第132頁共132頁目錄摘要 3aBSTRACT 4TOC\o"1-2"\h\z\u1緒論 51.1設(shè)計(jì)目的 51.2設(shè)計(jì)概述 51.3設(shè)計(jì)任務(wù) 52第一章工程概況 61.1設(shè)計(jì)工程名稱 61.2建筑物的地理位置及功能介紹 61.3設(shè)計(jì)參數(shù)的確定 63第二章空調(diào)負(fù)荷計(jì)算 92.1冷負(fù)荷計(jì)算 92.2新風(fēng)負(fù)荷計(jì)算 142.3負(fù)荷計(jì)算以及部分?jǐn)?shù)據(jù)匯總 154第三章空調(diào)系統(tǒng)方案的確定 253.1確定空調(diào)系統(tǒng)方案的因素 253.2空調(diào)系統(tǒng)方案的比較及選擇 253.3送風(fēng)量與氣流組織 285第四章冷熱源的選擇分析及設(shè)計(jì) 334.1風(fēng)冷與水冷機(jī)組的比較 334.2冷水機(jī)組的確定 344.3機(jī)房的布置 356第五章空調(diào)水系統(tǒng)設(shè)計(jì) 375.1空調(diào)冷凍水設(shè)計(jì) 375.2冷凝水管的設(shè)計(jì) 495.3膨脹水箱的選型 505.4集水器、分水器的設(shè)計(jì) 505.5過濾器的選擇 515.6空調(diào)冷卻水系統(tǒng)設(shè)計(jì) 517第六章空調(diào)風(fēng)系統(tǒng)設(shè)計(jì) 556.1風(fēng)管材料和形狀 556.2送風(fēng)系統(tǒng)的設(shè)計(jì) 558第七章消聲、減震、保溫 587.1消聲器的選擇 587.2減震措施 587.3保溫措施 58致謝 60參考文獻(xiàn) 61摘要此設(shè)計(jì)是重慶市梅林酒店的空調(diào)系統(tǒng)。針對(duì)該酒店大樓的功能要求和特點(diǎn),以及該地氣象條件和空調(diào)要求,參考有關(guān)文獻(xiàn)資料對(duì)該樓的空調(diào)系統(tǒng)進(jìn)行系統(tǒng)規(guī)劃,設(shè)計(jì)計(jì)算和設(shè)備選型.首先計(jì)算各房間的冷負(fù)荷;計(jì)算完冷負(fù)荷以后,接下來是風(fēng)量的計(jì)算,風(fēng)量的計(jì)算包括送風(fēng)量和回風(fēng)量的計(jì)算.風(fēng)量的計(jì)算之初先在I-d圖上畫出空氣的處理過程,然后根據(jù)前面的負(fù)荷計(jì)算結(jié)果進(jìn)行計(jì)算,最后根據(jù)需要的風(fēng)量和冷風(fēng)量選擇空氣處理設(shè)備.在此基礎(chǔ)上,通過對(duì)各種空調(diào)方式的比較,選擇了合理的空調(diào)方式.考慮到本建筑的特點(diǎn),選用集中式風(fēng)機(jī);并對(duì)制冷系統(tǒng)和風(fēng)系統(tǒng)進(jìn)行了設(shè)計(jì)計(jì)算.根據(jù)各種計(jì)算結(jié)果,通過性價(jià)比分析,進(jìn)行了設(shè)備選型,確保了設(shè)備容量,壓強(qiáng),噪聲等方面滿足要求.本中央空調(diào)系統(tǒng)的設(shè)計(jì)力求達(dá)到經(jīng)濟(jì),舒適,方便,實(shí)用,并盡可能滿足節(jié)能要求關(guān)鍵詞:空調(diào)系統(tǒng),空調(diào)方式,節(jié)能

AbstractThisisthedesignofChongqingCity,ahotelbuildingofthedistrictair-conditioningsystems.Againstthebuildingofthefunctionalrequirementsandcharacteristics,andtheweatherconditionsandair-conditioningandasked,withreferencetodocumentationonthebuilding'sairconditioningsystemforsystemplanning,designandcalculationAndselectionofequipment.Roomofthefirstcalculationofthecoolingload;Endcoolingloadcalculations,thefollowingisthecalculationofthewind,theairvolume,includingthecalculationofairsupplyandreturnairofcalculation.WindofthefirstcalculationofthebeginningoftheIdplanstodrawonAirtheprocess,theninfrontoftheloadcalculationresults,accordingtotheneedsoftheendofthewindandcoldair-handlingequipmentofchoice.Onthisbasis,throughvariousformsofairconditioning,air-conditioningchooseareasonablemanner.ToconsiderThecharacteristicsofthisbuilding,thechoiceofacentralizedfan;andrefrigerationsystemsandwindsystemsdesignandcalculation.

Accordingtovariousresults,throughcost-effectiveanalysis,aselectionofequipmenttoensurethattheequipmentcapacity,pressure,noiseandotherareastomeetdemand.Thecentralair-conditioningsystemdesigntoachieveeconomic,comfortable,convenient,practicaland,wherepossible,Meetenergyrequirements.

緒論1.1設(shè)計(jì)目的通過畢業(yè)設(shè)計(jì)消化和鞏固大學(xué)四年學(xué)習(xí)的本專業(yè)全部理論知識(shí)和實(shí)際知識(shí),并將它應(yīng)用到工程實(shí)踐中去解決工程的實(shí)際問題,熟悉有關(guān)的技術(shù)法規(guī)內(nèi)容,培養(yǎng)施工設(shè)計(jì)的思維能力和制圖技巧及對(duì)工程技術(shù)的認(rèn)真態(tài)度。通過此次設(shè)計(jì)要求掌握設(shè)計(jì)原理、程序和內(nèi)容,熟練設(shè)計(jì)計(jì)算方法和步驟。1.2設(shè)計(jì)概述本工程位于重慶市,是一棟多層酒店大樓。建筑面積約為26284.095㎡,空調(diào)面積為約23000㎡。該工程一到四層采用全空氣系統(tǒng)五到十三層采用風(fēng)機(jī)盤管加新風(fēng)空調(diào)系統(tǒng)。采取最常用的混合式系統(tǒng),即處理的空氣來源一部分是新風(fēng),一部分是室內(nèi)的回風(fēng)。夏季送冷風(fēng)和冬季送熱風(fēng)都采用一條風(fēng)道??紤]到一到四層為大空間商業(yè)區(qū)空氣需求量較大并空氣組織較難故采用全空氣系統(tǒng)。五到十三層為客房部空氣調(diào)節(jié)房間較多且各房間要求單獨(dú)調(diào)節(jié),考慮使用率,防止能源浪費(fèi),采用風(fēng)機(jī)盤管系統(tǒng),當(dāng)某客房沒人時(shí),可單獨(dú)關(guān)閉該房間的風(fēng)機(jī)盤管系統(tǒng),新風(fēng)可以通過門窗開啟獲得。1.3設(shè)計(jì)任務(wù)根據(jù)確定的室內(nèi)外氣象條件,土建資料,人體舒適性要求及冷熱源情況設(shè)計(jì)該辦公用建筑物的空調(diào)系統(tǒng)及地下埋管系統(tǒng)。第一章工程概況1.1設(shè)計(jì)工程名稱:重慶市梅林酒店空調(diào)系統(tǒng)設(shè)計(jì)1.2建筑物的地理位置及功能介紹:此建筑物位于重慶市沙坪壩。建筑物的總建筑面積為:26284.095㎡??照{(diào)面積為:約23000㎡。屬一棟酒店兼商業(yè)建筑,包括銀行、餐廳、商務(wù)中心、酒吧、廚房、客房等部分。建筑總高為十五層,一層到四層層高均為4.5m,五到十三層層高均為3.6m,地下層高為4.5m。建筑空調(diào)區(qū)域?yàn)橐粚又潦龑拥纳虡I(yè)區(qū)與客房,除廁所和前室。1.3設(shè)計(jì)參數(shù)的確定空調(diào)設(shè)計(jì)室外設(shè)計(jì)計(jì)算參數(shù):根據(jù)現(xiàn)行的《采暖通風(fēng)與空氣調(diào)節(jié)設(shè)計(jì)規(guī)范》GBJ19-87(2001版)查得:1.3.1.地理位置緯度30°,經(jīng)度106°46′1.3.2.大氣壓力夏――97310Pa,冬――99360Pa1.3.3.室外空氣參數(shù)見表1-1室外空氣參數(shù)表表1-1空氣參數(shù)數(shù)值空氣參數(shù)數(shù)值冬季室外空調(diào)計(jì)算干球溫度3.5℃冬季室外通風(fēng)計(jì)算干球溫度5.2℃夏季室外空調(diào)計(jì)算干球溫度36.3℃夏季室外空調(diào)計(jì)算濕球溫度27.3℃夏季室外通風(fēng)計(jì)算干球溫度32.4℃室外相對(duì)濕度最熱月平均58%全年室外主導(dǎo)風(fēng)向NW室外冬季平均風(fēng)速0.8m/s室外夏季平均風(fēng)速2.1m/s1.3.4.空調(diào)室內(nèi)設(shè)計(jì)計(jì)算參數(shù),見表1-2

