文檔簡介

《HighVoltageEquipmentTesting》InsulationResistanceTest主講人:何發(fā)武(副教授)OperatingWorksheet:OperatingWorksheet:TableofContents01Followme02Workshop03Training01FollowmeⅠ.OverviewofinsulationresistanceMeasuringtheinsulationresistance,particularlytheabsorptionratioandpolarizationindexofthetransformer,ishighlysensitiveinassessingtheoverallinsulationcondition.Thismethodeffectivelyidentifiesissueslikemoisture,surfacecontamination,andthrough-holedefectsinthetransformerinsulation.Itcanalsodetectproblemssuchasshortcircuits,grounding,orcracksintheporcelaininsulation.Insulatingmaterialswithinthetransformer,includingtheinternalironcore,clamps,andthrough-bolts,playacrucialroleinensuringinsulation.Theinsulationinthewindingsectionscanwithstandhighvoltagelevels.Ⅰ.OverviewofinsulationresistanceWhentheinsulationofthetransformeriscompromisedduetopiercing,damagetotheceramicinsulation,connectionoftheleadwiretothecasing,ortheoccurrenceofmetalshort-circuitfaults,therewillbeanoticeablechangeintheinsulationresistance.Moreover,thechangeininsulationresistancebeforeandafterequipmentdryingissignificantlylargerthanthechangeinthedissipationfactorofthedielectric.Ⅰ.OverviewofinsulationresistanceForinstance,inthe7,500

kVAtransformer,thedissipationfactormaychangeby2.5timesbeforeandafterdrying,whiletheinsulationresistancemaychangebymorethan40times.Thischangeisquiteremarkable.Therefore,evaluatingtheinsulationresistanceofcomponentsliketheironcorecaneffectivelydetectoverallmoistureinthetransformerinsulation,surfacecontaminationofcomponents,andconcentratedthrough-holedefects.Ⅰ.OverviewofinsulationresistanceTheabsorptionratioKreferstotheratiooftheinsulationresistancevalueat60secondstotheinsulationresistancevalueat15seconds.ThepolarizationindexPIreferstotheratiooftheinsulationresistancevalueat10minutestotheinsulationresistancevalueat1minuteduringtesting.K=R60/R15 (2-1)PI=R600/R60 (2-2)Ⅰ.OverviewofinsulationresistanceThepolarizationindexisanimportantparameterforassessingwhetherlargepowerequipmentisaffectedbymoisture.Forthelargetransformer,generator,powercable,andparallelcapacitor,duetotheirlargesamplecapacitanceandcompositeinsulationmaterials,theabsorptioncurrentdecaysslowly,andthepolarizationprocessoftencannotbecompletedwithin1minute.Therefore,itisnecessarytomeasurefor10minutes,andcomparedtofactorytests,theinsulationconditionisjudgedusingthepolarizationindex(PI).Ⅰ.OverviewofinsulationresistanceTaketransformersasanexample,duetotheimprovementindryingprocesses,theinsulationresistanceoftransformersisincreasingandcangenerallyreachseveraltensofthousandsofmegaohms,causingthepolarizationprocessofthetransformertobecomelonger.Therefore,thepolarizationindexshouldbemeasured,andtheabsorptionratiotestresultsshouldnotbeusedtodetermineifthetransformerisqualified.Ⅰ.OverviewofinsulationresistanceWhentheinsulationresistanceofthetransformerexceeds10,000M,thereisnoneedtoconsidertheabsorptionratioorpolarizationindex.Therefore,whenconductinginsulationresistance,absorptionratio,orpolarizationindextesting,theresultsshouldbeanalyzedandjudgedincombinationwithspecificelectricalequipment.Inthe“Regulations”,itisstipulatedthattheabsorptionratioandpolarizationindexarenotconvertedbytemperature.Ⅱ.TestStandardsAccordingtothe“RegulationsonPreventiveTestingofPowerEquipment”,itisstipulatedthattheabsorptionratioshouldnotbelessthan1.3orthepolarizationindexshouldnotbelessthan1.5asthecompliancestandard.AsshowninTable2-1,2-2.Aftermeasuringinsulationresistance,itshouldbeuniformlyconvertedto20Candcomparedwiththefactoryvalueorthevaluefromthepreviousmeasurementcycle.StatusPolarizationIndex(PI)HazardousLessthan1.0Poor1.0–1.1suspicious1.1–1.25fair1.25–2.0goodGreaterthan2.0Table2-1

