER Consulting Co., Ltd.Reviewed by: Central Southern China Electric Power Design InstituteCHINA ELECTRIC POWER PRESS BEIJING, 2013圖書在版編目(CIP)數(shù)據(jù)DL/T 53402006 直流輸電線路對電信線路危險影響防護設(shè)計技術(shù)規(guī)定=Technical code for designing of telecommunicati

4、on lines against danger Effects from DC power transmission lines: 英文 / 中華人民共和國國家發(fā)展和改革委員會發(fā)布. 北京:中國電力出版社,2013.5ISBN 978-7-5123-4080-0. D . 中 . 直流輸電線路-影響-通信線路防護-設(shè)計規(guī)范-中國-英文 . TN913.3-65中國版本圖書館CIP 數(shù)據(jù)核字(2013)第 029582 號中國電力出版社出版(北京市東城區(qū)北京站西街 19 號 100005 ) 北京博圖彩色印刷有限公司印刷*2013 年 5 月第一版2013 年 5 月北京第一次印刷850 毫米1

5、168 毫米 32 開本 1.125 印張 24 千字敬 告 讀 者本書封底貼有防偽標簽,刮開涂層可查詢真?zhèn)伪緯缬杏⊙b質(zhì)量問題,我社發(fā)行部負責退換版 權(quán) 專 有翻 印 必 究DL / T 5340 2006ContentsForeword1 Scope12 Terms and Definitions23 Fault Conditions of DC Transmission Lines and Operating Conditions of Telecommunication Line Circuits64 Permissible Value of Danger Effects75 Calc

6、ulation of Danger Effects116 Protective Measures17Appendix A (Normative)Calculation of Mutual InductiveCoefficient of Infinite LongAdjacent Lines19Appendix B (Normative)Calculation of the Inductance to Groundof the Conductors of DC Transmission Lines23IDL / T 5340 2006ForewordThis code is prepared i

7、n response to the arrangement made by the Notice on Issuing the Plan for Supplementing Electric Power Industry Standard 2003 Issued by the General Office of National Development and Reform Commission (FGBGY2003873).The large-scale construction of HVDC transmission lines and the increasingly growing

8、transmission voltages are bound to cause electromagnetic interference to the adjacent telecommunication lines. Unfortunately, no material and literature in China and foreign countries has systematically presented the harmful effects caused by DC transmission lines to the adjacent telecommunication l

9、ines and the relevant protection measures, the relevant influencing mechanism and the calculation methods in this respect. Additionally, no unified calculation and design standard is available in China. In light of this, it makes great sense to establish this code to support the engineering design o

10、f DC transmission lines, address the actual problems of a project, improve the design quality of communication protections, make the project construction cycle less time consuming and reduce the investment costs of the project.This code places emphasis on describing the unique characteristics of the

11、 design of DC transmission lines that may cause adverse effects to the adjacent telecommunication lines. Since the design of DC transmission lines has much in common with that of AC transmission lines, DL/T 5033 2006 The Design Rules of Telecommunication Lines Against Danger and Interference Effects

12、 From Power Transmission Lines may be taken as a reference.IIDL / T 5340 2006Appendices A and B to this code are normative. This code is proposed by China Electricity Council.This code is solely managed and interpreted by Technical Committee on Electric Power Planning and Engineering of Standardizat

13、ion Administration of Power Industry.This code is mainly drafted by Central Southern China Electric Power Design Institute.The organizations participating in drafting this code include China Power Engineering Consulting Group Corporation, Northeast China Electric Power Design Institute, East China E

14、lectric Power Design Institute, Southwest Electric Power Design Institute, and Guangdong Electric Power Design and Research Institute.The leading authors of this code include Xiong Wanzhou, Wang Weihua, Zeng Liansheng, Xie Xing, Miao Guiliang, Zhao Shixiong, Yu Wenzhi, Han Yanming, Wei Dejun, and Me

15、ng Xianbin.This code is translated by SUNTHER Translation & Solutionsunder the authority of China Electric Power Planning & Engineering Association.IIIDL / T 5340 20061ScopeThis code specifies the permissible value of danger effects on telecommunication lines from DC transmission lines, presents the

16、 calculation methods of danger effects, and provides necessary parameters and protective measures.This code applies to the design of the protections that protect telecommunication lines from danger effects caused by the adjacent DC transmission lines.In addition to this code, the design of the prote

17、ctions that protect telecommunication lines from danger effects caused by the adjacent DC transmission lines shall comply with the provisions of the national standards currently in force as well.1DL / T 5340 20062Terms and DefinitionsThe following terms and definitions apply to this code.2. 0. 1Tele

18、communication linesCommunication lines in forms of overhead open wire, overhead or buried cable, overhead or buried telecommunication optical fiber cable, and railway signal electrical line, cable television (signal, feed and subscriber) line, and remote control and signaling line.2. 0. 2Railway sig

19、nal electrical linesCables and overhead open wires that transmit information for railway signal system, such as relay semi-automatic or automatic obturate way circuit, remote control line, remote signaling line, and railway circuit within the automatic obturate section.2. 0. 3Danger effectsThe induc