空調(diào)室內(nèi)設(shè)計(jì)計(jì)算參數(shù)表1-2季節(jié)夏季冬季項(xiàng)目溫度濕度風(fēng)速溫度濕度風(fēng)速數(shù)值2660%0.251860%.建筑物的基本設(shè)計(jì)參數(shù)墻體結(jié)構(gòu):外墻為內(nèi)外粉刷的磚墻,結(jié)構(gòu)同參考文獻(xiàn)[2],表2–27序號(hào)79的墻體。見下圖2–1,其基本參數(shù)如下:外墻厚,內(nèi)墻厚。窗戶結(jié)構(gòu):窗戶機(jī)構(gòu)均為3mm厚普通玻璃,屋頂為6mm厚玻璃,k=3.01w/m2k,無外遮陽。屋頂結(jié)構(gòu):上人屋面保溫層加氣混凝土、泡沫混凝土部上人屋面保溫層水泥膨脹珍珠巖,如圖1.2。第二章空調(diào)負(fù)荷計(jì)算2.1冷負(fù)荷計(jì)算在空調(diào)工程設(shè)計(jì)中,存在兩種冷負(fù)荷計(jì)算的計(jì)算方法:一為諧波反應(yīng)法(負(fù)荷溫差法),一為冷負(fù)荷系數(shù)法。冷負(fù)荷系數(shù)法是在傳遞函數(shù)的基礎(chǔ)上為便于在工程中進(jìn)行手算而建立起來的一種簡化計(jì)算法。通過冷負(fù)荷溫度與冷負(fù)荷系數(shù)直接從各種擾量值求得各分項(xiàng)逐時(shí)冷負(fù)荷。。諧波反應(yīng)法(負(fù)荷溫差法)計(jì)算的冷負(fù)荷的形成包括兩個(gè)過程:一是由于外擾(室外綜合溫度)形成室內(nèi)得熱量的過程(既內(nèi)擾量)。此過程考慮外擾的周期性以及圍護(hù)結(jié)構(gòu)對(duì)外擾量的衰減和延遲性。二是內(nèi)擾量形成冷負(fù)荷的過程。此過程是將該熱擾量分成對(duì)流和輻射兩個(gè)成分。前者是瞬時(shí)冷負(fù)荷的一部分,后者則要考慮房間總體蓄熱作用后才化為瞬時(shí)冷負(fù)荷。兩部分疊加即得各計(jì)算時(shí)刻的冷負(fù)荷。本設(shè)計(jì)運(yùn)用的是冷負(fù)荷系數(shù)法進(jìn)行冷負(fù)荷計(jì)算。2.1.1負(fù)荷計(jì)算方法及公式(一)、外墻和屋面?zhèn)鳠崂湄?fù)荷計(jì)算公式外墻或屋面?zhèn)鳠嵝纬傻挠?jì)算時(shí)刻冷負(fù)荷Qτ(W),按下式計(jì)算:Qτ=KFΔtτ-ξ

(2.1)式中

F—計(jì)算面積,㎡;

τ—計(jì)算時(shí)刻,點(diǎn)鐘;

τ-ξ—溫度波的作用時(shí)刻,即溫度波作用于外墻或屋面外側(cè)的時(shí)刻,點(diǎn)鐘;

Δtτ-ξ—作用時(shí)刻下,通過外墻或屋面的冷負(fù)荷計(jì)算溫差,簡稱負(fù)荷溫差,℃。注:例如對(duì)于延遲時(shí)間為5小時(shí)的外墻,在確定16點(diǎn)房間的傳熱冷負(fù)荷時(shí),應(yīng)取計(jì)算時(shí)刻τ=16,時(shí)間延遲為ξ=5,作用時(shí)刻為τξ=16-5=11。這是因?yàn)橛?jì)算16點(diǎn)鐘外墻內(nèi)表面由于溫度波動(dòng)形成的房間冷負(fù)荷是5小時(shí)之前作用于外墻外表面溫度波動(dòng)產(chǎn)生的結(jié)果。當(dāng)外墻或屋頂?shù)乃p系數(shù)β<0.2時(shí),可用日平均冷負(fù)荷Qpj代替各計(jì)算時(shí)刻的冷負(fù)荷Qτ:

Qpj=KFΔtpj

(2.2)式中

Δtpj—負(fù)荷溫差的日平均值,℃。、外窗的溫差傳熱冷負(fù)荷

通過外窗溫差傳熱形成的計(jì)算時(shí)刻冷負(fù)荷Qτ按下式計(jì)算:

Qτ=KFΔtτ(2.3)式中

Δtτ—計(jì)算時(shí)刻下的負(fù)荷溫差,℃;

K—傳熱系數(shù)。(三)外窗太陽輻射冷負(fù)荷透過外窗的太陽輻射形成的計(jì)算時(shí)刻冷負(fù)荷Qτ,應(yīng)根據(jù)不同情況分別按下列各式計(jì)算:

1.當(dāng)外窗無任何遮陽設(shè)施時(shí)

Qτ=FCsCaJwτ(2.4)

Jwτ—計(jì)算時(shí)刻下太陽總輻射負(fù)荷強(qiáng)度,W/㎡;

2.當(dāng)外窗只有內(nèi)遮陽設(shè)施時(shí)

Qτ=FCsCaCnJwτ(2.5)式中

Jwτ—計(jì)算時(shí)刻下太陽總輻射負(fù)荷強(qiáng)度,W/㎡;

3.當(dāng)外窗只有外遮陽板時(shí)

Qτ=[F1Jnτ+FJnnτ]CsCa(2.6)注:對(duì)于北緯27度以南地區(qū)的南窗,可不考慮外遮陽板的作用,直接按式(2.1)計(jì)算。4.當(dāng)窗口既有內(nèi)遮陽設(shè)施又有外遮陽板時(shí)

Qτ=[F1Jnτ+FJnnτ]CsCnCa(2.7)式中

Jnτ—計(jì)算時(shí)刻下,標(biāo)準(zhǔn)玻璃窗的直射輻射照度,W/㎡;

Jnnτ—計(jì)算時(shí)刻下,標(biāo)準(zhǔn)玻璃窗的散熱輻射照度,W/㎡;

F1—窗上收太陽直射照射的面積;

F—外窗面積(包括窗框、即窗的墻洞面積)㎡

Ccl、CclN—冷負(fù)荷系數(shù)(CclN為北向冷負(fù)荷系數(shù)),無因次,按緯度取值;

Ca—窗的有效面積系數(shù);

Cs—窗玻璃的遮擋系數(shù);

Cn—窗內(nèi)遮陽設(shè)施的遮陽系數(shù);

注:對(duì)于北緯27度以南地區(qū)的南窗,可不考慮外遮陽板的作用,直接按式(2.2)計(jì)算。(四)、內(nèi)圍護(hù)結(jié)構(gòu)的傳熱冷負(fù)荷

1.當(dāng)鄰室為通風(fēng)良好的非空調(diào)房間時(shí),通過內(nèi)窗的溫差傳熱負(fù)荷,可按式(2.1)計(jì)算。

2.當(dāng)鄰室為通風(fēng)良好的非空調(diào)房間時(shí),通過內(nèi)墻和樓板的溫差傳熱負(fù)荷,可按式(1.1)計(jì)算,或按式(1.2)估算。此時(shí)負(fù)荷溫差Δtτξ及其平均值Δtpj,應(yīng)按"零"朝向的數(shù)據(jù)采用。3.當(dāng)鄰室有一定發(fā)熱量時(shí),通過空調(diào)房間內(nèi)窗、隔墻、樓板或內(nèi)門等內(nèi)圍護(hù)結(jié)構(gòu)的溫差傳熱負(fù)荷,按下式計(jì)算:

Q=KF(twp+Δtls-tn)(2.8)式中

Q—穩(wěn)態(tài)冷負(fù)荷,下同,W;

twp—夏季空氣調(diào)節(jié)室外計(jì)算日平均溫度,℃;

tn—夏季空氣調(diào)節(jié)室內(nèi)計(jì)算溫度,℃;

Δtls—鄰室溫升,可根據(jù)鄰室散熱強(qiáng)度采用,℃。(五)、人體冷負(fù)荷

人體顯熱散熱形成的計(jì)算時(shí)刻冷負(fù)荷Q,按下式計(jì)算:

Qτ=nq1CclrCr(2.9)式中

Cr—群體系數(shù);

n—計(jì)算時(shí)刻空調(diào)房間內(nèi)的總?cè)藬?shù);

q1—一名成年男子小時(shí)顯熱散熱量,W;

Cclr—人體顯熱散熱冷負(fù)荷系數(shù)。、燈光冷負(fù)荷

照明設(shè)備散熱形成的計(jì)算時(shí)刻冷負(fù)荷Qτ,應(yīng)根據(jù)燈具的種類和安裝情況分別按下列各式計(jì)算:

