42/42空氣調(diào)節(jié)課程設(shè)計(jì)講明書(shū)課題名稱:濟(jì)南市某街道辦公樓空調(diào)系統(tǒng)

學(xué)生學(xué)號(hào):

131807011

專業(yè)班級(jí):建筑環(huán)境與能源應(yīng)用工程學(xué)生姓名:蔡世坤學(xué)生成績(jī):

指導(dǎo)教師:

崔鵬

教師職稱:設(shè)計(jì)日期:_2017年1月________第一章設(shè)計(jì)資料 41.1設(shè)計(jì)題目 41.2設(shè)計(jì)差不多參數(shù) 41.2.1室外參數(shù) 41.2.2土建參數(shù) 5第二章負(fù)荷計(jì)算 62.1負(fù)荷計(jì)算差不多公式 62.1.1外墻、屋頂?shù)乃沧儌鳠岬睦湄?fù)荷 62.1.2內(nèi)圍護(hù)冷負(fù)荷 72.1.3外窗玻璃瞬變傳導(dǎo)得熱形成的的冷負(fù)荷 72.1.4玻璃窗日射得熱形成的冷負(fù)荷 82.1.5設(shè)備散熱冷負(fù)荷 82.1.6燈光照明散熱形成的冷負(fù)荷 82.1.7人體散熱形成的冷負(fù)荷 9第三章空調(diào)方案確定和設(shè)備選型 17第四章夏季空調(diào)過(guò)程設(shè)計(jì) 204.1送風(fēng)狀態(tài)確定 204.2匯總于下表 214.3送風(fēng)量計(jì)算 224.4新風(fēng)量計(jì)算 224.5總排風(fēng)量的計(jì)算 23第六章房間的氣流組織計(jì)算 266.1氣流組織計(jì)算 26第七章布置風(fēng)管、進(jìn)行風(fēng)管水力計(jì)算,水管水力計(jì)算 287.1風(fēng)管的布置 287.2風(fēng)道的設(shè)計(jì)及水力計(jì)算 29參考文獻(xiàn) 32

摘要本設(shè)計(jì)是濟(jì)南市某街道辦公樓空調(diào)工程設(shè)計(jì),依照此樓功能要求,本建筑需要夏季提供冷負(fù)荷。以長(zhǎng)遠(yuǎn)利益為動(dòng)身點(diǎn),力求達(dá)到技術(shù)可靠,經(jīng)濟(jì)合理,節(jié)能環(huán)保、治理方便,功能調(diào)整的靈活性及使用安全可靠。在比較各種方案的可行性及水系統(tǒng)形式后,此工程設(shè)計(jì)采納風(fēng)機(jī)盤(pán)管加獨(dú)立新風(fēng)系統(tǒng);水系統(tǒng)采納一次泵、雙管制系統(tǒng):為滿足整棟大樓需求,同時(shí)為了在運(yùn)行過(guò)程中的節(jié)能,本設(shè)計(jì)冷熱源采納風(fēng)冷熱泵模塊機(jī)組。依照夏季空調(diào)計(jì)算負(fù)荷依次選擇機(jī)組、末端設(shè)備、新風(fēng)機(jī)組、風(fēng)口,最后還要對(duì)空調(diào)系統(tǒng)的設(shè)備和管路采取消聲、防振和保溫等措施。