20、ed voltage and current on telecommunication lines caused by DC transmission lines can possibly endanger the safety of telecommunication operation and maintenance personnel, damage telecommunication lines or equipment, cause fire to buildings and structures, or cause wrong operation of railway signal

21、ing equipment which will bring hazards to traffic safety.2. 0. 4AdjacencyThe relative position of telecommunication lines to DC transmission lines when the electromagnetic effects of DC2DL / T 5340 2006transmission lines may cause danger to the telecommunication lines.Parallel adjacency describes a

22、situation in which the variation of distance between two adjacent lines does not exceed 5% of the arithmetic mean of the distance. Oblique adjacency describes a situation in which the variation of distance between two adjacent lines exceeds 5% and increases or decreases linearly (both DC transmissio

23、n lines and telecommunication lines having no turning points).2. 0. 5Adjacent distanceThe distance obtained by perpendicularly drawing a line from any point on the center line of the telecommunication line to that of the DC transmission line.2. 0. 6Length of adjacent sectThe projected length of the

24、adjacent section of the telecommunication lines on the DC transmission lines.2. 0. 7Cross-overThe situation in which DC transmission lines pass through telecommunication lines from overhead.2. 0. 8Inductive coupling effectEffects of current in DC transmission lines or from the ground on telecommunic

25、ation lines through inductive coupling.2. 0. 9Capacitive coupling effectEffects of voltage of DC transmission lines on telecommunication lines through capacitive coupling.3DL / T 5340 20062. 0. 10Resistive coupling effectEffects on the grounding systems and the burial cables of telecommunication off

26、ices (stations) caused by ground resistive coupling when the short-circuit current flowing through the grounding system of DC power transmission line towers results in a potential difference between the direct grounding area and the remote ground area.2. 0. 11Magnetic induction endlong electromotanc

27、ePotential difference between any two points on a telecommunication line caused by the current in DC transmission line and the ground.2. 0. 12Magnetic induction ground voltageThe ground potential induced at any point on a telecommunication line by the current in the DC transmission line and the grou

28、nd.2. 0. 13Railway circuitA circuit in which the tracks of railway are used as conductors to check if there are trains on the railway, transmit the information about the presence of trains and form a communication circuit between the ground and the train.2. 0. 14Automatic obturate way circuitA circu

29、it used to determine the traveling directions of trains when they are traveling bi-directionally on the same railway within the automatic obturate section (normally in the same route of the4DL / T 5340 2006communication lines of railways).2. 0. 15Broadcasting signal linesSignal transmission lines of

30、 the wired broadcasting signal transmission system.2. 0. 16Broadcasting feedback linesFeedback transmission lines of the wired broadcasting power transmission system.2. 0. 17Broadcasting users linesThe transmission lines correspond the output end of transformers to the input end of users equipment u

31、sed in the wired broadcasting power transmission system.5DL / T 5340 20063Fault Conditions of DC Transmission Lines and Operating Conditions of Telecommunication Line Circuits3.0.1 1 The fault conditions of a DC transmission line that may have danger effects on the adjacent telecommunication lines s

32、hall include the following situations:1 Grounding short-circuit of the pole conductors of mono-polar operated DC transmission lines;2 Grounding short-circuit of conductors of one pole of bipolar operated DC transmission lines.3.0.2 2 When calculating the danger effects on adjacent telecommunication

33、lines caused by DC transmission lines, the following modes should be selected according to the operating conditions of the telecommunication lines.1 The telecommunication lines have one end grounded throughlow impedance and the other end grounded through high impedance (open circuit).2 The telecommu

34、nication lines have both ends grounded through low impedance.3 The telecommunication lines have both ends grounded through high impedance (open circuit).6DL / T 5340 20064 Permissible Value of Danger Effects4.0.1 1 In the event of grounding short-circuit fault of the pole conductors of DC transmissi

35、on lines, the endlong electromotance or the ground voltage induced on the telecommunication lines of the overhead open wires shall not exceed 3000 V (peak value).4.0.2 2 In the event of grounding short-circuit fault of DC transmission lines, the permissible value of endlong electromotance or the gro

36、und voltage induced on the core wires of the telecommunication cable lines shall comply with the following requirements.1 Where isolation transformers or lightning protectors areprovided at both ends of the core wires of the telecommunication cable lines:1) For telecommunication cable lines free of

37、long-distance power supplyUs0.85UDt(4.0.2-1)Us1.2UAt(4.0.2-2)2) For telecommunication cable lines with long-distance power supply in conductor-to-earth modeUs0.85UDt-Urs(4.0.2-3)Us1.2UAt-Urs(4.0.2-4)3) For telecommunication cable lines with long-distance power supply in conductor-to-conductor mode a

38、nd grounded at the center pointUs0.85UDt- Urs2(4.0.2-5)7DL / T 5340 2006Where:Us1.2UAt- Urs2(4.0.2-6)UDt DC test voltage of cable core and grounding sheath, V;UAt AC test voltage (effective value) of cable core and grounding sheath, V;Urs long-distance power supply voltage of the sections for which