1.白只燈和鎮(zhèn)流器在空調(diào)房間外的熒光燈

Q=1000n1NXτ-T(2.10)

2.鎮(zhèn)流器裝在空調(diào)房間內(nèi)的熒光燈

Q=1200n1NXτ-T(2.11)3.暗裝在吊頂玻璃罩內(nèi)的熒光燈

Q=1000n0NXτ-T(2.12)N—照明設(shè)備的安裝功率,kW;

n0—考慮玻璃反射,頂棚內(nèi)通風(fēng)情況的系數(shù),當(dāng)熒光燈罩有小孔,利用自然通風(fēng)散熱于頂棚內(nèi)時(shí),取為0.5-0.6,熒光燈罩無通風(fēng)孔時(shí),視頂棚內(nèi)通風(fēng)情況取為0.6-0.8;

n1—同時(shí)使用系數(shù),一般為0.5-0.8;

T—開燈時(shí)刻,點(diǎn)鐘;

τ-T—從開燈時(shí)刻算起到計(jì)算時(shí)刻的時(shí)間,h;

Xτ-T—τ-T時(shí)間照明散熱的冷負(fù)荷系數(shù)。、設(shè)備冷負(fù)荷

熱設(shè)備及熱表面散熱形成的計(jì)算時(shí)刻冷負(fù)荷Qτ,按下式計(jì)算:

Qτ=qsXτ-T(2.13)式中

T—熱源投入使用的時(shí)刻,點(diǎn)鐘;

τ-T—從熱源投入使用的時(shí)刻算起到計(jì)算時(shí)刻的時(shí)間,h;

Xτ-T—τ-T時(shí)間設(shè)備、器具散熱的冷負(fù)荷系數(shù);

qs—熱源的實(shí)際散熱量,W。

電熱、電動(dòng)設(shè)備散熱量的計(jì)算方法如下:

1.電熱設(shè)備散熱量

qs=1000n1n2n3n4N(2.14)2.電動(dòng)機(jī)和工藝設(shè)備均在空調(diào)房間內(nèi)的散發(fā)量

qs=1000n1aN(2.15)3.只有電動(dòng)機(jī)在空調(diào)房間內(nèi)的散熱量qs=1000n1a(1-η)N(2.16)4.只有工藝設(shè)備在空調(diào)房間內(nèi)的散熱量qs=1000n1aηN(2.17)式中

N—設(shè)備的總安裝功率,kW;

η—電動(dòng)機(jī)的效率;

n1—同時(shí)使用系數(shù),一般可取0.5-1.0;

n3—小時(shí)平均實(shí)耗功率與設(shè)計(jì)最大功率之比,一般可取0.5左右;

a—輸入功率系數(shù)。、滲透空氣顯熱冷負(fù)荷1.滲入空氣量的計(jì)算

(1)通過外門開啟滲入室內(nèi)空氣量G1(kg/h),按下式估算:

G1=n1V1pw

(2.18)n1—小時(shí)人流量;

V1—外門開啟一次的滲入空氣量,m3/h;

pw—夏季空調(diào)室外干球溫度下的空氣密度,kg/m3。(2)通過房間門、窗滲入空氣量G2(kg/h),按下式估算:

G2=n2V2pw(2.19)n2—每小時(shí)換氣次數(shù);

V2—房間容積,m3。

2.滲透空氣的顯冷負(fù)荷Q(W),按下式計(jì)算:

Q=0.28G(tw-tn)

(2.20)G—單位時(shí)間滲入室內(nèi)的總空氣量,kg/h;

tw—夏季空調(diào)室外干球溫度,℃;

tn—室內(nèi)計(jì)算溫度,℃。、伴隨散濕過程的潛熱冷負(fù)荷

1.人體散濕和潛熱冷負(fù)荷(1)人體散濕量按下式計(jì)算

D=0.001φng(2.21)式中

D—散濕量,kg/h;

g—一名成年男子的小時(shí)散濕量,g/h。(2)人體散濕形成的潛熱冷負(fù)荷Q(W),按下式計(jì)算:

Q=φnq2(2.22)式中

q2—一名成年男子小時(shí)潛熱散熱量,W;

φ—群體系數(shù)。2.滲入空氣散濕量及潛熱冷負(fù)荷

(1)滲透空氣帶入室內(nèi)的濕量(kg/h),按下式計(jì)算:

D=0.001G(dw-dn)(2.23)

(2)滲入空氣形成的潛熱冷負(fù)荷(W),按下式計(jì)算:

Q=0.28G(iw-in)(2.24)式中dw—室外空氣的含濕量,g/kg;

dn—室內(nèi)空氣的含濕量,g/kg;

iw—室外空氣的焓,kJ/kg;in—室內(nèi)空氣的焓,kJ/kg。

3.食物散濕量及潛熱冷負(fù)荷

(1)餐廳的食物散濕量(kg/h),按下式計(jì)算:

D=0.0115n(2.25)式中n—就餐總?cè)藬?shù)。(2)食物散濕量形成的潛熱冷負(fù)荷(W),按下式計(jì)算:

Q=8.7n(2.26)4.水面蒸發(fā)散濕量及潛熱冷負(fù)荷

(1)敞開水面的蒸發(fā)散濕量(kg/h),按下式計(jì)算:

D=(a+0.00013v)(Pqb-Pq)AB/B1(2.27)式中A—蒸發(fā)表面積,㎡;不同水溫下的擴(kuò)散系數(shù);v—蒸發(fā)表面的空氣流速;Pqb—相應(yīng)于水表面溫度下的飽和空氣的水蒸氣分壓力;

Pq—室內(nèi)空氣的水蒸氣分壓力;

B—標(biāo)準(zhǔn)大氣壓,101325Pa;B1—當(dāng)?shù)卮髿鈮海≒a)。詳細(xì)的負(fù)荷計(jì)算可見后附錄中的冷負(fù)荷計(jì)算說明書。最后資料匯總整棟建筑的最大冷負(fù)荷為2448.7kW,最大冷負(fù)荷的時(shí)間出現(xiàn)在18點(diǎn)鐘。冷指標(biāo)為93.2W/m2。

2.2新風(fēng)負(fù)荷計(jì)算2.2.1夏季空調(diào)新風(fēng)冷負(fù)荷Qc.o=Mo(ho—hR)(2.28)式中:Qc.o夏季新風(fēng)冷負(fù)荷,kW;Mo新風(fēng)量,kg/s;ho室外空氣的焓值,kJ/kg;hR室內(nèi)空氣的焓值,kJ/kg;表2-1房間類型每人最小新風(fēng)量m3/(h·人)客房、餐廳等房間30根據(jù)夏季空調(diào)室外計(jì)算干球溫度36.2℃,濕球溫度27.3℃,由濕空氣焓濕圖查得室外空氣焓值ho=70kJ/kg當(dāng)tR=26℃,φ=60℅時(shí),室內(nèi)空氣焓值hR=46kJ/kg;ΔhoR=70-46=24kJ/kg以會(huì)一樓大堂為例進(jìn)行計(jì)算,其新風(fēng)負(fù)荷為:Qc.o=Mo(ho—hR)=856×30×0.3×(70-46)/3600=51.36kw其它空調(diào)房間新風(fēng)負(fù)荷算法相同,結(jié)果詳見附錄部分的新風(fēng)負(fù)荷。夏季空調(diào)房間的總的新風(fēng)負(fù)荷是2363kW。

