1、斷路器安裝作業(yè)指導(dǎo)書(shū)編碼:BDDQ-ZW-03 編寫(xiě):目次1適用范圍 ············································&

2、#183;·················································&

3、#183;·················································&

4、#183;······· 272編寫(xiě)依據(jù) ········································

5、3;·················································

6、3;·················································

7、3;··········· 273作業(yè)流程 ·····································&

8、#183;·················································&

9、#183;·················································&

10、#183;·············· 274安全風(fēng)險(xiǎn)辨析與預(yù)控 ·································

11、;··················································

12、;················································· 285作

13、業(yè)準(zhǔn)備 ·················································&#

14、183;·················································&#

15、183;·················································&#

16、183;·· 286作業(yè)方法 ··············································

17、;··················································

18、;··················································

19、;······ 297質(zhì)量控制措施及檢驗(yàn)標(biāo)準(zhǔn) ·········································&

20、#183;·················································&

21、#183;································ 331適用范圍本作業(yè)指導(dǎo)書(shū)適用于 110500kV 電壓等級(jí),頻率為 50Hz 的支柱式和罐式 SF6 斷路器安裝作業(yè)。2編寫(xiě)依據(jù)表 2-1編寫(xiě)依據(jù)序號(hào)引用資料名稱(chēng)1GBJ 1471990電氣裝置安裝工程

22、 高壓電器施工及驗(yàn)收規(guī)范2DL 4081991電業(yè)安全工作規(guī)程(發(fā)電廠和變電所電氣部分)3DL 5009.31997電力建設(shè)安全工作規(guī)程(變電所部分)4Q/CSG 100012004變電站安健環(huán)設(shè)施標(biāo)準(zhǔn)5Q/CSG 100072004電力設(shè)備預(yù)防性試驗(yàn)規(guī)程610kV500kV 輸變電及配電工程質(zhì)量驗(yàn)收與評(píng)定標(biāo)準(zhǔn)第 2 部分:變電電氣安裝工程7Q/CSG 11105.22008南方電網(wǎng)工程施工工藝控制規(guī)范8中國(guó)南方電網(wǎng)公司十項(xiàng)重點(diǎn)反事故措施3作業(yè)流程作業(yè)(工序)流程見(jiàn)圖 3-1。圖 3-1作業(yè)(工序)流程圖4安全風(fēng)險(xiǎn)辨析與預(yù)控4.1 斷路器安裝作業(yè)前,施工項(xiàng)目部根據(jù)該項(xiàng)目作業(yè)任務(wù)、施工條件,參照

23、電網(wǎng)建設(shè)施工安全基準(zhǔn)風(fēng)險(xiǎn) 指南(下簡(jiǎn)稱(chēng)指南)開(kāi)展針對(duì)性安全風(fēng)險(xiǎn)評(píng)估工作,形成該任務(wù)的風(fēng)險(xiǎn)分析表。4.2 按指南中與斷路器安裝作業(yè)相關(guān)聯(lián)的電網(wǎng)建設(shè)安全施工作業(yè)票(編碼:BDDQ-ZW-03-01/01),結(jié)合現(xiàn)場(chǎng)實(shí)際情況進(jìn)行差異化分析,確定風(fēng)險(xiǎn)等級(jí),現(xiàn)場(chǎng)技術(shù)員填寫(xiě)安全施工作業(yè)票,安全員審核,施工負(fù)責(zé)人簽發(fā)。4.3 施工負(fù)責(zé)人核對(duì)風(fēng)險(xiǎn)控制措施,并在日站班會(huì)上對(duì)全體作業(yè)人員進(jìn)行安全交底,接受交底的作業(yè)人員負(fù)責(zé)將安全措施落實(shí)到各作業(yè)任務(wù)和步驟中。 安全施工作業(yè)票由施工負(fù)責(zé)人現(xiàn)場(chǎng)持有,工作內(nèi)容、地點(diǎn)不變時(shí)可連續(xù)使用 10 天,超過(guò) 10 天須重新 辦理作業(yè)票,在工作完成后上交項(xiàng)目部保存?zhèn)洳椤1?4-1