第一章設(shè)計(jì)資料1.1設(shè)計(jì)題目濟(jì)南市某街道空調(diào)工程設(shè)計(jì) 1.2設(shè)計(jì)差不多參數(shù)1.2.1室外參數(shù)緯度:28.13度經(jīng)度:112.55度海拔高度:68mAS冬季大氣壓力:1018.3pa夏季大氣壓力:995.6pa冬季通風(fēng)室外計(jì)算干球溫度:3.5℃冬季空調(diào)室外計(jì)算干球溫度:-0.8℃夏季通風(fēng)室外計(jì)算干球溫度:32.2℃夏季空調(diào)室外計(jì)算干球溫度:36.5℃夏季空調(diào)室外計(jì)算濕球溫度:29℃夏季空調(diào)室外計(jì)算日平均溫度:32.5℃冬季空調(diào)室外相對(duì)濕度:90%夏季通風(fēng)室外相對(duì)濕度:63%冬季室外平均風(fēng)速:2.4m/s夏季室外平均風(fēng)速:2.4m/s1.2.2土建參數(shù)1外墻參數(shù):通過(guò)查資料,選擇23號(hào)外墻,其差不多構(gòu)造為:1、水泥砂漿抹灰加淺色噴漿;2、磚墻;3、保溫層為硬質(zhì)聚氨酯板;=50mm,K=0.51W/(),衰減系數(shù)B=0.19,延遲時(shí)刻為8h.2內(nèi)墻參數(shù):選擇10號(hào)墻磚,=140mm,K=1.78W/(),衰減系數(shù)為0.29,延遲時(shí)刻為7h.3屋面參數(shù):選擇10號(hào)保溫層面,差不多結(jié)構(gòu),1、混凝土板;2、架空層;3、防水層;4、找平層;5、找坡層;6、加氣混凝土7、保溫層8、鋼筋混凝土屋面板。其中保溫層為擠塑聚苯板,=40mm,K=0.59W/(),衰減系數(shù)為0.22,延遲時(shí)刻為8h。4樓板參數(shù):選擇3號(hào)鋼筋混凝土樓板,由面層、鋼筋混凝土樓板、吊頂空間、鋼板網(wǎng)抹灰、濁漆組成。5外窗參數(shù):選擇6mm厚度單層鋁合金框架玻璃窗傳熱系數(shù)K=3.3W/(),內(nèi)遮陽(yáng)系數(shù)Cn=0.5,地點(diǎn)修正系數(shù):南面北面,東面和西面,,遮擋系數(shù)。第二章負(fù)荷計(jì)算2.1負(fù)荷計(jì)算差不多公式內(nèi)墻、內(nèi)窗、地板等其鄰室為空調(diào)房間時(shí),其室溫基數(shù)差小于3℃時(shí),不計(jì)算冷負(fù)荷。因此負(fù)荷計(jì)算時(shí),室溫基數(shù)差小于3℃的都不用考慮樓板和內(nèi)墻的傳熱。2.1.1外墻、屋頂?shù)乃沧儌鳠岬睦湄?fù)荷依照《有用供熱空調(diào)設(shè)計(jì)手冊(cè)》得,在日射和室外氣溫綜合作用下,外墻和屋面瞬變傳熱引起的逐時(shí)冷負(fù)荷可按式2.1計(jì)算。(公式STYLEREF1\s2.SEQ(公式\*ARABIC\s11)式中:計(jì)算時(shí)刻,h;圍護(hù)結(jié)構(gòu)表面受到周期為24h諧性溫度波作用,溫度波傳到內(nèi)表面的時(shí)刻延遲,h;溫度波的作用時(shí)刻,即溫度作用于圍護(hù)結(jié)構(gòu)外表面的時(shí)刻,h;——圍護(hù)結(jié)構(gòu)傳熱系數(shù),;圍護(hù)結(jié)構(gòu)計(jì)算面積,m2;—作用時(shí)刻下,圍護(hù)結(jié)構(gòu)的冷負(fù)荷計(jì)算溫度,簡(jiǎn)稱冷負(fù)荷溫度,℃;—負(fù)荷溫度地點(diǎn)修正值,℃,+1;—室內(nèi)設(shè)計(jì)溫度,℃。2.1.2內(nèi)圍護(hù)冷負(fù)荷由于相鄰空間通風(fēng)良好,臨室發(fā)熱量專門(mén)少,僅由于溫差形成內(nèi)圍護(hù)冷負(fù)荷,屬于穩(wěn)定傳熱,依照參考資料[1]可得計(jì)算公式2.2。