LIGHTINGSYSTEM

照明系統(tǒng)1LIGHTINGSYSTEM

照明系統(tǒng)1LIGHTINGSYSTEM1.Lightingsystemprepare;2.Luxcalculation;3.Lightingsystemarrangementdrawing;4.Lightingsystemsinglelinediagram.LIGHTINGSYSTEM1.Lightingsyst2LIGHTINGSYSTEM1.LightingSystemPrepareReferencefordesign:-Constructionspecification;-Generalarrangement(GA)drawing;-Hazardousareadivisiondrawing;-Firezonedivisiondrawing;-Escaperoutearrangementdrawing;LIGHTINGSYSTEM1.LightingSys3LIGHTINGSYSTEM2.Luxcalculation;Presenttwoofsolutions-Calculationwithformula;-Calculationwithvendorsoftware。LIGHTINGSYSTEM2.Luxcalculat4LIGHTINGSYSTEM-CalculationwithformulaNUfF=EADN:LightingfixtureQ’tyU:Utilizationfactor

利用系數(shù)

F:Lumen

流明E:Lux(averageintensityofilluminationrequired)

勒克斯(平均照度)A:Roomarea

房間面積

D:Depreciationfactor=1/M(Maintenancefactor)折舊率=1/M(維護(hù)系數(shù))LIGHTINGSYSTEM-Calculationw5LIGHTINGSYSTEM

U:Utilizationfactor

利用系數(shù)RoomIndex=AxB/((A+B)xh),或

=S/((P/2)xh)A:Width;B:Depth;

S:Area;P:Perimeter;h:

Roomheight

-

0.85M(fromfloor)-Distancefromlightstoceiling.RoomIndex

Uf0-1.490.351.5-1.990.402-2.490.452.5andabove0.50LIGHTINGSYSTEMU:Utilizatio6LIGHTINGSYSTEMF:Lumen

流明Fluorescent

40w–3000lmIncandescent

200w–2500lmLIGHTINGSYSTEMF:Lumen流明7LIGHTINGSYSTEM

D:Depreciationfactor(1/M)折舊率Fluorescent

Accomm.&onmaindeck

1.3

Engineroom

1.5

Gallery

1.7IncandescentAccomm.&onmaindeck

1.2

Engineroom

1.3

Gallery

1.5LIGHTINGSYSTEMD:Depreciati8LIGHTINGSYSTEMEx)Accomm.room:5x6M,E:200lux,U=0.45,D=1.340w=3000lm

N=?

NUfF=EADNx0.45x3000=200x5x6x1.3N=5.7

Answer=40wx2:3setLIGHTINGSYSTEMEx)Accomm.roo9LIGHTINGSYSTEMGuidanceforthedesignandfunctional

requirementsofthelightingsystemIEC

-Generallightingsystem–suppliedfromthemainsourceof

electricalpower.

Verificationofthelightinglevelsshallbemadebymeasurementsonemeterabovefloorlevelingeneral

areasandatactualworkplaceswhereappropriatelevelsarerequired.

Thenumberofmeasuringpointsrequiredformeasuringinagivenareaisbasedontheareaindexandmustbebasedonanevengridlayoutforthewholearea.

(SeeAreaindexcalculationbelow.)

Emergencylightingsystem–suppliedfromtheemergencysourceofelectricalpower;theemergencylightinglevelshallasaminimumbe30%ofthegenerallightingrequirement.

Theemergencylightingsystemshallbeswitchedonautomaticallyintheeventoffailureofthemainsourceofelectricalpower.Distributionboardsforemergencylightingshallbeequippedforremotealarmingoftrippedcircuittoamannedarea.Escapelightingsystem–suppliedfromthebatterybackupsourceofelectricalpowersystem.Distributionboardsforescapelightingshallbeequippedforremotealarmingoftrippedcircuitinamannedlocation.HazardousareasasperIEC-61892-7andthephilosophyforisolationsourcesincaseofemergenciesshallbecompliedwith.LIGHTINGSYSTEMGuidanceforth10LIGHTINGSYSTEMNORSOKNormallighting:Coveringapproximately70%ofthelightingrequirements.Thenormallightingshallbefedfromthemaindistributionsystem.Forthegenerallevelofilluminanceat1mofelevation,thearearequirementsaccordingtoAnnextableapply.TheilluminancelevelsshallcomplywithNORSOKstandardS-002(asbelow).Emergencylighting:Coveringapproximately30%oftheplatformlightingrequirements.Innormaloperationtheemergencystandbylightingshallformpartofthenormallightingsystem.