2、3負(fù)荷計(jì)算以及部分?jǐn)?shù)據(jù)匯總風(fēng)量計(jì)算表2-2名稱冷負(fù)荷(kw)房間人員密度面積面積熱指標(biāo)人數(shù)送風(fēng)量左前室6.7450.341.29223.36122.23356744973部電梯9.70615.771882.15618.821490468大堂72.2540.3856144.412571.444088785會(huì)計(jì)1.29136.867.6960.67690217391快餐廳32.4580.4153.76291.10622.9109521332男廁所0.60819.6830.8900.30894308943女廁所0.54417.2231.5900.31591173055辦公室0.8040.1722.1470.3140.70314363144男廁所2.35827.286.6900.86691176471女廁所2.0442485.1700.85166666667銀行左前室2.3940.519.2224.69102.246875銀行39.2460.14703.283.81980.83810580205寬四米的四個(gè)外雅間14.6150.632576.72195.7671875四個(gè)內(nèi)雅間8.3750.622.8487.32144.873245614商務(wù)中心4.6730.364133.02191.33015625商店5.1770.564180.89321.80890625消防中心4.77048107.7121.0770833333過廳1.4130.516.8184.1181.8410714286另點(diǎn)餐廳9.3290.7256176.441791.7644140625廚房21.6390.1455267.20770.67201086957右前室8.0610.1756.67176.24101.7624457385走廊2.5570.536.8169.48181.6948369565寬4.4米的外雅間3.9380.635.2231.88212.31875冷負(fù)荷計(jì)算表2-3寬4.4米的一個(gè)外雅間東外窗瞬時(shí)時(shí)間11:0012:0013:0014:0015:00twl29.9030.8031.5031.9032.20td3.003.003.003.003.00twl+td32.9033.8034.5034.9035.20tNx26.0026.0026.0026.0026.00Δt6.907.808.508.909.20CwKw3.6123.6123.6123.6123.612Fw6.246.246.246.246.24CL155.52175.80191.58200.60207.36東外窗日射時(shí)間11:0012:0013:0014:0015:00CLQ0.560.370.290.290.28Dj,max539.00539.00539.00539.00539.00Ccs0.520.520.520.520.52Fw6.246.246.246.246.24CL971.88642.13503.29503.29485.94外東墻時(shí)間11:0012:0013:0014:0015:00twl32.8034.1035.6037.2038.50td2.002.002.002.002.00kα1.021.021.021.021.02kβ0.970.970.970.970.97twl'34.4335.7237.2038.7840.07tNx26.0026.0026.0026.0026.00K3.193.193.193.193.19F13.5613.5613.5613.5613.56CL364.70420.34484.53553.01608.65照明負(fù)荷時(shí)間11:0012:0013:0014:0015:00CLQ0.100.090.080.070.06n11.201.201.201.201.20n21.001.001.001.001.00N200.00200.00200.00200.00200.00CL24.0021.6019.2016.8014.40人體散熱時(shí)間11:0012:0013:0014:0015:00CLQ0.550.640.700.750.79qs60.5060.5060.5060.5060.50n20.0020.0020.0020.0020.00φ0.930.930.930.930.93CLs618.92720.19787.71843.98888.99q173.3073.3073.3073.3073.30CL11363.381363.381363.381363.381363.38合計(jì)1982.302083.572151.092207.362252.37設(shè)備散熱時(shí)間11:0012:0013:0014:0015:00CLQ0.620.680.720.760.79q200.00200.00200.00200.00200.00CL124.00136.00144.00152.00158.0016:0017:0018:0019:0020:0021:0022:0023:000:0032.2032.0031.6030.8029.9029.1028.4027.8027.203.003.003.003.003.003.003.003.003.0035.2035.0034.6033.8032.9032.1031.4030.8030.2026.0026.0026.0026.0026.0026.0026.0026.0026.009.209.008.607.806.906.105.404.804.203.6123.6123.6123.6123.6123.6123.6123.6123.6126.246.246.246.246.246.246.246.246.24207.36202.85193.83175.80155.52137.49121.71108.1994.6616:0017:0018:0019:0020:0021:0022:0023:000:000.260.240.220.190.170.160.150.140.13539.00539.00539.00539.00539.00539.00539.00539.00539.000.520.520.520.520.520.520.520.520.526.246.246.246.246.246.246.246.246.24451.23416.52381.81329.74295.03277.68260.32242.97225.6116:0017:0018:0019:0020:0021:0022:0023:000:0039.5040.2040.5040.7040.7040.6040.2039.7039.102.002.002.002.002.002.002.002.002.001.021.021.021.021.021.021.021.021.020.970.970.970.970.970.970.970.970.9741.0641.7542.0542.2542.2542.1541.7541.2640.6626.0026.0026.0026.0026.0026.0026.0026.0026.003.193.193.193.193.193.193.193.193.1913.5613.5613.5613.5613.5613.5613.5613.5613.56651.45681.40694.24702.80702.80698.52681.40660.01634.3316:0017:0018:0019:0020:0021:0022:0023:000:000.370.670.710.760.790.810.830.840.291.201.201.201.201.201.201.201.201.201.001.001.001.001.001.001.001.001.00200.00200.00200.00200.00200.00200.00200.00200.00200.0088.80160.80170.40182.40189.60194.40199.20201.6069.6016:0017:0018:0019:0020:0021:0022:0023:000:000.810.840.860.880.890.910.920.450.3660.5060.5060.5060.5060.5060.5060.5060.5060.5020.0020.0020.0020.0020.0020.0020.0020.0020.000.930.930.930.930.930.930.930.930.93911.49945.25967.76990.261001.521024.021035.28506.39405.1173.3073.3073.3073.3073.3073.3073.3073.3073.301363.381363.381363.381363.381363.381363.381363.381363.381363.382274.872308.632331.142353.642364.902387.402398.661869.771768.4916:0017:0018:0019:0020:0021:0022:0023:000:000.810.840.600.480.390.330.280.240.21200.00200.00200.00200.00200.00200.00200.00200.00200.00162.00168.00120.0096.0078.0066.0056.0048.0042.00表2-4大堂西外窗瞬時(shí)時(shí)間11:0012:0013:0014:0015:00twl29.9030.8031.5031.9032.20td3.003.003.003.003.00twl+td32.9033.8034.5034.9035.20tNx26.0026.0026.0026.0026.00Δt6.907.808.508.909.20CwKw3.6123.6123.6123.6123.612Fw44.0744.0744.0744.0744.07CL1098.351241.611353.041416.711464.46西外窗日射時(shí)間11:0012:0013:0014:0015:00CLQ0.170.180.250.370.47Dj,max539.00539.00539.00539.00539.00Ccs0.520.520.520.520.52Fw44.0744.0744.0744.0744.07CL2083.682206.253064.234535.065760.75西幕墻時(shí)間11:0012:0013:0014:0015:00twl32.8032.4032.1032.1032.30td3.003.003.003.003.00kα1.021.021.021.021.02kβ0.970.970.970.970.97twl'35.4235.0234.7334.7334.93tNx26.0026.0026.0026.0026.00K3.303.303.303.303.30F152.13152.13152.13152.13152.13CL4729.374530.694381.684381.684481.02西幕墻瞬時(shí)時(shí)間11:0012:0013:0014:0015:00twl29.9030.8031.5031.9032.20td3.003.003.003.003.00twl+td32.9033.8034.5034.9035.20tNx26.0026.0026.0026.0026.00Δt6.907.808.508.909.20CwKw3.3003.3003.3003.3003.300Fw152.13152.13152.13152.13152.13CL3464.003915.834267.254468.064618.67西幕墻日射時(shí)間11:0012:0013:0014:0015:00CLQ0.190.200.340.560.72Dj,max539.00539.00539.00539.00539.00Ccs0.740.740.740.740.74Fw152.13152.13152.13152.13152.13CL11528.9312135.7120630.7133980.0043688.57西外墻時(shí)間11:0012:0013:0014:0015:00twl32.8032.4032.1032.1032.30td2.002.002.002.002.00kα1.021.021.021.021.02kβ0.970.970.970.970.97twl'34.4334.0433.7433.7433.94tNx26.0026.0026.0026.0026.00K3.193.