(公式STYLEREF1\s2.SEQ(公式\*ARABIC\s12)式中:——圍護(hù)結(jié)構(gòu)傳熱系數(shù),;圍護(hù)結(jié)構(gòu)計(jì)算面積,m2;——夏季空調(diào)室外計(jì)算日平均溫度,℃;——室內(nèi)設(shè)計(jì)溫度,℃。2.1.3外窗玻璃瞬變傳導(dǎo)得熱形成的的冷負(fù)荷在室內(nèi)外溫差的作用下,玻璃窗瞬傳熱形成的冷負(fù)荷可按式2.3計(jì)算。(公式STYLEREF1\s2.SEQ(公式\*ARABIC\s13)式中:——窗玻璃的傳熱系數(shù),;——窗的計(jì)算面積,m2;——計(jì)算時(shí)刻下的冷負(fù)荷溫度,℃;——地點(diǎn)修正系數(shù),℃;——室內(nèi)設(shè)計(jì)溫度,℃;a——窗框修正系數(shù)。2.1.4玻璃窗日射得熱形成的冷負(fù)荷透過(guò)玻璃窗進(jìn)入室內(nèi)的日射得熱形成的逐時(shí)冷負(fù)荷按式2.4計(jì)算。(公式STYLEREF1\s2.SEQ(公式\*ARABIC\s14)式中:——窗的構(gòu)造修正系數(shù);——地點(diǎn)修正系數(shù);——內(nèi)遮陽(yáng)系數(shù);——計(jì)算時(shí)刻下,透過(guò)有內(nèi)遮陽(yáng)設(shè)施窗玻璃太陽(yáng)輻射的冷負(fù)荷強(qiáng)度,。2.1.5設(shè)備散熱冷負(fù)荷(公式STYLEREF1\s2.SEQ(公式\*ARABIC\s15)式中:F——空調(diào)區(qū)面積,m2。qf——電器設(shè)備功率密度,W/m2。2.1.6燈光照明散熱形成的冷負(fù)荷白熾燈散熱形成的冷負(fù)荷按照式2.6計(jì)算。(公式STYLEREF1\s2.SEQ(公式\*ARABIC\s16)式中:同時(shí)使用系數(shù),由于缺少實(shí)測(cè)數(shù)據(jù),取=0.6~0.8;——計(jì)算時(shí)刻,h;——開(kāi)燈時(shí)刻,h;——從開(kāi)燈時(shí)刻算起到計(jì)算時(shí)刻的持續(xù)時(shí)刻,h;——時(shí)刻燈具顯熱散熱的冷負(fù)荷系數(shù);——照明燈具所需功率,缺少數(shù)據(jù)時(shí),可依照空調(diào)使用面積推算功率指標(biāo)W。2.1.7人體散熱形成的冷負(fù)荷人員的冷負(fù)荷包括人員顯熱和潛熱部分,顯熱部分需要進(jìn)行逐時(shí)計(jì)算,而潛熱由于變化范圍較小,按穩(wěn)定傳熱計(jì)算。依照參考資料得:人體顯熱形成的計(jì)算時(shí)刻冷負(fù)荷按照公式2.7計(jì)算公式。(公式STYLEREF1\s2.SEQ(公式\*ARABIC\s17)式中:——不同室和氣勞動(dòng)性質(zhì)時(shí)一名成年男子小時(shí)顯熱散熱量,W;計(jì)算時(shí)刻空調(diào)區(qū)內(nèi)的總?cè)藬?shù);——群集系數(shù);——計(jì)算時(shí)刻,h;——人員進(jìn)入空調(diào)區(qū)的時(shí)刻,h;——從人員進(jìn)入空調(diào)區(qū)的時(shí)刻算起到計(jì)算時(shí)刻的持續(xù)時(shí)刻h;——時(shí)刻人體顯熱散熱的冷負(fù)荷系數(shù)。人體散濕形成的潛熱冷負(fù)荷(W)計(jì)算公式:(公式STYLEREF1\s2.SEQ(公式\*ARABIC\s18)式中:——不同室和氣勞動(dòng)性質(zhì)時(shí)一名成年男子小時(shí)潛熱散熱量,W;計(jì)算時(shí)刻空調(diào)區(qū)內(nèi)的總?cè)藬?shù);——群集系數(shù)。