TheilluminancelevelscomplywiththerelevantpartsofEN1838.Distributionboardsforemergencylightingshallbeequippedforcommonremotealarmingoftrippedcircuit.Emergencyescapelighting:Apartoftheemergencyluminaries,shallbesuppliedfromabatterysource,andsitedaccordingtoEN1838.Otheremergencyluminariese.g.floodlights,shallbesuppliedfromaUPSsystem.Portableemergencylighting:

Thebatterychargerforbatteryoperatedhandlampsshallbefedfromtheemergencydistributionsystem.Localdistributionboardsshallbeprovidedforpowerdistributiontothelightingsystemwithineachfunctionalarea.Thedistributionboardsshalltotheextentpossiblebelocatedinnon-hazardousdryareas.LIGHTINGSYSTEMNORSOK11LIGHTINGSYSTEMDescriptionIECDescriptionNORSOK

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)GeneralOutdoorArea5020100Externalwalkwaysandaccessways100--GeneralIndoorAreas,Corridors,accommodationect.10040200CorridorinLQs100--Corridorinworkareas100--Laydownarea200--Musterarea200--CoffeebarinLQ,televisionroometc.150--Gymnasiummin:300--Cabins150--Toilet/Changingroommin:200--CoffeebaroutsideLQ150--Stairways15060300Stairs,walkwaysandaccesswaysinenclosedworkarea150--Processareas-Occasionallymanned15060300Unmannedmachineryroom200--Batteryroom200--Stores-Largeparts200--Stores-smallparts300--LIGHTINGSYSTEMDescriptionIECD12DescriptionIECDescriptionNORSOK

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)Processareas-frequentlymanned300150450Generalprocessandutilityarea200--HVACroom200--Localinstrumentroom400--Mudroom,mixingarea200--Mudroom,teststation300--Mudlab300--Monkeyboard200--Piperackarea200--Mud/welllogging500--Shaleshaker300--Blowoutpreventerandwellhead150--Cranecabin400--Driller'scabinAdj:400--Operatorcabinindrillingunit400--Drillfloor300150450Drillfloor350--Controlrooms-Laboratories500250750CentralcontrolroomAdj:500--Localcontrolroom400--Laboratory500--Enginerooms-Pumprooms20080400Maingeneratorroom200--Firepumproom200--Auxiliaryenginerooms20080400Emergencygeneratorroom200--LIGHTINGSYSTEMDescriptionIECDescriptionNORSO13DescriptionIECDescriptionNORSOK

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)

AveragelluminanceE(lux)EminE(lux)EmaxE(lux)Workshops300120600Inst/El.Workshop500--Mechanicalworkshop/welding500--Workshopoffice500--Paintshop500--Sandblastingroom300--Switchboardrooms300150450Switchboardandtransformerroom200--Offices500250750Office/MeetingroomAdj:500--Laundry,galleyandmessarea300120600Laundry-machineryarea300--Laundry-workarea300--Galley500--Servingarea400--Diningroom300--Dishwashingmin:300--Hospital300120360Hospital/wardmin:500--Emergencyhospital(ifrequired)300120360Hospitalspotlight10005001500Radiorooms500250750Radioroom500--LIGHTINGSYSTEMDescriptionIECDescriptionNORSO14LIGHTINGSYSTEMAreasindexCalculation(IEC)IEC-61892-2Thenumberofmeasuringpointsrequiredformeasuringinagivenareaisbasedontheareaindexandmustbebasedonanevengridlayoutforthewholearea.AreaindexNumberofpointsBelow141andupto292andupto3163andabove25Theareaindexisgivenbytheformula:K=(a*b)/h(a+b)