Referencestandardsforassessinginsulationconditionbasedonthepolarizationindex.Ⅱ.TestStandardsTable2-2QualifiedstandardforinsulationresistancetestⅡ.TestStandardsTable2-2QualifiedstandardforinsulationresistancetestⅡ.TestStandardsTable2-2Qualifiedstandardforinsulationresistancetest02WorkshopⅠ.MeasurementmethodsDuringthemeasurement,recordtheambienttemperatureandhumidity.Measuretheinsulationresistanceandabsorptionratiosequentiallyforeachwindingwithrespecttogroundandbetweenotherwindings.Short-circuitallleadsofthewindingbeingtested,andshort-circuitandgroundallleadsofthenon-testedwindings.Thisallowsformeasuringtheinsulationconditionbetweenthetestedwindingandground,aswellasbetweenthetestedwindingandthenon-testedwindings,whileavoidingtheinfluenceofresidualchargesinthenon-testedwindingsonthemeasurement.Ⅰ.MeasurementmethodsDuringthemeasurement,recordtheambienttemperatureandhumidity.Measuretheinsulationresistanceandabsorptionratiosequentiallyforeachwindingwithrespecttogroundandbetweenotherwindings.Short-circuitallleadsofthewindingbeingtested,andshort-circuitandgroundallleadsofthenon-testedwindings.Thisallowsformeasuringtheinsulationconditionbetweenthetestedwindingandground,aswellasbetweenthetestedwindingandthenon-testedwindings,whileavoidingtheinfluenceofresidualchargesinthenon-testedwindingsonthemeasurement.Ⅰ.MeasurementmethodsFigure2-1showsthefunctionaldiagramoftheinsulationresistancetester,Figure2-2showsthewiringdiagramformeasuringtheinsulationresistanceofthehigh-voltagewindingofthehigh-voltagegenerator.Figure2-1

InsulationresistancetesterfunctiondiagramFigure2-2Wiringdiagramforinsulationresistancemeasurementofthree-Phasetransformerhigh-voltagewindingⅠ.MeasurementmethodsWhenmeasuringtheinsulationresistanceofwindingsratedat1

kVandbelow,useamegohmmeterwitharangenotexceeding0.5

kV.Forwindingswithvoltagesof2.5

kVandabove,amegohmmeterwithavoltageof1

kVor2.5

kVcanbeused.Forwindingsratedat10

kVandabove,usea5

kVinsulationresistancetesterandrecordthetopoiltemperature.Ⅰ.MeasurementmethodsAnalysisofinsulationresistancemeasurementresultsisconductedusingacomparativemethod,primarilyrelyingoncomparingtheresultswithprevioustestresultsofthistransformer.Generally,theswitchingtestvalueshouldnotbelowerthan70%ofthefactorytestvalue.Whenconvertinginsulationresistancetotheinsulationresistanceat20C,transformersupto220

kVshouldhaveavaluenotlessthan800

M,andthetransformerof500

kVshouldhaveavaluenotlessthan2,000

M.Theabsorptionratioshouldnotbelowerthan1.3.Ⅰ.MeasurementmethodsWhenmeasuringtheinsulationresistanceofwindingsratedat1