濟(jì)南市在西安市修正+1101房間負(fù)荷計(jì)算南墻冷負(fù)荷:時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00tc(τ)31.831.831.832.032.332.933.634.234.9Δt+1tc’(τ)32.832.832.833.033.333.934.635.235.9tR26K0.45A10.8Qc(τ)28.0728.0728.0728.9030.1332.6135.5037.9840.87南窗冷負(fù)荷:時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00tc(τ)31.031.732.333.033.433.733.833.633.4tR26K2.4A4.8Qc(τ)57.665.6672.5880.6485.2588.7089.8687.5585.25南外窗日射負(fù)荷時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00CLQ0.300.400.510.530.670.680.650.440.39Ca0.75Aw4.8Cs0.78Ci0.6Djmax243Qc(τ)122.82163.76208.80216.99274.30278.40266.11180.14159.67西外墻冷負(fù)荷時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00tc(τ)34.234.033.833.833.934.134.434.935.7Δt+1tc’(τ)35.235.034.834.834.935.135.435.936.7tR26K0.43A21.6Qc(τ)85.4583.5981.7381.7382.6684.5287.3191.9599.38照明散熱冷負(fù)荷時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00CLQ0.40.720.770.810.830.850.870.890.9n11n20.6N232Qc(τ)55.68100.22107.18112.75115.54118.32121.10123.89125.28室內(nèi)人員散熱冷負(fù)荷時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00CLQ0.460.780.830.860.880.890.910.920.93qs60.5n5ψ0.90125.24212.36225.97234.14239.58242.30247.75250.47253.19ql73.3329.85329.85329.85329.85329.85329.85329.85329.85329.85Qc(τ)455.09542.21555.82563.99569.43572.15577.60580.32583.04101房間各負(fù)荷匯總表時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00南墻28.0728.0728.0728.9030.1332.6135.5037.9840.87西墻85.4583.5981.7381.7382.6684.5287.3191.9599.38外窗57.665.6672.5880.6485.2588.7089.8687.5585.25窗日照122.82163.76208.8216.99274.3278.4266.11180.14159.67人體455.09542.21555.82563.99569.43572.15577.6580.32583.04照明55.68100.22107.18112.75115.54118.32121.1123.89125.28合計(jì)804.71983.511054.1810851157.311174.71177.481101.831093.49102-108房間各負(fù)荷匯總表時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00南墻28.0728.0728.0728.9030.1332.6135.5037.9840.87外窗57.665.6672.5880.6485.2588.7089.8687.5585.25窗日照122.82163.76208.8216.99274.3278.4266.11180.14159.67人體455.09542.21555.82563.99569.43572.15577.6580.32583.04照明55.68100.22107.18112.75115.54118.32121.1123.89125.28合計(jì)719.05899.92972.451003.271082.151090.181056.251105.251093.49109房間各負(fù)荷匯總表時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00南墻28.0728.0728.0728.9030.1332.6135.5037.9840.87東墻85.4583.5981.7381.7382.6684.5287.3191.9599.38外窗65.4865.6672.5880.6485.2588.7089.8687.5585.25窗日照122.82163.76208.8216.99274.3278.4266.11180.14159.67人體455.09542.21555.82563.99569.43572.15577.6580.32583.04照明88.68100.22107.18112.75115.54118.32121.1123.89125.28合計(jì)935.561065.521158.241284.411305.241358.151358.151335.851315.25110-112.114.115房間各負(fù)荷匯總表時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00北墻85.4583.5981.7381.7382.6684.5287.3191.9599.38外窗57.665.6672.5880.6485.2588.7089.8687.5585.25窗日照122.82163.76208.8216.99274.3278.4266.11180.14159.67人體455.09542.21555.82563.99569.43572.15577.6580.32583.04照明55.68100.22107.18112.75115.54118.32121.1123.89125.28合計(jì)776.64955.441026.111056.11127.181142.091141.981063.851052.62113房間各負(fù)荷匯總表時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::00北墻170.9167.18163.46163.46165.32169.04174.62183.9198.76外窗115.2131.32145.16161.28170.5177.4179.72175.1170.5窗日照245.64327.52417.6433.98548.6556.8532.22360.28319.34人體910.181084.421111.641127.981138.861144.31155.21160.641166.08照明111.36200.44214.36225.5231.08236.64242.2247.78250.56合計(jì)1553.281910.882052.222112.22254.362284.182283.962127.72105.24各房間負(fù)荷匯總表房間號(hào)一層房間濕負(fù)荷時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::000.49101804.71983.511054.1810851157.311174.71177.481101.831093.490.49102719.05899.92972.451003.271082.151090.181056.251105.251093.490.49103719.05899.92972.451003.271082.151090.181056.251105.251093.490.49104719.05899.92972.451003.271082.151090.181056.251105.251093.490.49105719.05899.92972.451003.271082.151090.181056.251105.251093