24、作業(yè)任務(wù)安全基準(zhǔn)風(fēng)險(xiǎn)指南序號(hào)危 害 名 稱(chēng)風(fēng)險(xiǎn)種類(lèi)風(fēng)險(xiǎn)等級(jí)風(fēng)險(xiǎn)控制措施1無(wú)佩戴防護(hù)用品的作業(yè) 人員打擊可接受的風(fēng)險(xiǎn)工作人員必須戴好安全帽、穿好工作服。站班會(huì)時(shí)檢查作業(yè)人員的防護(hù)用品2無(wú)資質(zhì)的人員進(jìn)行特種作業(yè)設(shè)備損壞可接受的風(fēng)險(xiǎn)由項(xiàng)目總工對(duì)特種作業(yè)人員資質(zhì)進(jìn)行審核,確 保特種人員資質(zhì)符合要求3關(guān)鍵工序不熟悉設(shè)備損壞可接受的風(fēng)險(xiǎn)施工前由項(xiàng)目總工對(duì)施工人員進(jìn)行詳細(xì)的技術(shù)交底4無(wú)防護(hù)的坑洞跌落可接受的風(fēng)險(xiǎn)進(jìn)行預(yù)埋螺絲安裝前,安全員組織人員對(duì)安裝現(xiàn)場(chǎng)檢查,先將周邊的坑洞加蓋封板5強(qiáng)度不足的基礎(chǔ)打擊可接受的風(fēng)險(xiǎn)專(zhuān)人檢查基礎(chǔ)的強(qiáng)度,達(dá)到要求后,才進(jìn)行支架或底座安裝6無(wú)證的司索人員設(shè)備破損可接受的風(fēng)險(xiǎn)由項(xiàng)目總

25、工對(duì)特種作業(yè)人員資質(zhì)進(jìn)行審核,確 保特種人員資質(zhì)符合要求7不合格的吊具設(shè)備損壞可接受的風(fēng)險(xiǎn)使用前由專(zhuān)人檢查,確保尼龍繩合格方可使用8未限位的人字梯墜落可接受的風(fēng)險(xiǎn)斷路器吊裝時(shí)使用的人字梯應(yīng)有緊固的鉸鏈和 限制開(kāi)度的拉鏈9沒(méi)系安全帶(繩)的高空作業(yè)人員墜落中等風(fēng)險(xiǎn)對(duì)作業(yè)人員進(jìn)行安全教育,技術(shù)交底,現(xiàn)場(chǎng)加 強(qiáng)檢查并設(shè)專(zhuān)人監(jiān)護(hù),高空作業(yè)人員作業(yè)前,必 須系好安全帶(繩)10未穿 軟 底鞋 進(jìn)行高 處作業(yè)墜落中等風(fēng)險(xiǎn)加強(qiáng)作業(yè)人員安全教育,進(jìn)行技術(shù)交底,設(shè)專(zhuān) 人監(jiān)護(hù),不穿軟底鞋進(jìn)行高空作業(yè)11移動(dòng)時(shí)失去保護(hù)墜落中等風(fēng)險(xiǎn)監(jiān)護(hù)人員對(duì)高空作業(yè)人員進(jìn)行監(jiān)護(hù),確保移動(dòng)過(guò)程中不能失去安全帶保護(hù)12不當(dāng)?shù)拇杉跹b方式

26、設(shè)備損壞可接受的風(fēng)險(xiǎn)吊裝瓷件時(shí),采用尼龍繩。當(dāng)用鋼絲繩吊瓷件時(shí),鋼絲扣與瓷質(zhì)接觸部分,必須加緩沖物13滑脫的手工具打擊可接受的風(fēng)險(xiǎn)套筒及開(kāi)口扳手用布帶綁住系在施工人員手腕 上,防止滑脫傷及人員14滑脫的手工具設(shè)備破損可接受的風(fēng)險(xiǎn)套筒及開(kāi)口扳手用布帶綁住系在施工人員手腕 上,防止滑脫傷及設(shè)備序號(hào)危 害 名 稱(chēng)風(fēng)險(xiǎn)種類(lèi)風(fēng)險(xiǎn)等級(jí)風(fēng)險(xiǎn)控制措施15不合格的氣源設(shè)備性能下降可接受的風(fēng)險(xiǎn)充氣前,送專(zhuān)業(yè)機(jī)構(gòu)檢驗(yàn),由項(xiàng)目總工對(duì)檢驗(yàn)結(jié)果確認(rèn),合格后方可充氣16泄漏的氣體中毒中等風(fēng)險(xiǎn)安全員監(jiān)督充氣人員戴好口罩,充氣現(xiàn)場(chǎng)不許吸煙、吃食物17氣瓶搬運(yùn)方式不當(dāng)扭傷可接受的風(fēng)險(xiǎn)使用叉車(chē)搬運(yùn)氣瓶,當(dāng)使用人力搬運(yùn)時(shí),確保 人力