193.193.193.19F11.6911.6911.6911.6911.69CL314.33299.58288.51288.51295.89照明負(fù)荷時(shí)間11:0012:0013:0014:0015:00CLQ0.100.090.080.070.06n11.201.201.201.201.20n21.001.001.001.001.00N34003400340034003400CL408367326286245設(shè)備散熱時(shí)間11:0012:0013:0014:0015:00CLQ0.620.680.720.760.79n3.003.003.003.003.00q1065.001065.001065.001065.001065.00CL1980.902172.602300.402428.202524.05南外墻時(shí)間11:0012:0013:0014:0015:00K3.19F12.00Δt6.20CL237.26南外門時(shí)間11:0012:0013:0014:0015:00K4.65F2.40Δt6.20CL69.19大堂管道間西墻時(shí)間11:0012:0013:0014:0015:00K3.19F14.40Δt6.20CL284.8016:0017:0018:0019:0020:0021:0022:0023:000:0032.2032.0031.6030.8029.9029.1028.4027.8027.203.003.003.003.003.003.003.003.003.0035.2035.0034.6033.8032.9032.1031.4030.8030.2026.0026.0026.0026.0026.0026.0026.0026.0026.009.209.008.607.806.906.105.404.804.203.6123.6123.6123.6123.6123.6123.6123.6123.61244.0744.0744.0744.0744.0744.0744.0744.0744.071464.461432.631368.961241.611098.35971.00859.58764.07668.5616:0017:0018:0019:0020:0021:0022:0023:000:000.520.620.550.240.230.210.200.180.17539.00539.00539.00539.00539.00539.00539.00539.00539.000.520.520.520.520.520.520.520.520.5244.0744.0744.0744.0744.0744.0744.0744.0744.076373.607599.296741.312941.662819.092573.952451.382206.252083.6816:0017:0018:0019:0020:0021:0022:0023:000:0032.8033.7035.0036.7038.7040.5042.0042.8042.903.003.003.003.003.003.003.003.003.001.021.021.021.021.021.021.021.021.020.970.970.970.970.970.970.970.970.9735.4236.3137.6039.2841.2643.0444.5245.3145.4126.0026.0026.0026.0026.0026.0026.0026.0026.003.303.303.303.303.303.303.303.303.30152.13152.13152.13152.13152.13152.13152.13152.13152.134729.375176.415822.136666.537659.958554.029299.089696.459746.1216:0017:0018:0019:0020:0021:0022:0023:000:0032.2032.0031.6030.8029.9029.1028.4027.8027.203.003.003.003.003.003.003.003.003.0035.2035.0034.6033.8032.9032.1031.4030.8030.2026.0026.0026.0026.0026.0026.0026.0026.0026.009.209.008.607.806.906.105.404.804.203.3003.3003.3003.3003.3003.3003.3003.3003.300152.13152.13152.13152.13152.13152.13152.13152.13152.134618.674518.264317.453915.833464.003062.382710.962409.742108.5216:0017:0018:0019:0020:0021:0022:0023:000:000.830.770.530.110.100.090.090.080.08539.00539.00539.00539.00539.00539.00539.00539.00539.000.740.740.740.740.740.740.740.740.74152.13152.13152.13152.13152.13152.13152.13152.13152.1350363.2146722.5032159.646674.646067.865461.075461.074854.294854.2916:0017:0018:0019:0020:0021:0022:0023:000:0032.8033.7035.0036.7038.7040.5042.0042.8042.902.002.002.002.002.002.002.002.002.001.021.021.021.021.021.021.021.021.020.970.970.970.970.970.970.970.970.9734.4335.3236.6138.2940.2742.0543.5344.3344.4226.0026.0026.0026.0026.0026.0026.0026.0026.003.193.193.193.193.193.193.193.193.1911.6911.6911.6911.6911.6911.6911.6911.6911.69314.33347.53395.49458.19531.97598.37653.70683.21686.9016:0017:0018:0019:0020:0021:0022:0023:000:000.370.670.710.760.790.810.830.840.291.201.201.201.201.201.201.201.201.201.001.001.001.001.001.001.001.001.0034003400340034003400340034003400340015102734289731013223330533863427118316:0017:0018:0019:0020:0021:0022:0023:000:000.810.840.600.480.390.330.280.240.213.003.003.003.003.003.003.003.003.001065.001065.001065.001065.001065.001065.001065.001065.001065.002587.952683.801917.001533.601246.051054.35894.60766.80670.95第三章空調(diào)系統(tǒng)方案的確定3.1.確定空調(diào)系統(tǒng)方案的因素空調(diào)系統(tǒng)的方案確定與很多因素有關(guān),在設(shè)計(jì)是應(yīng)與建筑、結(jié)構(gòu)、工藝等專業(yè)密切配合,其中主要需考慮以下的因素:1.外部環(huán)境(1)氣象資料:建筑物所處的地點(diǎn),緯度,海拔高度,室外氣溫、相對(duì)濕度、風(fēng)向、平均風(fēng)速,冬季和夏季的日照率等。(2)周圍環(huán)境:建筑物周圍有無有害氣體放散源、灰塵放散源;周圍環(huán)境噪聲要求;屬于住宅區(qū)、混合區(qū)還是工業(yè)區(qū);周圍建筑的位置、規(guī)模和高度;環(huán)保、防火和城市規(guī)劃等部門對(duì)本建筑的要求等。2.所設(shè)計(jì)建筑物的特點(diǎn)(1)規(guī)模:需要所空調(diào)凈化的面積,所在的位置。(2)用途:目前的用途,今后可能的改變。(3)室內(nèi)參數(shù)要求:要求的溫度、相對(duì)濕度及其允許波動(dòng)范圍,有無區(qū)域溫差要求;允許的工作區(qū)氣流速度和均勻度;房間的凈化要求;需不需要過濾、需要的凈化級(jí)別;噪聲的控制要求等。(4)負(fù)荷情況:房間朝向、圍護(hù)結(jié)構(gòu)的構(gòu)造,窗的構(gòu)造和尺寸;設(shè)備的發(fā)熱情況,人員及其流動(dòng)情況,照明等發(fā)熱情況;排風(fēng)量。(5)能源:有無區(qū)域供熱、供冷及其壓力、溫度,可供應(yīng)的量、價(jià)格等。3.2空調(diào)系統(tǒng)方案的比較及選擇空調(diào)系統(tǒng)一般由空氣處理設(shè)備和空氣輸送管道以及空氣分配裝置組成。根據(jù)需要,可以組成許多不同形式的系統(tǒng)。工程中常用到的空調(diào)系統(tǒng)形式有一次回風(fēng)系統(tǒng)、變風(fēng)量(VAV)空調(diào)系統(tǒng)、風(fēng)機(jī)盤管+新風(fēng)空調(diào)系統(tǒng)、水環(huán)熱泵空調(diào)系統(tǒng)、變制冷劑流量(VRV)空調(diào)系統(tǒng)、家用中央空調(diào)系統(tǒng)等。3.2.1空調(diào)系統(tǒng)的分類現(xiàn)如今在我國廣泛應(yīng)用的系統(tǒng)主要有以下幾種:風(fēng)機(jī)盤管加新風(fēng)系統(tǒng)、制冷劑系統(tǒng)、傳統(tǒng)的中央空調(diào)、冷熱組合系統(tǒng)中的熱泵系統(tǒng)及燃?xì)忮仩t加制冷系統(tǒng)等。一、按介質(zhì)分類:(1)全水系統(tǒng):熱水時(shí)承擔(dān)室內(nèi)熱負(fù)荷;冷水時(shí)承擔(dān)冷負(fù)荷和濕負(fù)荷。優(yōu)點(diǎn)是:輸送能耗低水管占空間小;使用靈活方便,各房間可獨(dú)立調(diào)節(jié)控制;各房間空氣互不串通,有利于保證空氣品質(zhì);系統(tǒng)占建筑面積小。缺點(diǎn)是:運(yùn)行維護(hù)量大;無加濕功能;風(fēng)機(jī)盤管運(yùn)行時(shí)有噪音。適用于對(duì)室內(nèi)空氣品質(zhì)要求不高的旅館客房的等建筑中。(2)全空氣系統(tǒng):以空氣為介質(zhì)向室內(nèi)提供冷量或熱量。優(yōu)點(diǎn)是:空氣分布可按需要均勻分布,可采用全新風(fēng)使空氣品質(zhì)好,有較強(qiáng)的除濕能力,維護(hù)簡單。缺點(diǎn)是:對(duì)層高有要求,風(fēng)水管占用空間大。適用于高大空間的場所,冷負(fù)荷密度大潛熱負(fù)荷大或?qū)κ覂?nèi)含塵濃度由要求的場所。(3)空氣水系統(tǒng):以空氣和水為介質(zhì)共同承擔(dān)室內(nèi)的負(fù)荷。優(yōu)點(diǎn)是:可各房間分別單獨(dú)控制,室內(nèi)空氣品質(zhì)較好,出初投資低,而且機(jī)房占用面積小。缺點(diǎn)是:不可采用全新風(fēng)運(yùn)行,維修量大,運(yùn)行費(fèi)用高。(4)冷劑系統(tǒng):以制冷劑為介質(zhì)直接用于對(duì)室內(nèi)空調(diào)進(jìn)行冷卻去濕或加熱即擁戴制冷機(jī)的空調(diào)器來處理室內(nèi)的負(fù)荷。優(yōu)點(diǎn)是:結(jié)構(gòu)緊湊體積小占地面積小自動(dòng)化程度高,機(jī)房層高要求低,使用靈活方便,各房間不會(huì)相互污染串聲,發(fā)生火災(zāi)時(shí)不會(huì)通過風(fēng)道蔓延對(duì)防火有利,比較環(huán)保。缺點(diǎn)是:能源的選擇和組合受限制,制冷性能系數(shù)較小,噪聲大壽命較短。2)按用途分類:制冷空調(diào)按用途分類主要有家用制冷空調(diào)、商用制冷空調(diào)、工業(yè)制冷空調(diào)三個(gè)部分,下面從這三個(gè)方面作以介紹:a)