.490.49106719.05899.92972.451003.271082.151090.181056.251105.251093.490.49107719.05899.92972.451003.271082.151090.181056.251105.251093.490.49108719.05899.92972.451003.271082.151090.181056.251105.251093.490.49109935.561065.521158.241284.411305.241358.151358.151335.851315.250.49110776.64955.441026.111056.11127.181142.091141.981063.851052.620.49111776.64955.441026.111056.11127.181142.091141.981063.851052.620.49112776.64955.441026.111056.11127.181142.091141.981063.851052.620.491131553.281910.882052.222112.22254.362284.182283.962127.72105.240.98114776.64955.441026.111056.11127.181142.091141.981063.851052.620.49115776.64955.441026.111056.11127.181142.091141.981063.851052.620.49門(mén)廳855.15895.25925.25102.53962.111025.251056.23986.25961.262.95房間號(hào)二層房間濕負(fù)荷時(shí)刻9::0010::0011::0012::0013::0014::0015::0016::0017::000.49201903.51125.521205.511256.111324.211356.581389.531305.581283.580.49202905.521025.541105.651225.561262.521295.451272.521220.41195.240.49203905.521025.541105.651225.561262.521295.451272.521220.41195.240.49204905.521025.541105.651225.561262.521295.451272.521220.41195.240.492051811.042051.082211.32451.122525.042590.92545.042440.82390.480.98206905.521025.541105.651225.561262.521295.451272.521220.41195.240.49207905.521025.541105.651225.561262.521295.451272.521220.41195.240.49208905.521025.541105.651225.561262.521295.451272.521220.41195.240.49209950.251152.411258.251283.121345.251386.251393.251423.561410.520.49210910.251056.281125.651175.561208.251256.251286.251298.251274.250.49211910.251056.281125.651175.561208.251256.251286.251298.251274.250.49212910.251056.281125.651175.561208.251256.251286.251298.251274.250.492131820.52112.562251.32351.122416.52512.52572.52596.52548.50.98樓梯間450.58525.44592.54608.25656.25698.15702.25697.25710.230.49214910.251056.281125.651175.561208.251256.251286.251298.251274.250.49215910.251056.281125.651175.561208.251256.251286.251298.251274.250.49門(mén)廳352.2365.25381.56369.25421.25458.25421.25423.25395.251.96第三章空調(diào)方案確定和設(shè)備選型空調(diào)系統(tǒng)的分類方案確定空調(diào)系統(tǒng)按負(fù)擔(dān)室內(nèi)空調(diào)負(fù)荷所用介質(zhì)分類,可分為全空氣系統(tǒng)、全水系統(tǒng)、空氣-水系統(tǒng)和冷劑式系統(tǒng)。一、全空氣系統(tǒng)是指室內(nèi)空調(diào)負(fù)荷全部由處理過(guò)的空氣負(fù)擔(dān)。系統(tǒng)適用性:1、建筑空間大,易于布置風(fēng)道;2、室內(nèi)溫、濕度、潔凈度操縱要求嚴(yán)格;3、負(fù)荷大或潛熱負(fù)荷大的場(chǎng)合。二、全水系統(tǒng)是指室內(nèi)空調(diào)負(fù)荷全部由水來(lái)負(fù)擔(dān)。系統(tǒng)適用性:1、建筑空間小,不宜于布置風(fēng)道;2、不需通風(fēng)換氣的場(chǎng)所。三、空氣-水系統(tǒng)是指室內(nèi)空調(diào)負(fù)荷由空氣和水共同負(fù)擔(dān)。1、室內(nèi)溫、濕度要求一般的場(chǎng)合;2、層高較低的場(chǎng)合;3、冷負(fù)荷較小、濕負(fù)荷也較小的場(chǎng)所。四、冷劑式系統(tǒng)是指空調(diào)房間負(fù)荷由制冷劑直接承擔(dān)。1、空調(diào)房間布置分散;2、要求靈活操縱空調(diào)使用時(shí)刻;3、無(wú)法集中設(shè)置冷熱源。全空氣一次回風(fēng)系統(tǒng)的空調(diào)機(jī)組送風(fēng)量是恒定的,系統(tǒng)的夏季冷量由室內(nèi)冷負(fù)荷、新風(fēng)負(fù)荷和再熱負(fù)荷組成,關(guān)于送風(fēng)溫差無(wú)嚴(yán)格要求的舒適性空調(diào),如采納大溫差送風(fēng)即露點(diǎn)送風(fēng)的一次回風(fēng)系統(tǒng),可不需要消耗再熱量,因此可節(jié)約能耗。但送風(fēng)溫差過(guò)大,往往會(huì)造成送風(fēng)口解霜現(xiàn)象,為幸免此類現(xiàn)象的發(fā)生,采納一次回風(fēng)空調(diào)系統(tǒng)需利用再熱來(lái)解決送風(fēng)溫差受限制的問(wèn)題,即為了保證必須的送風(fēng)溫差,一次回風(fēng)系統(tǒng)在夏季需要再熱,從而產(chǎn)生冷熱抵消的現(xiàn)象風(fēng)機(jī)盤(pán)管加新風(fēng)系統(tǒng)是空氣-水系統(tǒng)的一種要緊形式,也是我國(guó)民用建筑中采納最普遍的一種空調(diào)方式,它的投資少,使用靈活和節(jié)約建筑空間等優(yōu)點(diǎn)被廣泛應(yīng)用于各類建筑中。該系統(tǒng)具有以下特點(diǎn):本設(shè)計(jì)為培訓(xùn)中心,通過(guò)對(duì)上述空調(diào)系統(tǒng)的分析,本設(shè)計(jì)采納空氣-水系統(tǒng)。新風(fēng)系統(tǒng)的形式采納分樓層水平式,每層設(shè)置新風(fēng)系統(tǒng),采納風(fēng)機(jī)盤(pán)管加新風(fēng)系統(tǒng),新風(fēng)處理方式不一樣,對(duì)室內(nèi)空氣品質(zhì)有專門(mén)大的阻礙。風(fēng)機(jī)盤(pán)管加新風(fēng)系統(tǒng)的空氣處理方式有:(1)新風(fēng)處理到室內(nèi)狀態(tài)的等焓線,不承擔(dān)室內(nèi)負(fù)荷;(2)新風(fēng)處理到低于室內(nèi)空氣的焓值,并低于室內(nèi)空氣的含濕量,承擔(dān)部分室內(nèi)負(fù)荷。那個(gè)地點(diǎn)選用不承擔(dān)室內(nèi)冷負(fù)荷方案,在每層的空調(diào)機(jī)房處設(shè)置一新風(fēng)處理機(jī)組,負(fù)擔(dān)新風(fēng)負(fù)荷,新風(fēng)不與風(fēng)機(jī)盤(pán)管回風(fēng)混合,新風(fēng)口單獨(dú)送風(fēng)。