39、the effects are calculated;Us induced voltage (peak value) of the cable core in the event of faults of DC transmission lines, V.2 When the conditions in clause 1 of 4.0.2 are not satisfied, thevalues specified in 4.0.1 shall be used; in this case, the insulation electric strength of the telecommunic

40、ation lines and equipment at both ends of them as well as the over-current capability of the protection unit shall be considered.4.0.3 3 In the event of grounding short-circuit fault of the pole conductor of DC transmission line, the magnetic induction voltages (including magnetic inductive endlong

41、electromotance and magnetic inductive ground voltage) generated on the telecommunication optical fiber cables shall meet the following provisions:1 For telecommunication optical fiber cable lines which havemetal wire pairs and are free of long-distance power supply:Us0.85UDt(4.0.3-1)2 For telecommun

42、ication optical fiber cable lines which have metal wire pairs and long-distance power supply:1) Telecommunication optical fiber cable lines with long-distance power supply in conductor-to-earth mode:Us0.85UDt-Urs(4.0.3-2)8DL / T 5340 20062) Telecommunication optical fiber cable lines with long-dista

43、nce power supply in conductor-to-conductor mode and grounded at the center point:Us0.85UDt- Urs2(4.0.3-3)3 Telecommunication optical fiber cable lines with metal members but free of metal wire pairs:Us0.85UDt(4.0.3-4)Where:UDt DC test voltage of outer insulating sheath of optical fiber cables, V;Urs

44、 long-distance power supply voltage of the sections for which the effects are calculated, V;Us induced voltage (peak value) of the metal members of the optical fiber cables in the event of faults of DC transmission lines, V.4 Danger effects may not be considered for optical fiber cablesfree of metal

45、 members and wire pairs.4.0.4 4 When grounding short-circuit fault occurs at one pole conductor of the DC transmission line, the permissible value of potential difference between the adjacent buried telecommunication cable cores, the metal wire pairs of the telecommunication optical fiber cable, the

46、 metal members and the ground, and the permissible value of potential rise on grounding devices disposed at telecommunication office (station) shall comply with the provisions of 4.0.2 and 4.0.3.4.0.5 5 Where inductive coupling effect and resistive coupling effect are simultaneously caused by DC tra

47、nsmission lines to underground telecommunication cables or telecommunication optical fiber cables,9DL / T 5340 2006the resultant value shall comply with the provisions of 4.0.2 and 4.0.3.4.0.6 6 If the composite effects of magnetic induction endlong electromotance and the ground potential rise excee

48、ds the permissible value, the ground voltage of the telecommunication line conductors must be further calculated according to the operating conditions of the telecommunication circuit described in 3.0.2.10DL / T 5340 20065 Calculation of Danger Effects5.1 1Provisions of Calculation5.1.1 1 When groun

49、ding short-circuit fault occurs at DC transmission lines, the magnetic danger effects on the telecommunication lines caused by the fault current originating from the rectifier station side shall be considered; when checking the ground voltage of the telecommunication lines, the magnetic danger effec

50、ts on the telecommunication lines caused by the fault current originating from the inverter station side may be considered.5.1.2 2 The effects caused by DC transmission lines to the underground telecommunication cable lines and the telecommunication optical fiber cable lines shall include resistive

51、coupling effect which shall be calculated based on the short-circuit current flowing through the tower grounding device when one pole conductor of the DC transmission lines experiences grounding short-circuit faults.5.1.3 3 Where DC transmission lines cause both inductive and resistive coupling effe

52、cts to buried telecommunication cable lines and optical fiber cable lines, the resultant effect shall be calculated as the square root of the sum of squares of both effect values.5.1.4 4 For design of telecommunication lines with dischargers for protection at locations such as repeaters, junction ca

53、binets and junction boxes, the ground voltage of telecommunication lines shall be considered when the dischargers operate.5.1.5 5 For DC transmission lines with ground wires, the magnetic11DL / T 5340 2006danger effects may be considered according to the return current effect in ground wires.5.2 2Ca

54、lculation of Magnetic Danger Effects5.2.1 1 When one pole conductor of DC transmission lines experiences grounding short-circuit fault, the endlong electromotance induced by the short-circuit current on telecommunication lines through inductive coupling shall be calculated using Formula 5.2.1.nWhere

55、:E= SwMili Is sti =1(5.2.1)Emagnetic induction endlong electromotance on telecommunication lines, V;w apparent angular frequency affecting the current, rad/s,w =2 f, f=30 Hz;Mi mutual induction coefficient of the ith adjacent section between the DC transmission line and the telecommunication line at 30 Hz, H/km;il length of the ith adjacent section between the DCtransmission line and the telecommunication line, km;ls sum of weighted values of the short-circuit current components at individual frequencies when one pole conductor of the

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負責。
  • 6. 下載文件中如有侵權(quán)或不適當內(nèi)容,請與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

評論

0/150

提交評論