27、足夠。搬運(yùn)時(shí)輕裝輕卸,嚴(yán)禁拋擲、溜放18有缺陷的氣瓶大氣污染可接受的風(fēng)險(xiǎn)工作負(fù)責(zé)人檢查 SF6 氣瓶,外觀良好,確保防振圈應(yīng)齊全,安全帽擰緊19存放位置不當(dāng)?shù)臍馄勘ǖ惋L(fēng)險(xiǎn)氣瓶存放在防曬、防潮和通風(fēng)良好的場(chǎng)所;不得靠近熱源和油污的地方20火烤的解凍方法爆炸低風(fēng)險(xiǎn)冬季充氣時(shí),用恒溫加熱器解凍,禁止用火直 接烤氣瓶,氣瓶應(yīng)與火源保持一定距離21直接排放的氣體大氣污染可接受的風(fēng)險(xiǎn)對(duì)運(yùn)行過(guò)的六氟化硫斷路器拆裝和轉(zhuǎn)移安裝 時(shí),用六氟化硫氣體回收裝置將六氟化硫氣體進(jìn) 行回收和處理22充氣速度不符合要求設(shè)備性能下降可接受的風(fēng)險(xiǎn)項(xiàng)目總工在開(kāi)工前將充氣的要求對(duì)作業(yè)人員做好交底,確保按廠方規(guī)定的時(shí)間和要求進(jìn)行充氣

28、23操作未充氣的開(kāi)關(guān)設(shè)備性能下降可接受的風(fēng)險(xiǎn)操作前由施工負(fù)責(zé)人對(duì)斷路器的氣壓進(jìn)行檢查,禁止未充氣進(jìn)行分合閘操作24動(dòng)作的連桿碰撞可接受的風(fēng)險(xiǎn)在調(diào)整、檢修開(kāi)關(guān)設(shè)備及傳動(dòng)裝置時(shí),有防止 開(kāi)關(guān)意外脫扣傷人的可靠措施,工作人員必須避 開(kāi)開(kāi)關(guān)可動(dòng)部分的動(dòng)作空間25拆除未泄壓的儲(chǔ)能機(jī)構(gòu)打擊可接受的風(fēng)險(xiǎn)工作前,由施工負(fù)責(zé)人對(duì)機(jī)構(gòu)進(jìn)行泄壓,確認(rèn) 完全釋放能量后方可進(jìn)行機(jī)構(gòu)拆除。嚴(yán)禁在有壓 力或彈簧儲(chǔ)能的狀態(tài)下進(jìn)行拆裝或檢修工作26高分貝的響聲心理傷害可接受的風(fēng)險(xiǎn)就地操作分、合空氣斷路器時(shí),事先通知附近的工作人員,特別是高處作業(yè)人員27不按規(guī)定程序作業(yè)設(shè)備損壞可接受的風(fēng)險(xiǎn)電動(dòng)操作前,施工負(fù)責(zé)人監(jiān)督施工人員進(jìn)行慢

29、 分慢合操作,確保開(kāi)關(guān)動(dòng)作正常??諝鈹嗦菲鞒?次試動(dòng)作時(shí),應(yīng)從低壓做起5作業(yè)準(zhǔn)備5. 1人員配備表 5-1作業(yè)人員 配備 表工 序 名 稱(chēng)建議工作人數(shù)負(fù)責(zé)人數(shù)監(jiān)護(hù)人數(shù)預(yù)埋螺栓安裝21支架底座安裝61斷路器本體吊裝511連桿等附件安裝211充氣(由生產(chǎn)廠家負(fù)責(zé))21接線及試驗(yàn)421注:作業(yè)人數(shù)根據(jù)具體工程量規(guī)模配備。5.2主要工器具及儀器儀表配置表 5-2主要工器具及儀器儀表配置表序號(hào)名稱(chēng)規(guī)格/編號(hào)單位數(shù)量備注1力矩扳手8300N·m套12套筒扳手846mm套13梅花扳手1032mm套14經(jīng)緯儀套15水平尺400mm把26活動(dòng)扳手450mm把17減壓閥、充氣接頭及充氣裝置套1真空斷路器