第四章夏季空調(diào)過(guò)程設(shè)計(jì)4.1送風(fēng)狀態(tài)確定空氣—水系統(tǒng)是由空氣和水共同來(lái)承擔(dān)空調(diào)房間冷、熱負(fù)荷的系統(tǒng),除了向房間內(nèi)送入通過(guò)處理的空氣外,還在房間內(nèi)設(shè)有以水作為介質(zhì)的末端設(shè)備對(duì)室內(nèi)空氣進(jìn)行冷卻或加熱。新風(fēng)將不在承擔(dān)室內(nèi)負(fù)荷,將新風(fēng)處理到室內(nèi)空氣的焓值,而風(fēng)機(jī)盤(pán)管承擔(dān)室內(nèi)人員、設(shè)備冷負(fù)荷和建筑維護(hù)結(jié)構(gòu)冷負(fù)荷。氣——水系統(tǒng)送風(fēng)狀態(tài)的確定可在i-d圖上進(jìn)行,具體步驟如下:1)在i-d圖上找出室內(nèi)狀態(tài)點(diǎn)N,室外狀態(tài)點(diǎn)W。2)依照計(jì)算出來(lái)的室內(nèi)冷負(fù)荷Q和濕負(fù)荷W求出,過(guò)N點(diǎn)作線與=90%相交,即得送風(fēng)點(diǎn)S。3)依照等焓線,由新風(fēng)處理后的機(jī)器露點(diǎn)相對(duì)濕度定出D點(diǎn)。4)依照N、S兩點(diǎn)確定房間總風(fēng)量。5)依照新風(fēng)比確定風(fēng)機(jī)盤(pán)管處理風(fēng)量即終狀態(tài)。其中,人體散濕量Mw=0.278ng×10-6Mw——人體散濕量,kg/s;g——c成年男子小時(shí)散熱量,g/h。4.2匯總于下表熱濕負(fù)荷與熱濕比最大冷負(fù)荷人數(shù)成年男子小時(shí)散濕量濕負(fù)荷熱濕比房間編號(hào)Qci(W)n(人)g(g/h)Mwi(g/s)εi(kJ/kg)1011157.3151090.1369852102至1081105.2551090.13699621091358.1551090111、112、114、1151142.0951090.13697581132868.41101090.27210355門(mén)廳458.2511090.027102352011389.53510902081295.4551090.136112562052590.9101090.272118652091423.5651090211、212、214、2151298.2551090.136116262132596.5101090.272113654.3送風(fēng)量計(jì)算送風(fēng)量的計(jì)算公式為:Ms——送入房間的風(fēng)量,kg/s;Qc(τ)——全熱冷負(fù)荷,KW;hR——室內(nèi)空氣的比焓,kJ/kg;hs——送風(fēng)的比焓,kJ/kg。4.4新風(fēng)量計(jì)算4.3.1人員所需新風(fēng)量的計(jì)算公式為:式中n——每個(gè)房間人數(shù);gw——沒(méi)人所需新風(fēng)量,m3/人·h。4.3.2為維持房間正壓所需的新風(fēng)量計(jì)算公式為:式中N——換氣次數(shù),/h;V——房間體積,m3;新風(fēng)量取兩者中最大值。各房間總風(fēng)量、新風(fēng)量如下表4.5總排風(fēng)量的計(jì)算房間編號(hào)新風(fēng)量排風(fēng)量kg/sm3/skg/sm3/s1010.050.040.040.03102至1080.050.040.040.031090.050.040.040.03110、111、112、114、1150.050.040.040.031130.100.080.070.06門(mén)廳0.010.0080.0070.006一樓總0.8010.6750.5610.4732010.050.040.040.03202至2080.050.040.040.032050.100.080.070.062090.050.040.040.03210、211、212、214、2150.050.040.040.032130.100.080.070.06二樓總0.850.7080.5950.496第五章空調(diào)制冷設(shè)備選型5.1新風(fēng)機(jī)組的選型一層二層采納空氣——水風(fēng)機(jī)盤(pán)管系統(tǒng),對(duì)新風(fēng)機(jī)組進(jìn)行選型。一層承擔(dān)總的新風(fēng)量為1985m3/h,承擔(dān)的新風(fēng)冷量為15.2KW,所查得的型號(hào)為ZKD3-X二層承擔(dān)總的新風(fēng)量為2015m3/h,承擔(dān)的新風(fēng)冷量為15.8KW,所查得的型號(hào)為ZKD3-X5.2風(fēng)機(jī)盤(pán)管的選型關(guān)于該系統(tǒng),風(fēng)機(jī)盤(pán)管的冷負(fù)荷即為室內(nèi)冷負(fù)荷,風(fēng)機(jī)盤(pán)管所承擔(dān)的風(fēng)量為送風(fēng)量-新風(fēng)量。往常室房間為例,該房間的冷負(fù)荷為1583.53W,風(fēng)機(jī)盤(pán)管所承擔(dān)的風(fēng)量為承擔(dān)的風(fēng)量為315m3/h。查得風(fēng)機(jī)盤(pán)管的型號(hào)為FP—34。各房間風(fēng)機(jī)盤(pán)管型號(hào)房間編號(hào)風(fēng)機(jī)盤(pán)管型號(hào)101FP-34WA102至108FP-34WA109FP-34WA110、111、112、114、115FP-34WA113FP-68WA門(mén)廳FP-34WA201FP-51WA202至208FP-34WA209FP-51WA210、211、212、214、215FP-34WA213FP-68WA