kVandbelow,useamegohmmeterwitharangenotexceeding0.5

kV.Forwindingswithvoltagesof2.5

kVandabove,amegohmmeterwithavoltageof1

kVor2.5

kVcanbeused.Forwindingsratedat10

kVandabove,usea5

kVinsulationresistancetesterandrecordthetopoiltemperature.WhenmeasuringtheabsorptionratioKofthetransformer,theironcoremustbegrounded.Iftheironcoreisnotgrounded,insulationmaterialssuchascardboardbetweenthetransformerwindingsandthecasingareintroducedinseries,causinganincreaseinthemeasuredinsulationvalueR15,resultinginadecreaseintheabsorptionratio,whichcaneasilyleadtoanunqualifiedresult.Ⅰ.WorkspecificationWhenconductinghigh-voltagetestsonelectricalequipment,afencemustbesetuparoundtheworkarea,withasignhangingonthefencewith“NoEntry,HighVoltageDanger!”Guardsshouldbestationedthere.Onlyoneworkgroupisallowedtoperformhigh-voltagetestsononepieceofequipmentwithinaspecificelectricalconnection.Agroundingwireshouldbeinstalledonthemaintenancesideofthedisconnectionpoint,andasignwith“NoEntry,HighVoltageDanger!”shouldbehungonthehigh-voltagetestside,facingthemaintenanceworkarea.Ⅱ.TechnicalstandardsForthelargepowertransformerof35

kVandbelow,theabsorptionratioshouldnotbelowerthan1.3.Forthelargepowertransformerswithvoltagesequaltoorhigherthan60

kV,theabsorptionratioshouldbecontrollednotlowerthan1.5.Inthecommissioningtestofthepowerindustry,thecorrespondingrequirementfortheabsorptionratioisnotlowerthan1.2and1.3,respectively.Ⅲ.JudgmentandAnalysisInsulationresistancecanpartiallyreflecttheinsulationconditionofwindings.However,itisgreatlyinfluencedbyfactorssuchasinsulationstructure,operationmode,environment,equipmenttemperature,insulationoilquality,andmeasurementerrors.Therefore,duringinstallation,theinsulationresistancevalueR60sshouldnotbelowerthan70%ofthemeasuredinsulationresistancevalueduringthefactorytest.Duringpreventivetests,theinsulationresistancevalueR60sshouldnotbelowerthan50%ofthemeasuredvalueafterinstallation,majorrepairs,andpriortobeingputintooperation.Forthe500

kVtransformer,underthesametemperatureconditions,itsinsulationresistanceshouldnotbelowerthan70%ofthefactoryvalue,andtheminimumresistancevalueat20Cshouldnotbelessthan2,000

M.Ⅳ.SpecialNoticesDuetothedesignedshieldingloopinthemegohmmeter’sinternalcircuitrytoensuremeasurementaccuracy,itisimportanttocorrectlyconnectthecircuit.TheL-terminalofthelineshouldbeconnectedtotheconductivepartofthetestspecimeninsulatedfromtheground,whiletheE-terminalshouldbeconnectedtothegroundingendofthetestspecimen.Interchangingtheseconnectionsisnotallowedasitmayresultinmeasurementerrors.Ⅳ.SpecialNoticesSelectingamegohmmeterwithameasuringvoltagethatmatchestheratedvoltageofthespecimeniscrucial.Thebreakdownvoltageoftheinsulationmaterialisrelatedtotheappliedvoltage,andthemeasurementaccuracyofinsulationcharacteristicsalsodependsontheappliedvoltage.Ifthemeasuringvoltageistoolow,itwillnotaccuratelymeasuretheinsulationcondition,andifitistoohigh,itmaydamagetheinsulationofthespecimen.Ⅳ.SpecialNoticesTemperatureandhumidityshouldberecordedduringthemeasurement.Theabsorptionratioistemperature-dependent.Forverygoodinsulation,theabsorptionratioincreaseswithtemperature.Forpoorinsulationsuchasoilorpaperinsulation,theabsorptionratiodecreaseswithtemperature.Inequipmentwithseveremoisture,theinsulationresistancevariessignificantlywithtemperature.Iftheequipmenttransitionsfromoperationtoshutdown,itshouldbemeasuredaftertheinternalinsulationhascooleddowncompletely,andtheinsulationresistanceshouldbeconvertedtotheinsulationresistanceat20C.Ⅳ.SpecialNoticesForneworRepairedoil-immersedtransformers,Itwilltakedozensofhourstowaitfortheoilcirculationandbubbleescapebeforemeasuringtheinsulationresistance.Forthetransformerwithacapacityof8,000

kVAorabove,theyshouldbeleftstandingforatleast20hours,whileotherlower-capacitytransformersrequireastandingtimeofatleast5hours.Thequalityofoilinthetransformerdirectlyaffectstheinsulationresistancevalue.Thebettertheoilquality,thehighertheinsulationresistanceandthehighertheabsorptionratio.

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

評論

0/150

提交評論