家用空調(diào)當(dāng)中現(xiàn)今運(yùn)用最為廣泛的一種系統(tǒng)為變制冷劑流量系統(tǒng)。變制冷劑流量(VariedRefrigerantVolume,簡稱VRV)空調(diào)系統(tǒng)是一種冷劑式空調(diào)系統(tǒng),它以制冷劑為輸送介質(zhì),室外主機(jī)由室外側(cè)換熱器、壓縮機(jī)和其他制冷附件組成,末端裝置是由直接蒸發(fā)式換熱器和風(fēng)機(jī)組成的室內(nèi)機(jī)。一臺(tái)室外機(jī)通過管路能夠向若干個(gè)室內(nèi)機(jī)輸送制冷劑液體。通過控制壓縮機(jī)的制冷劑循環(huán)量和進(jìn)入室內(nèi)各換熱器的制冷劑流量,可以適時(shí)地滿足室內(nèi)冷、熱負(fù)荷要求。

VRV系統(tǒng)具有節(jié)能、舒適、運(yùn)轉(zhuǎn)平穩(wěn)等諸多優(yōu)點(diǎn),而且各房間可獨(dú)立調(diào)節(jié),能滿足不同房間不同空調(diào)負(fù)荷的需求。但該系統(tǒng)控制復(fù)雜,對(duì)管材材質(zhì)、制造工藝、現(xiàn)場焊接等方面要求非常高,且其初投資比較高。其次是水源熱泵空調(diào),目前市場上較適用的是閉式水環(huán)路水源熱泵機(jī)組,由于大多在小區(qū)內(nèi)設(shè)置集中冷卻水房,經(jīng)過室外管網(wǎng)送到各用戶,室內(nèi)機(jī)包括壓縮機(jī)、盤管等設(shè)備,機(jī)組一般設(shè)置在衛(wèi)生間的吊頂上。它不同于一機(jī)一戶式的小型中央空調(diào),隨著水環(huán)熱泵技術(shù)等集中供熱/冷技術(shù)的成熟,相信這種小區(qū)式中央空調(diào)也將會(huì)更加廣泛的應(yīng)用。另外商用制冷空調(diào)主要有以下幾種:蓄冰空調(diào)系統(tǒng)它是采用單螺桿雙溫工況冷水機(jī)組和冰球罐冰方式,并設(shè)有完善的微機(jī)中央工作站檢測和控制系統(tǒng)。它目前被很多大型酒店所采用,該系統(tǒng)設(shè)計(jì)合理,設(shè)備性能可靠、施工優(yōu)質(zhì)、控制先進(jìn)。直燃型溴化鋰吸收式冷熱水機(jī)組由于直燃機(jī)不以電位能源(只需極少的電作輔助的循環(huán)動(dòng)力),可以大幅度削減電力投資。由于我國目前電力緊張,其直燃機(jī)的這個(gè)特點(diǎn)也將會(huì)使它在電力行業(yè)及燃?xì)庑袠I(yè)的健康發(fā)展上有舉足輕重的影響。隨著我國工業(yè)化的進(jìn)程,燃料結(jié)構(gòu)必將發(fā)生變化,將由固體燃料(煤)、液體(油)、氣體(可燃?xì)怏w)多樣化的燃料結(jié)構(gòu),而我國的氣體,液體燃料運(yùn)輸方便,燃料效率高登有點(diǎn),其更受青睞??深A(yù)計(jì),我國燃?xì)?、燃油直燃機(jī)的市場將十分廣闊。模塊式風(fēng)冷熱泵機(jī)組模塊式風(fēng)冷熱泵機(jī)組是各個(gè)獨(dú)立的風(fēng)冷熱泵機(jī)組組合在一起同時(shí)使用,目前模塊式機(jī)組時(shí)商用空調(diào)市場銷售非常好的機(jī)型。它的優(yōu)點(diǎn)是可以根據(jù)客戶的負(fù)荷情況改變模塊單元機(jī)組的數(shù)量或允許客戶在使用過程中再增加機(jī)組,方便客戶根據(jù)自己的資金和適用情況靈活采購和使用機(jī)組。在模塊式風(fēng)冷熱能迸機(jī)組的結(jié)構(gòu)上,每個(gè)模塊均有相同口徑的進(jìn)出水管,模塊之間只需水管對(duì)接即可,安裝非常方便,由于模塊機(jī)這種特殊的形式,、模塊機(jī)組的進(jìn)出水管的流速不確定,給模塊機(jī)組的水流控制帶來了一定的難度。確保每個(gè)模塊得到合適的水流量三模塊機(jī)組可靠工作的必要保證,不適當(dāng)?shù)乃髁靠赡軐?dǎo)致某個(gè)模塊單元機(jī)組蒸發(fā)器凍結(jié)、冷暖壓力高、壓縮機(jī)“咬缸”等故障。對(duì)于模塊機(jī)組一般制冷量比較大,因此模塊機(jī)組的水流量控制及保護(hù)是非常重要的,合適的水流檢測方法以及檢測部件可以保證機(jī)組只在系統(tǒng)水流量的的大于允許的最小流量小工作,在很大程度上可以避免空調(diào)主機(jī)發(fā)生故障。活塞式、離心式冷水機(jī)組活塞式、離心式冷水機(jī)組時(shí)目前大多數(shù)商場所采用的制冷系統(tǒng),因?yàn)樗倪\(yùn)行和保養(yǎng)十分方便,采用后基本上能保證到它的使用期,所以很多商家會(huì)首選這種制冷機(jī)組。而工業(yè)(民用)制冷系統(tǒng)比較有專業(yè)性,針對(duì)性比較強(qiáng),控制也比較嚴(yán)格。表現(xiàn)在以下幾個(gè)方面:例如醫(yī)院病房樓潔凈手術(shù)部空調(diào)設(shè)計(jì)強(qiáng)調(diào)應(yīng)該以全過程控制的概念和手術(shù)室細(xì)菌的綜合措施來真正有效的減少手術(shù)后感染率。分析了手術(shù)室界潔凈空調(diào)系統(tǒng)的熱濕處理過程,指出應(yīng)以經(jīng)濟(jì)有效的手段來實(shí)施手術(shù)室潔凈送風(fēng)系統(tǒng),避免過高的初投資和運(yùn)行成本。合理的布局和設(shè)施保證手術(shù)后患者的感染率,減少抗生素的用量。手術(shù)部潔凈用房的等級(jí)在突出生物潔凈濕特點(diǎn)的原則下,以控制有生命微粒為主要目標(biāo),故應(yīng)以細(xì)菌濃度來進(jìn)行分級(jí),而空氣潔凈度標(biāo)準(zhǔn)的方法造成不必要的額外投資和昂貴的云運(yùn)行費(fèi)用。而設(shè)計(jì)樓辦公樓的制冷設(shè)計(jì)主要體現(xiàn)在噪聲和震動(dòng)方面,除了要滿足舒適性還要保證工作不受影響,所以在制冷上重點(diǎn)也要考慮這兩方面的污染,當(dāng)然制冷機(jī)組的制冷劑藥考慮是不是有毒。對(duì)于像會(huì)堂和圖書館、候車室此類建造制冷首要考慮安全問題,目前采用氟利昂的還是很多,但是一般不采用吸收式制冷,考慮到制冷量的關(guān)系。根據(jù)以上空調(diào)系統(tǒng)方案確定因素的分析,本設(shè)計(jì)的空調(diào)系統(tǒng)方案確定如下:該建筑二至五層各房間均采用風(fēng)機(jī)盤管加獨(dú)立新風(fēng)的末端裝置;一層綜合營業(yè)廳則采用VRV變制冷劑流量空調(diào)系統(tǒng)。3.2.2房間中的新風(fēng)送風(fēng)方式房間中的新風(fēng)供應(yīng)有三種方式:(1)新風(fēng)與風(fēng)機(jī)盤管各自送風(fēng)至空調(diào)房間。這種方式即使風(fēng)機(jī)盤管機(jī)組停止運(yùn)行,新風(fēng)將保持不變。(2)新風(fēng)與風(fēng)機(jī)盤管的出風(fēng)口處(壓出端)混合。這種方式無需設(shè)置專門的新風(fēng)口,對(duì)吊頂布置比較有利;當(dāng)風(fēng)機(jī)盤管機(jī)組運(yùn)行時(shí),要求新風(fēng)提高在該處的壓力。這種的方法在衛(wèi)生條件上較好。(3)新風(fēng)與風(fēng)機(jī)盤管回風(fēng)混合后送入空調(diào)房間。這種方式與上述兩種方式比較房間換氣次數(shù)略有減少;當(dāng)風(fēng)機(jī)盤管機(jī)組停止運(yùn)行時(shí),新風(fēng)量有所減少;而且新風(fēng)從回風(fēng)口吹出,回風(fēng)口一般都有過濾器,此時(shí)過濾器上灰塵將被吹入房間。根據(jù)最新的空調(diào)衛(wèi)生標(biāo)準(zhǔn)次種送風(fēng)方式已禁止使用。所以本設(shè)計(jì)均采用新風(fēng)加風(fēng)機(jī)盤管的方法。3.2.3新風(fēng)處理狀態(tài)點(diǎn)的分析房間的顯熱冷負(fù)荷和濕負(fù)荷(包括新風(fēng)負(fù)荷)是由風(fēng)機(jī)盤管與新風(fēng)共同來承擔(dān),因此風(fēng)機(jī)盤管與新風(fēng)如何分配這些負(fù)荷是設(shè)計(jì)者應(yīng)該考慮的,目前有三種設(shè)計(jì)方案:方案一,新風(fēng)處理到低于室內(nèi)的含濕量,承擔(dān)室內(nèi)的濕負(fù)荷。這時(shí)風(fēng)機(jī)盤管只承擔(dān)室內(nèi)部分顯熱冷負(fù)荷。優(yōu)點(diǎn)是(1)盤管表面干燥,衛(wèi)生條件好;(2)冷凍水溫度高,如盤管用冷凍水單獨(dú)有冷水機(jī)組制備,則它的制冷系數(shù)高,能耗低;(3)在室外濕球溫度低時(shí),可利用冷卻塔的水做冷源,或采用地下水做冷源,以降低人空制冷的能耗。缺點(diǎn)是:(1)新風(fēng)系統(tǒng)需要溫度比較低的冷凍水,而盤管需要溫度比較高的冷凍水,因此冷凍水系統(tǒng)比較復(fù)雜;(2)盤管在干工況下運(yùn)行,其制冷能力大約只有原來標(biāo)準(zhǔn)工況(7℃冷凍水)的60%以下,雖然風(fēng)機(jī)盤管負(fù)荷減少了,但所選用的風(fēng)機(jī)盤管的規(guī)格并不能減小,而這時(shí)新風(fēng)系統(tǒng)的冷卻設(shè)備因負(fù)荷增加而需要加大規(guī)格;(3)一些不可預(yù)見的原因使室內(nèi)濕負(fù)荷增加(如室內(nèi)人員密度增加,室外濕空氣滲入房間),風(fēng)機(jī)盤管也可能出現(xiàn)所不希望的工況。