第六章房間的氣流組織計(jì)算6.1氣流組織計(jì)算采納散流器平送氣流組織形式,徑向貼附散流器,送出的氣流為貼附于頂棚的射流,回風(fēng)口布置在房間下部。因散流器服務(wù)的長(zhǎng)寬比大于1.25時(shí),采納矩形散流器。散流器中心與側(cè)墻的距離不小于1m。房間尺寸為7.2×4×3.6(長(zhǎng)×寬×高),(以901房間為例)。(1)、按兩個(gè)散流器布置,則散流器所對(duì)應(yīng)的Fn=4×3.6=14.4㎡,水平射程分不為2m及1.8m,平均取=1.9m,垂直射程=3.6-2=1.6m.(2)、設(shè)送風(fēng)溫差=6℃,因此總送風(fēng)量為L(zhǎng)=1743.5×3.6÷(1.2×1.01×6)=863.1m3/h換氣次數(shù):n=863.1÷(7.2×3.6×4)=8.3l/h按照兩個(gè)散流器布置,每個(gè)散流器的送風(fēng)量為=863.1/2=431.55m3/h(3)、散流器出風(fēng)速度選定為3.0m/s,如此:=431.55÷(3.0×3600)=0.04㎡(4)、檢查,依照式5.1得到。(公式STYLEREF1\s5.SEQ(公式\*ARABIC\s11)式中:=1.41;——依照0.1/=0.1=0.95,查圖5-13,按=1.9/1.6=1.188查得=0.49;、——均取1.代入各已知值得:=0.118m/s。(5)、檢查:=0.21℃依照資料推舉的送風(fēng)溫差和換氣次數(shù),計(jì)算結(jié)果講明及均滿足要求。(6)、檢查射流貼附長(zhǎng)度:(其中h0=0.3d0)=3.78因此=0.4×3.78×exp(0.35-0.62ho/)=2.03m>1.9m因此,貼附射流長(zhǎng)度滿足要求。6.2散流器的選擇房間編號(hào)房間面積風(fēng)口尺寸風(fēng)口個(gè)數(shù)Smm×mmn10121.06100*3001102至10821.06100*300110921.06100*4001110至11521.06100*300111342.12100*300220121.06100*4001202至20821.06100*400120542.12100*400220921.06100*4001210至21521.06100*300121342.12100*3002第七章布置風(fēng)管、進(jìn)行風(fēng)管水力計(jì)算,水管水力計(jì)算7.1風(fēng)管的布置(1)送風(fēng)口:該會(huì)議室采納散流器送風(fēng),依照《民用建筑空調(diào)系統(tǒng)建筑手冊(cè)》可查得散流器布置的原則是:布置時(shí)充分考慮建筑結(jié)構(gòu)的特點(diǎn),散流器平送方向不得有障礙物(如柱);一般按對(duì)稱布置或梅花形布置;每個(gè)方行散流器所服務(wù)的區(qū)域最好為正方形或接近正方形;假如散流器服務(wù)區(qū)的長(zhǎng)度比大于1.25時(shí),宜選用矩形散流器;假如采納頂棚回風(fēng),則回風(fēng)口應(yīng)布置在距散流器最遠(yuǎn)處。散流器送風(fēng)氣流分布計(jì)算,要緊選用合適的散流器,使房間內(nèi)風(fēng)速滿足設(shè)計(jì)要求。此外,散流器中心與側(cè)墻的距離不宜小于1m,4m×4m的散流器,間距一般在3.5米。(2)風(fēng)管的布置及附件:風(fēng)管道全部用鍍鋅鋼板制作,厚度及加工方法,按《通風(fēng)與空調(diào)工程施工及驗(yàn)收規(guī)范》(GB50243-97)的規(guī)定確定,主管和支管的斷面尺寸在途中標(biāo)明;設(shè)計(jì)圖中所注風(fēng)管的標(biāo)高,以風(fēng)管底為準(zhǔn);穿越沉降縫或變形縫處的風(fēng)管兩側(cè),以及與通風(fēng)機(jī)進(jìn)、出口相連處,應(yīng)設(shè)置長(zhǎng)度為200~300mm的人造革軟接;軟接的接口應(yīng)牢固、嚴(yán)密。