WhereKistheareaindex,aandbarethesidesoftheroom/areaandhistheheightoftheluminariesabovetheworkplane.Anylightmeasurementmustbeconsideredinadditiontoanybackgroundlightattheplaceofmeasurement.Note:Theinitialilluminationlevelsshouldallowforlampdeteriorationandaccumulation.LIGHTINGSYSTEMAreasindexCal15LIGHTINGSYSTEMNORSOKIllumination-Forthegenerallevelofilluminanceat1mofelevation,thearearequirementsaccordingtoAnnextableapply.Theuniformityoftheillminanceshallbeequalto,orbetterthan,Emin/Emean=0.5inprocess,utilityanddril-lingareas.TheuniformityoftheilluminanceforindividualworkareasshallbeequaltoorbetterthanEmin/Emean=0.7.Forlightingcalculations,amaintenancefactorreflectingtheenvironmentandtimebetweenmaintenanceintervalsshallbeestablishedandapplied.Maintenancefactor0.7isrecomme-nded.Lightingshallbespecifiedforeachworkplacethatrequiresatleastdailyaccessoriscriticalfromasafetypointofview.TheguidelinesinEN12464-1shallbeappliedinthespecificationoftasklighting.LIGHTINGSYSTEMNORSOK16LIGHTINGSYSTEMThelightingshall,asaminimum,beincludedforworkplacesthatrequiredailyaccessordetailedreadingofinformation,criticalfromasafetypointofview.Thisincludesgauges,indicators,areasthatneedtobecheckedforleakageandareasthatfrequentlyneedmaintenance.Toavoidshadows,illuminationplanningshalltakethelocationoffixtures,racksandmechanicalequipmentintoconsideration.Thedifferenceinilluminationlevelbetweenadjacentareasshouldnotexceed5:1.Inenclosedworkareas,thedifferenceshallneverbemorethan40:1withinthetotalfieldofvision.Provisionshallmaketoavoiddirectglarefromsunshine,fromartificiallightsourcesandfromreflectingsurfaces.Glareinvisualdisplayunitsfromreflectingsurfaces,lampsandwindowsshallbeavoided.Inthedesignofthelighting,thelevelofilluminationandlocationoflampsshallmakeiteasytoseeobstructions,stepsincorridors,walkwaysetc.LIGHTINGSYSTEMThelightingsh17Differentlevelsofilluminancerequiredifferentlightcolorsifthelightingistobecomfortable.Warmcolorshouldbeusedincabinandrecreationareaswherethelightinglevelsarebelow500lux.Highcolortemperature,whiterlight,shouldbeusedinareaswithhighlightlevels.Inareasmonitoredbyclosedcircuittelevision,theilluminanceshallbesufficienttoproducequalityvideopictures.-Theneedforadjustableworkstationlightingshallbeprovidesasneededforfixedworkplaces.LIGHTINGSYSTEMDifferentlevelsofilluminan18EmergencyLightingSystemIEC-61892-2EmergencylightingshallnotbebelowtheescapelightinglevelrequirementaspertableBelow.Thelocationofthelightingfixtureshallbebasedontheneedforlightintheemergencyoperationsituation.Theemergencylightingsystemshallbeswitchedonautomaticallyintheeventoffailureofthemainsourceofelectricalpower.Theemergencylightingsystemshall:ensureilluminationforsafeoperationofemergencysystemsincludingmanualoperationarea;illuminateallaccommodationspaces,controlcenter,worklocations,escaperoutes;helicopterdeckandotherpossibleevacuationlocationssuchaslifeboatstations;illuminatetheseawherelifeboatandliferaftsaretobelaunched;illuminatetheidentificationsystemoftheunit;illuminateallspaceswherelossoflightingpresentsadangertopersonal;illuminationsystemforcontrolstationsthatshallbeoperativeunderemergencyconditions.Hospitalsandemergencyhospitals,ifany,shallbefullyoperationalatalltimes.LIGHTINGSYSTEMEmergencyLightingSystemLIGHT19EscapelightingsystemIEC-61892-2Theescapelightingsystemshall,asaminimum,providealightingleveltomeetilluminationlevelgivenintablebelow.Theescapelightingsystemshallbeswitchedonautomaticallyintheeventoffailureofthemainandemergencypowersupply.Thelocationofescapelightfixtureshallbebasedontheneedforlightintheescapesituation.Theescapelightingsystemsshall:haveapowersupplywithminimum30minutesbackuptimesuppliedbybatterieseitherintegratedorcentralizedandhaveasupplyfromaemergencygenerator;NOTEthebackupshouldtakeaccountofthewayinwhichpersonalwillmusterandevacuateaunit,andhowmuchanevacuationistobetakingout;forhelicopterandtheirmobilizationtime.illuminateallaccommodationspaces,controlcenter,worklocations,escaperoutes;helicopterdeckandotherpossibleevacuationlocationssuchaslifeboatstation;illuminatetheseawherelifeboatandliferaftsaretobelaunched;illuminateallspaceswherelossoflightingpresentsadangertopersonal;illuminatealllocationswhereoperationofsafetyequipmentcanbenecessarytobringtheinstallationofasafestage.LIGHTINGSYSTEMEscapelightingsystemLIGHTING20LIGHTINGSYSTEMAREAAverage–illuminanceE(lux)EminGeneralOutdoorArearoutes51GeneralIndoorescaperoutes,Corridors,accommodationect.51Stairwaysescaperoutes51Processareas-Occasionallymanned51Processareas-frequentlymanned101Drillfloor203Controlrooms250125Enginerooms-Pumprooms101Workshops101Switchboardrooms102Offices101Laundry,galleyandmessarea51Hospital300120Hospitalspotlight1000500Emergencyhospital(ifrequired)300120Radiorooms250125Loadingstations-musterstation203Overside(sealevel)152Lifeboat-Liferaftstation203Sealevellaunchingareas152LIGHTINGSYSTEMAREAAverage–i211WAY–2POLE