30、不需要8溫度計(jì)個(gè)19SF6 檢漏儀套1真空斷路器不需要10微水儀及各種試驗(yàn)儀器套1真空斷路器不需微水儀11吊帶條212吊車(chē)25T臺(tái)1注:主要工器具及儀器儀表根據(jù)具體工程量規(guī)模配備。6作業(yè)方法6. 1施工準(zhǔn)備6. 1. 1技術(shù)準(zhǔn)備:按規(guī)程、生產(chǎn)廠家安裝說(shuō)明書(shū)、圖紙、設(shè)計(jì)要求及施工措施對(duì)施工人員進(jìn)行技術(shù)交底,交底要有針對(duì)性。6. 1.2人員組織:技術(shù)負(fù)責(zé)人、安裝負(fù)責(zé)人、安全質(zhì)量負(fù)責(zé)人和技術(shù)工人。6. 1.3機(jī)具的準(zhǔn)備:按施工要求準(zhǔn)備機(jī)具,并對(duì)其性能及狀態(tài)進(jìn)行檢查和維護(hù)。6. 1.4施工材料準(zhǔn)備:螺栓等。6.2預(yù)埋螺栓安裝把水泥基礎(chǔ)預(yù)留孔清理干凈,按圖紙及支架尺寸畫(huà)好中心線,然后用鋼板做一個(gè)架子用于

31、固定地腳螺栓,使其裝上斷路器支架剛好露出 35 扣,而后用混凝土灌漿,保養(yǎng)不少于 7 天。6.3支架或底座安裝6. 3. 1將分相斷路器支架分別安裝在預(yù)埋螺栓上,用水平儀通過(guò)調(diào)節(jié)地腳螺栓上的螺母使支架處于水 平,底部螺栓全部擰緊,以待本體吊裝。6. 3.2將分相斷路器機(jī)構(gòu)箱按 A、B、C 相依次吊裝在預(yù)埋基礎(chǔ)上,用經(jīng)緯儀校驗(yàn)后緊固地腳螺栓(部分分相斷路器液壓機(jī)構(gòu)箱直接立于土建基礎(chǔ)上)。6. 3.3三相聯(lián)動(dòng)斷路器采用三極共用兩個(gè)支架、一個(gè)橫梁、一個(gè)操動(dòng)機(jī)構(gòu),因此斷路器本體安裝前必須先安裝支架、橫梁,并用螺栓、螺母和平墊緊固,然后測(cè)量調(diào)節(jié),通過(guò)調(diào)節(jié)地腳螺栓上的螺母使橫梁在橫向和縱向都處于水平,緊固

32、螺母并鎖固。6.4斷路器本體吊裝6. 4. 1將分相斷路器吊起(見(jiàn)圖 6-1),用兩條等長(zhǎng)的強(qiáng)度足夠的尼龍繩對(duì)稱(chēng)地捆在滅弧室瓷套上部、上法蘭下邊,尼龍繩另一端掛在吊鉤上,以法蘭焊接為支點(diǎn)用吊車(chē)將本體緩慢吊起,待本體直立后吊離包 裝箱,吊裝時(shí)本體底部離地約 1m 的距離,由 2 人牽引扶持,平穩(wěn)的固定在支架上,調(diào)整斷路器的垂直度,然后同時(shí)固定支架螺栓。圖 6-1分相斷路器瓷套1法蘭焊接;2不銹鋼六角螺栓;3不銹鋼墊圈;4不銹鋼彈簧墊圈;5不銹鋼六角螺母6. 4.2將分相斷路器吊到機(jī)構(gòu)箱頂部以后(本體 A、B、C 相序與機(jī)構(gòu) A、B、C 相對(duì)應(yīng)),緩慢下落, 讓支柱拉桿從機(jī)構(gòu)箱頂部中心孔穿入,最后