在軟接處禁止變徑;風(fēng)管上的可拆卸接口,不得設(shè)置在墻體或樓板內(nèi);所有水平或垂直的風(fēng)管,必須設(shè)置必要的支、吊或托架,其構(gòu)造形式由安裝單位在保證牢固、可靠的原則下依照現(xiàn)場(chǎng)情況選定,詳見(jiàn)國(guó)標(biāo)T616;風(fēng)管支、吊或托架應(yīng)設(shè)置于保溫層的外部,并在支吊托架與風(fēng)管間鑲以墊木,同時(shí),應(yīng)幸免在法蘭、測(cè)量孔、調(diào)節(jié)閥等零部件處設(shè)置支吊托架;安裝調(diào)節(jié)閥、蝶閥等調(diào)節(jié)配件時(shí),必須注意將操作手柄配置在便于操作的部位;安裝防火閥和排煙閥時(shí),應(yīng)先對(duì)其外觀質(zhì)量和動(dòng)作的靈活性與可靠性進(jìn)行檢驗(yàn),確認(rèn)合格后再行安裝;防火閥的安裝位置必須與設(shè)計(jì)相符,氣流方向務(wù)必與閥體上標(biāo)志的箭頭相一致,嚴(yán)禁反向;防火閥必須單獨(dú)配置支吊架;每個(gè)風(fēng)支管都接防火調(diào)節(jié)閥。7.2風(fēng)道的設(shè)計(jì)及水力計(jì)算風(fēng)管水力計(jì)算方法有假定流速法、壓損平均法和靜壓復(fù)得法等幾種,那個(gè)地點(diǎn)采納假定流速法,假定流速法的特點(diǎn)是先按技術(shù)經(jīng)濟(jì)要求選定風(fēng)管的流速,再依照風(fēng)管的風(fēng)量確定風(fēng)管的斷面尺寸和阻力。(1)繪制空調(diào)系統(tǒng)軸測(cè)圖,并對(duì)管段風(fēng)道進(jìn)行編號(hào),標(biāo)準(zhǔn)長(zhǎng)度和風(fēng)量(管道長(zhǎng)度一般按兩個(gè)管件的中心線長(zhǎng)度計(jì)算,不扣除管件本身的長(zhǎng)度)。(2)確定風(fēng)道內(nèi)的合理流速,在輸送空氣量一定的情況,增大流速但是風(fēng)管斷面積減小,制作風(fēng)管所消耗的材料,建筑費(fèi)用等較低,但同時(shí)也會(huì)增加空氣流經(jīng)風(fēng)管的流淌阻力和氣流噪聲,增大空調(diào)系統(tǒng)的運(yùn)行費(fèi)用;減小風(fēng)速則可降低輸送空氣的動(dòng)力損耗,節(jié)約空調(diào)系統(tǒng)的運(yùn)行費(fèi)用,降低氣流噪聲,但卻增加風(fēng)管制作消耗的材料及建設(shè)費(fèi)用。因此必須依照風(fēng)管系統(tǒng)的建設(shè)費(fèi)用、運(yùn)行費(fèi)用和氣流噪聲等因素進(jìn)行技術(shù)經(jīng)濟(jì)比較(3)依照各風(fēng)道的風(fēng)量和選擇的流速確定各管段的斷面尺寸,計(jì)算沿程阻力和局部阻力。注意阻力計(jì)算應(yīng)該選擇最不利環(huán)路(即阻力最大的環(huán)路)進(jìn)行。阻力計(jì)算可按以下步驟計(jì)算:①風(fēng)管沿程壓力損失,可按下式計(jì)算:通過(guò)圓形風(fēng)管的風(fēng)量(m3/h),

溫馨提示

  • 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。

評(píng)論

0/150

提交評(píng)論