2250/1550/15:80%LIGHTINGSYSTEM1WAY–2POLE2250/1550/15:22LIGHTINGSYSTEM23J/BinunittoiletD/B2WAY–2POLE

LIGHTINGSYSTEM23J/Binunitt23TypicalWiringDiagram典型接線TypicalWiringDiagram典型接線24TypicalWiringDiagram典型接線TypicalWiringDiagram典型接線25TypicalWiringDiagram典型接線TypicalWiringDiagram典型接線26NAVIGATIONLIGHTNavigationLightingDefinition:Mastheadlight-meansawhitelightplacedovertheforeandaftcenterlineofthevesselshowinganunbrokenlightoveranarcofthehorizonof225degreesandsofixedastoshowthelightfromrightaheadto22.5degreesabaftthebeamoneithersideofthevessel.Sidelights-meansagreenlightonthestarboardsideandaredlightontheportsideeachshowinganunbrokenlightoveranarcofthehorizonof112.5degreesandsofixedastoshowthelightfromrightaheadto22.5degreesabaftthebeamonitsrespectiveside.Inavesseloflessthan20metersinlengththesidelightsmaybecombinedinonelanterncarriedontheforeandaftcenterlineofthevessel.Sternlight-meansawhitelightplacedasnearlyaspracticableatthesternshowinganunbrokenlightoveranarcofthehorizonof135degreesandsofixedastoshowthelight67.5degreesfromrightaftoneachsideofthevessel.Towinglight-meansayellowlighthavingthesamecharacteristicsasthe“sternlight”definedinparagraph(c)ofthisRule.All-roundlight-meansalightshowinganunbrokenlightoveranarcofthehorizonof360degrees.Flashinglight-meansalightflashingatregularintervalsatafrequencyof120flashesormoreperminute.NAVIGATIONLIGHTNavigationLi27NAVIGATIONLIGHTVisibilityofLightsThelightsprescribedintheseRulesshallhaveanintensityasspecifiedinSection8ofAnnexItotheseRegulationssoastobevisibleatthefollowingminimumranges:(a)Invesselsof50metersormoreinlength:—amastheadlight,6miles;—asidelight,3miles;—asternlight,3miles;—atowinglight,3miles;—awhite,red,greenoryellowall-roundlight,3miles.(b)Invesselsof12metersormoreinlengthbutlessthan50metersinlength:—amastheadlight,5miles;exceptthatwherethelengthofthevesselislessthan20meters,3miles;—asidelight,2miles;—asternlight,2miles;—atowinglight,2miles;—awhite,red,greenoryellowall-roundlight,2miles.(c)Invesselsoflessthan12metersinlength:—amastheadlight,2miles;—asidelight,1mile;—asternlight,2miles;—atowinglight,2miles;—awhite,red,greenoryellowall-roundlight,2miles.(d)Ininconspicuous,partlysubmergedvesselsorobjectsbeingtowed:—awhiteall-roundlight,3miles.NAVIGATIONLIGHTVisibilityof28NAVIGATIONLIGHT29112.5degree112.5degree225degree135degree225degreePORT:REDSTBD:GREEN£