33、使支柱充氣接頭處于連接座的中心孔缺口處,待支柱進(jìn)入連 接座上面的止口后擰緊法蘭與機(jī)構(gòu)箱頂部的連接螺栓(部分分相斷路器液壓機(jī)構(gòu)箱直接立于土建基礎(chǔ)上, 比如由西安開(kāi)關(guān)廠生產(chǎn)的斷路器)。6. 4.3 三相聯(lián)動(dòng)斷路器吊裝時(shí)用吊繩拴在極柱頂部(見(jiàn)圖 6-2),先中間相再到另外兩相的順序吊裝在支架 的相應(yīng)位置,吊裝時(shí)應(yīng)用木方等將其和其他極柱隔離。起吊時(shí)注意極柱的方向,一直保持到極柱垂直、緩 慢起吊,當(dāng)放下極柱在橫梁或支架上時(shí),注意 SF6 管路以免碰損。每個(gè)極柱出廠時(shí)已被調(diào)到分閘位置,并 預(yù)儲(chǔ)能,因此該機(jī)構(gòu)與 C 相傳動(dòng)室之間的連桿已調(diào)整好,嚴(yán)禁拆卸,合閘緩沖器也已調(diào)整好,嚴(yán)禁拆卸。圖 6-2三相聯(lián)動(dòng)斷路

34、器瓷套6.5連桿等附件安裝6. 5. 1三相聯(lián)動(dòng)斷路器連桿及管道等附件安裝必須在生產(chǎn)廠家現(xiàn)場(chǎng)技術(shù)人員的指導(dǎo)下進(jìn)行,若無(wú)廠家代 表的同意,施工人員不得擅自進(jìn)行工作連桿的連接,連桿連接圖見(jiàn)圖 6-3。拉桿的安裝工作在筒內(nèi)進(jìn)行。 C 相與 B 相間的拉桿連接步驟如下:(1) 向機(jī)構(gòu)方向轉(zhuǎn)動(dòng) B 相傳動(dòng)臂 1,以便拉桿 2 可以放入 C 相連接器 3 和 B 相連接器 4 之間。(2) 將彈簧墊圈放在拉桿兩端的螺母上。將拉桿兩端的螺紋同時(shí)旋入連接器 4(左旋)和連接器 3(右旋)。(3) 旋轉(zhuǎn)拉桿 2 使其長(zhǎng)度縮短直至 C 相傳動(dòng)臂 8,使 C 相傳動(dòng)臂帶動(dòng)分閘彈簧連桿移動(dòng) 1mm,并 檢查拉桿的螺紋

35、已經(jīng)到達(dá)檢查孔 9、10。由于拉桿的兩個(gè)螺母已互相鎖緊,故可以輕松地轉(zhuǎn)動(dòng) 拉桿。圖 6-3連桿連接圖1傳動(dòng)臂;2拉桿;3右旋連接器;4左旋連接器;5鎖緊墊圈;6鎖母(右旋螺紋);7鎖母(左旋螺紋);8傳動(dòng)臂;9螺紋旋入長(zhǎng)度檢查孔(C 相);10螺紋旋入長(zhǎng)度檢查孔(B 相)6. 5.2安裝操動(dòng)機(jī)構(gòu)與 A 相間的拉桿:(1) 檢查操動(dòng)機(jī)構(gòu)的操作桿沒(méi)有被鎖在合閘位置,操作桿可以自由地向分閘位置移動(dòng),如果操作 桿被鎖在合閘位置,鎖舌 2 被彈簧保持在合閘位置,可用一螺絲刀擠壓鎖舌,使其通過(guò)滾軸 3。 操作桿安裝圖見(jiàn)圖 6-4。圖 6-4操作桿安裝圖1操動(dòng)機(jī)構(gòu)操作桿;2分閘臂鎖舌;3滾軸(2) 彈簧墊裝

36、配圖見(jiàn)圖 6-5。將操動(dòng)機(jī)構(gòu)的操作桿 1 向合閘方向移動(dòng),將拉桿 2 裝在 A 相連接器 3 與機(jī)構(gòu)操作桿 1 之間。將拉桿 2 同時(shí)旋入操動(dòng)機(jī)構(gòu)的操作桿 1(左旋螺紋)和 A 相連接器(右 旋螺紋)。旋轉(zhuǎn)拉桿 2 縮短 A 相連接器 3 和機(jī)構(gòu)操作桿 1 之間的距離(機(jī)構(gòu)操縱桿首先移動(dòng)到其分閘位置,然后帶動(dòng)斷路器各極柱向合閘位置移動(dòng))。繼續(xù)轉(zhuǎn)動(dòng)拉桿直至 A 相極柱到達(dá)其分 閘位置,此時(shí),在 A 相傳動(dòng)臂上的檢查孔 7 和在 A 相傳動(dòng)箱外壁上的檢查孔,兩個(gè)孔的圓心 前后應(yīng)在一條直線上。用直徑 6mm 的檢查桿校對(duì),應(yīng)很容易插入這兩個(gè)孔中。注意:將彈簧 墊 4 裝在拉桿兩端的鎖母 5、6 上。