方案二,新風(fēng)處理到室內(nèi)空氣的焓值,而風(fēng)機(jī)盤管承擔(dān)室內(nèi)人員、設(shè)備冷負(fù)荷和建筑維護(hù)結(jié)構(gòu)冷負(fù)荷。新風(fēng)與風(fēng)機(jī)盤管的空氣處理過程及送風(fēng)在室內(nèi)的狀態(tài)變化過程在h-d圖上的表示見圖3-1。室外新風(fēng)W被冷卻處理到機(jī)器露點(diǎn)D;此點(diǎn)的溫度根據(jù)設(shè)計(jì)的室內(nèi)狀態(tài)點(diǎn)的焓只限于相對(duì)濕度90%線的交點(diǎn)確定。工程實(shí)踐中多采用此種設(shè)計(jì)方案。方案三,根據(jù)室內(nèi)的冷負(fù)荷、濕負(fù)荷和風(fēng)機(jī)盤管的熱濕比確定新風(fēng)的處理狀態(tài)點(diǎn)這種方案很復(fù)雜。本設(shè)計(jì)采用方案二來進(jìn)行設(shè)計(jì)。3.3送風(fēng)量與氣流組織3.3.1送風(fēng)量的確定采用新風(fēng)不擔(dān)負(fù)室內(nèi)負(fù)荷的方案,即送入室內(nèi)新風(fēng)的焓處理到與室內(nèi)空氣焓hn線,新風(fēng)處理的機(jī)器露點(diǎn)相對(duì)濕度即可定出新風(fēng)處理后的機(jī)器露點(diǎn)L。空調(diào)系統(tǒng)送風(fēng)狀態(tài)和送風(fēng)量的確定可在h-d圖上進(jìn)行,具體步驟如下:[1]在i-d圖上找出室內(nèi)狀態(tài)點(diǎn)N,室外狀態(tài)點(diǎn)W[2]根據(jù)計(jì)算出的室內(nèi)冷負(fù)荷Q和濕負(fù)荷W求出,再過N點(diǎn)畫出線與φ=90℅線相交,得送風(fēng)點(diǎn)S[3]根據(jù)hn等焓線,由新風(fēng)處理后的機(jī)器露點(diǎn)相對(duì)濕度定出D點(diǎn):[4]過N點(diǎn)作機(jī)械熱濕比線FC與DS線交于F點(diǎn);[5]連接N,F(xiàn)如圖3-1所示:3.3.2氣流組織的形式及其選擇常用氣流組織的形式及其使用范圍空調(diào)調(diào)房間的氣流組織也稱空氣分布,是空調(diào)設(shè)計(jì)的一個(gè)重要環(huán)節(jié)。影響氣流組織的因素很多,如房間的幾何形狀、送回風(fēng)口的位置、送風(fēng)口的形式、送風(fēng)量等等,其中送風(fēng)口的空氣射流和參數(shù)是影響氣流組織的重要因素。.1氣流組織的形式:(1)上送下回方式上送下回方式是最基本的氣流組織形式。送風(fēng)口安裝在房間的側(cè)上部或頂棚上,而回風(fēng)口則設(shè)在房間的下部。它的主要特點(diǎn)是送風(fēng)氣流在進(jìn)入工作區(qū)之前就已經(jīng)與室內(nèi)空氣充分混合,易形成均勻的溫度場和速度場,適用于溫濕度和潔凈度要求較高的空調(diào)房間。(2)上送上回方式次種方式的主要特點(diǎn)是施工方便,但影響房間的凈空使用,且如設(shè)計(jì)計(jì)算不準(zhǔn)確,會(huì)造成氣流短路,影響空氣質(zhì)量。這種布置比較適用于有一定美觀要求的民用建筑。(3)中送風(fēng)某些高大空間的空調(diào)房間,采用前述方式需要送風(fēng)量大,空調(diào)耗熱量也大。因而采用在房間高度的中部位置上用側(cè)送風(fēng)口或噴口送風(fēng)的方式。中送風(fēng)是將房間下部作為空調(diào)區(qū),上部作為非空調(diào)區(qū)。在滿足工作區(qū)要求的前提下,有顯著的節(jié)能效果。(4)下送風(fēng)此種送風(fēng)方式直接進(jìn)入工作區(qū),為滿足生產(chǎn)或人的要求,送風(fēng)溫差必然遠(yuǎn)小于上送風(fēng)方式,因而加大了送風(fēng)量。同時(shí)考慮到人的舒適條件,送風(fēng)速度也不能大,一般不超過0.50.7m/s,這就必須增大送風(fēng)口的面積或數(shù)量,給風(fēng)口布置帶來困難。此外,地面容易積聚贓物,將會(huì)影響送風(fēng)的清潔度。但下送風(fēng)方式能使新鮮空氣首先通過工作區(qū),同時(shí)由于是頂部排風(fēng),因而房間上部余熱可以不進(jìn)入工作區(qū)而直接排走,故具有一定的節(jié)能效果,同時(shí)有利于改善工作區(qū)的空氣質(zhì)量。.2常見送回風(fēng)口形式:(1).側(cè)送側(cè)送是空調(diào)房間中最常用的一種氣流組織方式。一般為貼附射流形式出現(xiàn),工作區(qū)通常是回流。對(duì)于室溫允許波動(dòng)范圍有要求的空調(diào)房間,一般能夠滿足區(qū)域溫差的要求。因此,除了區(qū)域溫差和工作區(qū)風(fēng)速要求很嚴(yán)格,以及送風(fēng)射程很短,不能滿足射流擴(kuò)散和室溫溫差衰減的要求以外,通常宜采用這種方式。(2).散流器平送和下送散流器平送和側(cè)送一樣,工作區(qū)總處于回流,但送風(fēng)射流射程和回流的流程都比側(cè)送短。空氣由散流器送出時(shí),沿著頂棚和墻形成帖附射流,射流擴(kuò)散較好,區(qū)域溫差一般能滿足。散流器下送,只有采用頂棚密集布置向下送風(fēng)時(shí),工作區(qū)風(fēng)速才能均勻,有可能形成平行流,對(duì)有潔凈度要求的房間有利。(3).噴口送風(fēng)噴口送風(fēng)是大型體育館、禮堂、劇院、通用大廳以及高大空間等建筑中通常采用的一種送風(fēng)方式。由高速噴口送出的射流帶動(dòng)室內(nèi)空氣進(jìn)行強(qiáng)烈混合,使射流流量成倍的增加,射流截面不斷擴(kuò)大,速度逐漸衰減,室內(nèi)形成大的回旋氣流,工作區(qū)一般是回流。由于這種送風(fēng)方式具有射程遠(yuǎn)、系統(tǒng)簡單、投資較省,一般能夠滿足工作區(qū)舒適條件。因此,在高大空間以及要求舒適性的空調(diào)建筑中,宜采用噴口送風(fēng)。(4)回風(fēng)口由于回風(fēng)口的氣流流動(dòng)對(duì)室內(nèi)氣流組織影響不大,因而回風(fēng)口的構(gòu)造比較簡單。常用的回風(fēng)口有單層百葉風(fēng)口、格柵風(fēng)口、網(wǎng)式風(fēng)口及活動(dòng)蓖板式風(fēng)口。回風(fēng)口的形狀和位置根據(jù)氣流組織要求而定。根據(jù)以上介紹,在本設(shè)計(jì)中的房間均選擇采用都采用散流器平送風(fēng)方式。氣流組織的計(jì)算方法散流器應(yīng)根據(jù)《采暖通風(fēng)國家標(biāo)準(zhǔn)圖集》和生產(chǎn)廠樣本選取。根據(jù)空調(diào)房間的大小和室內(nèi)所要求的參數(shù),確定散流器個(gè)數(shù)。一般按對(duì)稱位置或梅花形布置,梅花形布置時(shí)每個(gè)散流器送出氣流有互補(bǔ)性,氣流組織更為均勻。布置散流器時(shí),散流器之間的距離及離墻的距離,一方面應(yīng)使射流有足夠射程,另一方面又應(yīng)使射流擴(kuò)散效果好。布置時(shí)充分考慮建筑結(jié)構(gòu)的特點(diǎn),散流器平送風(fēng)方向不得有障礙物。每個(gè)圓形或方形散流器所服務(wù)的區(qū)域最好為正方形或接近正方形。圓形或方形散流器相應(yīng)送風(fēng)面積的長邊和短邊比值不宜大于1.5。散流器中心線和側(cè)墻的距離,一般不應(yīng)小于1m。如果散流器服務(wù)區(qū)的長寬比大于1.25時(shí),宜選用矩形散流器。散流器的水平射程與垂直射程(hx=H-2)之比應(yīng)維持在0.51.5。散流器平送氣流組織的設(shè)計(jì)步驟如下:(1)按照房間(或分區(qū))的尺寸布置散流器,計(jì)算每個(gè)散流器的送風(fēng)量。(2)初選散流器。按下表選擇適當(dāng)?shù)纳⒘髌鲃挪匡L(fēng)速Uo,層高較低或要求噪聲低時(shí)。應(yīng)選低風(fēng)速;層高較高或噪聲控制要求不高時(shí),可選用高風(fēng)速;選定風(fēng)速后,進(jìn)一步選定散流器規(guī)格,可參看有關(guān)樣本。表3-1送風(fēng)勁部最大允許風(fēng)速使用場合勁部最大風(fēng)速/(m/s)播音室3~3.5醫(yī)院門診、病房、旅館客房、接待室、居市、計(jì)算機(jī)房4~5劇場、劇場休息市、教室、音樂廳、食堂、圖書館、游藝廳、一般辦公室5~6商店、旅館、大劇場、飯店6~7.5選定散流器后可算出實(shí)際勁部風(fēng)速。散流器實(shí)際出口面積約為勁部面積的90%,所以Uo=Uo’/0.9。(3)計(jì)算射程(4)校核工作區(qū)的平均速度。若Um滿足工作區(qū)風(fēng)速要求,則認(rèn)為設(shè)計(jì)合理;若Um不滿足工作區(qū)風(fēng)速要求,則重新布置散流器,重新計(jì)算。