Power-drivenvesselunderwayshallexhibit:(i)amastheadlightforward;(ii)asecondmastheadlightabaftofandhigherthantheforwardone;exceptthatavesseloflessthan50metersinlengthshallnotbeobligedtoexhibitsuchlightbutmaydoso;(iii)sidelights;(iv)asternlight.Note:NavigationlightingdetailrequirementcanbefoundinCONVENTIONONTHEINTERNATIONALREGULATIONSFORPREVENTINGCOLLISIONSATSEA,1972.NAVIGATIONLIGHT29112.5degree2930蘇伊士運(yùn)河燈按蘇伊士運(yùn)河當(dāng)局規(guī)定,船舶在夜間通過蘇伊士運(yùn)河時(shí)必須安裝3種燈具:-在尾燈上方設(shè)置一盞顯示不間斷燈光的專用紅色尾燈;-在左右橋舷各安置一盞橋舷投光燈;在船首中心線位置安裝專用的蘇伊士運(yùn)河探照燈。其中,探照燈必須滿足下列7項(xiàng)要求:

a.探照燈的反射器由兩半組合而成,裝在各自的轉(zhuǎn)軸上,轉(zhuǎn)動(dòng)其角度,可使單一光束分成各與正前方水平夾角至少為5°的兩束光。單光束在離燈1800m時(shí)應(yīng)有1lx的照度(大氣透射比為0.85),兩光束之間的暗區(qū)可在0°~10°范圍內(nèi)平滑變化。b.燈內(nèi)必須裝有兩個(gè)燈泡,如果一個(gè)發(fā)生故障,可直接切換另一個(gè)并自動(dòng)接通電源。c.燈體為水密型(能承受0.0245MPa的壓力)和氣密型(電氣設(shè)備應(yīng)能在危險(xiǎn)區(qū)域內(nèi)使用),并用軟管與裝有安全閥的通氣管相聯(lián),將燈體內(nèi)的熱量排至安全區(qū)。d.燈的功率按船舶的蘇伊士運(yùn)河總噸位選用,不超過3萬總噸位的船舶為2000W,超過3萬總噸位的為3000W。燈的發(fā)光強(qiáng)度應(yīng)不低于3×106cd。e.燈體和支架由耐腐蝕材料制造,燈具能在水平和垂直兩個(gè)方向上轉(zhuǎn)動(dòng)。f.探照燈前玻璃為鋼化玻璃。g.反射鏡用優(yōu)質(zhì)鏡面玻璃或高純錳鋼拋光后制作。

SUEZCANALSIGNALLIGHT30蘇伊士運(yùn)河燈SUEZCANALSIGNALLIG30SUEZCANALSIGNALLIGHT31RWRWRWRGRWGRWSuezCanalSignalLightPORTSTBD10feet3feetSUEZCANALSIGNALLIGHT31RWRWR31LIGHTINGSYSTEM

照明系統(tǒng)32LIGHTINGSYSTEM

照明系統(tǒng)1LIGHTINGSYSTEM1.Lightingsystemprepare;2.Luxcalculation;3.Lightingsystemarrangementdrawing;4.Lightingsystemsinglelinediagram.LIGHTINGSYSTEM1.Lightingsyst33LIGHTINGSYSTEM1.LightingSystemPrepareReferencefordesign:-Constructionspecification;-Generalarrangement(GA)drawing;-Hazardousareadivisiondrawing;-Firezonedivisiondrawing;-Escaperoutearrangementdrawing;LIGHTINGSYSTEM1.LightingSys34LIGHTINGSYSTEM2.Luxcalculation;Presenttwoofsolutions-Calculationwithformula;-Calculationwithvendorsoftware。LIGHTINGSYSTEM2.Luxcalculat35LIGHTINGSYSTEM-CalculationwithformulaNUfF=EADN:LightingfixtureQ’tyU:Utilizationfactor

利用系數(shù)

F:Lumen

流明E:Lux(averageintensityofilluminationrequired)

勒克斯(平均照度)A:Roomarea

房間面積

D:Depreciationfactor=1/M(Maintenancefactor)折舊率=1/M(維護(hù)系數(shù))LIGHTINGSYSTEM-Calculationw36LIGHTINGSYSTEM

U:Utilizationfactor

利用系數(shù)RoomIndex=AxB/((A+B)xh),或

=S/((P/2)xh)A:Width;B:Depth;

S:Area;P:Perimeter;h:

Roomheight

-

0.85M(fromfloor)-Distancefromlightstoceiling.RoomIndex

Uf0-1.490.351.5-1.990.402-2.490.452.5andabove0.50LIGHTINGSYSTEMU:Utilizatio37LIGHTINGSYSTEMF:Lumen

流明Fluorescent

40w–3000lmIncandescent

200w–2500lmLIGHTINGSYSTEMF:Lumen流明38LIGHTINGSYSTEM

D:Depreciationfactor(1/M)折舊率Fluorescent

Accomm.&onmaindeck

1.3

Engineroom

1.5

Gallery

1.7IncandescentAccomm.&onmaindeck

1.2

Engineroom

1.3

Gallery

1.5LIGHTINGSYSTEMD:Depreciati39LIGHTINGSYSTEMEx)Accomm.room:5x6M,E:200lux,U=0.45,D=1.340w=3000lm

N=?

NUfF=EADNx0.45x3000=200x5x6x1.3N=5.7

Answer=40wx2:3setLIGHTINGSYSTEMEx)Accomm.roo40LIGHTINGSYSTEMGuidanceforthedesignandfunctional

requirementsofthelightingsystemIEC

-Generallightingsystem–suppliedfromthemainsourceof

electricalpower.

Verificationofthelightinglevelsshallbemadebymeasurementsonemeterabovefloorlevelingeneral

areasandatactualworkplaceswhereappropriatelevelsarerequired.

Thenumberofmeasuringpointsrequiredformeasuringinagivenareaisbasedontheareaindexandmustbebasedonanevengridlayoutforthewholearea.

(SeeAreaindexcalculationbelow.)

Emergencylightingsystem–suppliedfromtheemergencysourceofelectricalpower;theemergencylightinglevelshallasaminimumbe30%ofthegenerallightingrequirement.

Theemergencylightingsystemshallbeswitchedonautomaticallyintheeventoffailureofthemainsourceofelectricalpower.Distributionboardsforemergencylightingshallbeequippedforremotealarmingoftrippedcircuittoamannedarea.Escapelightingsystem–suppliedfromthebatterybackupsourceofelectricalpowersystem.Distributionboardsforescapelightingshallbeequippedforremotealarmingoftrippedcircuitinamannedlocation.HazardousareasasperIEC-61892-7andthephilosophyforisolationsourcesincaseofemergenciesshallbecompliedwith.LIGHTINGSYSTEMGuidanceforth41LIGHTINGSYSTEMNORSOKNormallighting:Coveringapproximately70%ofthelightingrequirements.Thenormallightingshallbefedfromthemaindistributionsystem.Forthegenerallevelofilluminanceat1mofelevation,thearearequirementsaccordingtoAnnextableapply.TheilluminancelevelsshallcomplywithNORSOKstandardS-002(asbelow).Emergencylighting:Coveringapproximately30%oftheplatformlightingrequirements.Innormaloperationtheemergencystandbylightingshallformpartofthenormallightingsystem.