第四章冷熱源的選擇分析及設(shè)計(jì)4.1風(fēng)冷與水冷機(jī)組的比較4.1.1風(fēng)冷與水冷機(jī)組費(fèi)用上的比較一、風(fēng)冷機(jī)組與水冷冷水機(jī)組的初投資的比較

風(fēng)冷熱泵機(jī)組所需的附屬設(shè)施為:冷凍水泵、集水器、分水器而水冷式冷水機(jī)組所需的設(shè)施為:專用機(jī)房、冷卻塔、冷卻水泵、冷凍水泵、集水器、分水器。從中可以得出在初期投資中風(fēng)冷熱泵機(jī)組要小于水冷式冷水機(jī)組。

二、風(fēng)冷熱泵機(jī)組與水冷冷水機(jī)組的運(yùn)行費(fèi)用的綜比較合

1、電量的比較:比較兩者的耗電量應(yīng)明確機(jī)組裝機(jī)容量與耗電量的區(qū)別及負(fù)荷分布對(duì)機(jī)組效率和耗電量的影響。全負(fù)荷時(shí),風(fēng)冷式冷水機(jī)組之冷凝溫度高于水冷式機(jī)組,故風(fēng)冷式冷水機(jī)組的壓縮機(jī)需要較大的功率,但是空調(diào)負(fù)荷在整個(gè)夏季的分布式及不均勻的,所以機(jī)組在最大負(fù)荷下運(yùn)行的時(shí)間是極其有限的。風(fēng)冷式冷水機(jī)組的冷凝溫度取決于室外干球溫度,而水冷式冷水機(jī)組的冷凝溫度則取決于室外濕球溫度。在一天之內(nèi),室外空氣干球溫度的變化比濕球溫度要大得多,在干旱地區(qū)甚至可以達(dá)到15℃—16℃,而濕球溫度在一天之內(nèi)是變化很小的所以可以認(rèn)為水冷式機(jī)組的冷凝溫度在一天之內(nèi)是幾乎不變,而風(fēng)冷式機(jī)組的冷凝溫度當(dāng)室外干球溫度下降時(shí)隨之下降。

2、維護(hù)費(fèi)用的比較:風(fēng)冷式冷水機(jī)組在維護(hù)上只需要對(duì)機(jī)組本身進(jìn)行維護(hù)而水冷式冷水機(jī)組不僅要對(duì)機(jī)組進(jìn)行維護(hù)對(duì)冷卻設(shè)施也需要很多的維護(hù)其中冷卻塔的維護(hù)費(fèi)用尤為多,例如風(fēng)機(jī)電機(jī)軸承的更換、水泵的軸瓦、軸套的更換、冷卻塔的沖洗等等。

結(jié)論:

(1)風(fēng)冷式機(jī)組的初投資要比水冷式機(jī)組的初投資低但單位制冷耗電量要略高于水冷機(jī)組,但風(fēng)冷機(jī)組的年度綜合費(fèi)用與水冷機(jī)組基本持平或稍低。

(2)從運(yùn)行上看,只有在機(jī)組年運(yùn)行時(shí)間非常長的情況下,水冷機(jī)組才有可能在以后慢慢收回高出的那部分投資。

(3)水冷機(jī)組冷卻水補(bǔ)水量的多少是影響其費(fèi)用的重要因素。加強(qiáng)維護(hù)管理,減少水消耗量是降低水冷機(jī)組費(fèi)用的重要方面。4.1.2風(fēng)冷與水冷機(jī)組優(yōu)缺點(diǎn)比較同水冷機(jī)組相比,風(fēng)冷機(jī)組具有以下優(yōu)缺點(diǎn):

不需要占用專門的機(jī)房,并且無需安裝冷卻塔及泵房,維修簡單,運(yùn)行方便,無需專業(yè)人員維護(hù)。

無冷卻水系統(tǒng),無冷卻水系統(tǒng)動(dòng)力消耗,無冷卻水損耗。

空氣源熱泵體型較大,占地面積大,同時(shí)室外機(jī)噪聲較高,并存在熱島效應(yīng),使得外界局部空間環(huán)境條件惡化。

冬季在一定的溫度和濕度條件下,室外機(jī)組需要除霜,浪費(fèi)能源,相關(guān)文獻(xiàn)顯示除霜損失約占熱泵總能耗損失的10%左右;

受室外環(huán)境制約:這是空氣源熱泵的主要缺點(diǎn)。在遇到夏季高溫和冬季寒冷的天氣時(shí)熱泵的效率大大降低,而且制熱量隨室外空氣溫度降低而減少,制冷量隨室外溫度升高而降低,這與建筑熱負(fù)荷需求趨勢正好相反;尤其在室外溫度低于-8℃時(shí),機(jī)組效率極低,甚至無法開機(jī)。結(jié)論:本設(shè)計(jì)采用水冷式冷水機(jī)組作為冷源。4.2冷水機(jī)組的確定4.2.1冷凍站冷負(fù)荷的確定根據(jù)以上分析計(jì)算冷凍站的設(shè)計(jì)最大冷負(fù)荷,作為選擇冷水機(jī)類型、臺(tái)數(shù)、確定冷凍站規(guī)模的依據(jù)。冷凍站的最大計(jì)算冷負(fù)荷等于設(shè)計(jì)計(jì)算冷負(fù)荷乘以冷量消耗系數(shù),對(duì)于一般冷水機(jī)組冷量消耗系數(shù)取1.05~1.10,氨制冷系統(tǒng)取1.10~1.15。本設(shè)計(jì)將采用一般的冷水機(jī)組,在此取1.10。根據(jù)冷負(fù)荷計(jì)算的總冷負(fù)荷可知道本建筑中采用水冷式冷水機(jī)組承擔(dān)的設(shè)計(jì)計(jì)算冷負(fù)荷為:2148.7kw,所以冷凍站的最大計(jì)算冷負(fù)荷為:2148.7×1.10=2363.6kw。4.2.2冷水機(jī)組類型的選擇制冷機(jī)組種類較多,各種制冷機(jī)組的容量范圍和性能都各有特點(diǎn)及最佳適應(yīng)條件。主要應(yīng)根據(jù)用戶的經(jīng)濟(jì)效益及能耗等優(yōu)劣狀況進(jìn)行綜合分析,全面衡量,一般要考慮以下幾點(diǎn):1.選擇冷水機(jī)組的考慮因素:

★建筑物的用途。各類冷水機(jī)組的性能和特征。當(dāng)?shù)厮?包括水量水溫和水質(zhì))、電源和熱源(包括熱源種類、性質(zhì)及品位)。建筑物全年空調(diào)冷負(fù)荷(熱負(fù)荷)的分布規(guī)律。初投資和運(yùn)行費(fèi)用。對(duì)氟利昂類制冷劑限用期限及使用替代制冷劑的可能性。2.冷水機(jī)組的選擇注意事項(xiàng):在充分考慮上述幾方

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。

最新文檔

評(píng)論

0/150

提交評(píng)論