TheilluminancelevelscomplywiththerelevantpartsofEN1838.Distributionboardsforemergencylightingshallbeequippedforcommonremotealarmingoftrippedcircuit.Emergencyescapelighting:Apartoftheemergencyluminaries,shallbesuppliedfromabatterysource,andsitedaccordingtoEN1838.Otheremergencyluminariese.g.floodlights,shallbesuppliedfromaUPSsystem.Portableemergencylighting:

Thebatterychargerforbatteryoperatedhandlampsshallbefedfromtheemergencydistributionsystem.Localdistributionboardsshallbeprovidedforpowerdistributiontothelightingsystemwithineachfunctionalarea.Thedistributionboardsshalltotheextentpossiblebelocatedinnon-hazardousdryareas.LIGHTINGSYSTEMNORSOK42LIGHTINGSYSTEMDescriptionIECDescriptionNORSOK

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)GeneralOutdoorArea5020100Externalwalkwaysandaccessways100--GeneralIndoorAreas,Corridors,accommodationect.10040200CorridorinLQs100--Corridorinworkareas100--Laydownarea200--Musterarea200--CoffeebarinLQ,televisionroometc.150--Gymnasiummin:300--Cabins150--Toilet/Changingroommin:200--CoffeebaroutsideLQ150--Stairways15060300Stairs,walkwaysandaccesswaysinenclosedworkarea150--Processareas-Occasionallymanned15060300Unmannedmachineryroom200--Batteryroom200--Stores-Largeparts200--Stores-smallparts300--LIGHTINGSYSTEMDescriptionIECD43DescriptionIECDescriptionNORSOK

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)Processareas-frequentlymanned300150450Generalprocessandutilityarea200--HVACroom200--Localinstrumentroom400--Mudroom,mixingarea200--Mudroom,teststation300--Mudlab300--Monkeyboard200--Piperackarea200--Mud/welllogging500--Shaleshaker300--Blowoutpreventerandwellhead150--Cranecabin400--Driller'scabinAdj:400--Operatorcabinindrillingunit400--Drillfloor300150450Drillfloor350--Controlrooms-Laboratories500250750CentralcontrolroomAdj:500--Localcontrolroom400--Laboratory500--Enginerooms-Pumprooms20080400Maingeneratorroom200--Firepumproom200--Auxiliaryenginerooms20080400Emergencygeneratorroom200--LIGHTINGSYSTEMDescriptionIECDescriptionNORSO44DescriptionIECDescriptionNORSOK

Averagellumi-nanceE(lux)EminE(lux)EmaxE(lux)

AveragelluminanceE(lux)EminE(lux)EmaxE(lux)Workshops300120600Inst/El.Workshop500--Mechanicalworkshop/welding500--Workshopoffice500--Paintshop500--Sandblastingroom300--Switchboardrooms300150450Switchboardandtransformerroom200--Offices500250750Office/MeetingroomAdj:500--Laundry,galleyandmessarea300120600Laundry-machineryarea300--Laundry-workarea300--Galley500--Servingarea400--Diningroom300--Dishwashingmin:300--Hospital300120360Hospital/wardmin:500--Emergencyhospital(ifrequired)300120360Hospitalspotlight10005001500Radiorooms500250750Radioroom500--LIGHTINGSYSTEMDescriptionIECDescriptionNORSO45LIGHTINGSYSTEMAreasindexCalculation(IEC)IEC-61892-2Thenumberofmeasuringpointsrequiredformeasuringinagivenareaisbasedontheareaindexandmustbebasedonanevengridlayoutforthewholearea.AreaindexNumberofpointsBelow141andupto292andupto3163andabove25Theareaindexisgivenbytheformula:K=(a*b)/h(a+b)

WhereKistheareaindex,aandbarethesidesoftheroom/areaandhistheheightoftheluminariesabovetheworkplane.Anylightmeasurementmustbeconsideredinadditiontoanybackgroundlightattheplaceofmeasurement.Note:Theinitialilluminationlevelsshouldallowforlampdeteriorationandaccumulation.LIGHTINGSYSTEMAreasindexCal46LIGHTINGSYSTEMNORSOKIllumination-Forthegenerallevelofilluminanceat1mofelevation,thearearequirementsaccordingtoAnnextableapply.Theuniformityoftheillminanceshallbeequalto,orbetterthan,Emin/Emean=0.5inprocess,utilityanddril-lingareas.TheuniformityoftheilluminanceforindividualworkareasshallbeequaltoorbetterthanEmin/Emean=0.7.Forlightingcalculations,amaintenancefactorreflectingtheenvironmentan

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。

評(píng)論

0/150

提交評(píng)論