37、圖 6-5彈簧墊裝配圖1操作桿;2拉桿;3連接器(右旋螺紋);4彈簧墊;5鎖母(右旋螺紋);6鎖母(左旋螺紋);7檢查孔(3) 三相連桿裝配圖見(jiàn)圖 6-6。調(diào)整拉桿要旋轉(zhuǎn) A 相與 B 相之間的拉桿 1,使 B 相傳動(dòng)臂的檢查 孔 2 和 B 相傳動(dòng)箱外壁上的檢查孔兩孔的圓心前后對(duì)齊,用直徑 6mm 檢查桿校對(duì)。旋轉(zhuǎn) B 相與 C 相之間的拉桿 4,使 C 相傳動(dòng)臂的檢查孔 5 和 C 相傳動(dòng)箱外壁上的檢查孔兩孔的圓心 前后對(duì)齊,用直徑 6mm 檢查桿校對(duì)。圖 6-6三相連桿裝配圖1拉桿;2B 相檢查孔;3鎖母(左旋螺紋);4拉桿;5C 相檢查孔;6鎖母(左旋螺紋)6. 5.3 斷路器 SF6

38、 氣體管道連接時(shí)(見(jiàn)圖 6-7),三相氣管都先將氣管的鎖母 1 擰到各相逆止閥螺紋的 凹槽處 3,這樣氣管即可以密封好,而且斷路器各相的逆止閥也沒(méi)有打開(kāi),斷路器內(nèi)的 SF6 氣體不會(huì)被 釋放,將各相氣管的鎖母全部緊到位;當(dāng)所有的斷路器極柱氣管全部按以上方式連接后,用 SF6 氣體充 放氣裝置,將氣管抽真空。將密度計(jì)的電纜用捆扎帶固定于 A 相、B 相之間的氣管上。將無(wú)指示型密度繼電器裝在斷路器充氣閥的逆止閥上。有指示型密度繼電器在充氣后安裝。圖 6-7氣體管道連接圖1氣管鎖母;2逆止閥關(guān)閉指示槽;3逆止閥;4密度計(jì)電纜;5充氣閥6. 5.4操動(dòng)機(jī)構(gòu)箱安裝 操動(dòng)機(jī)構(gòu)箱的安裝應(yīng)在開(kāi)箱后檢查標(biāo)識(shí)牌上

39、操動(dòng)機(jī)構(gòu)和極柱的編號(hào)是否對(duì)應(yīng),必須核對(duì)正確,以防混裝。6.6充氣打開(kāi)密度繼電器充氣接頭的蓋板,將充氣接頭與氣管連接(見(jiàn)圖 6-8),將斷路器充氣至高于額定氣 壓 3MPa 的指針數(shù)。SF6 氣體充裝由生產(chǎn)廠家代表進(jìn)行,南網(wǎng)公司協(xié)助及檢查。圖 6-8充氣連管圖1氣瓶;2調(diào)節(jié)器;3密度監(jiān)視器;4連接頭;5閥;6斷路器氣閥;7充氣軟管;8適配器;9螺紋連接器;10十字接頭;11閥6.7 接線及試驗(yàn)6.7.1 1 電氣接線詳見(jiàn)屏柜安裝及二次接線安裝作業(yè)指導(dǎo)書(shū)(編號(hào):BDDQ-ZW-13)。6.7.2 2 試驗(yàn)斷路器試驗(yàn)包括檢漏,微量水測(cè)量,絕緣電阻,回路電阻,直流電阻,電容器試驗(yàn),分、合閘時(shí)間、速度、同期試驗(yàn),氣體密度繼電器、壓力表及壓

溫馨提示

  • 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶(hù)所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶(hù)上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶(hù)上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶(hù)因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。

最新文檔

評(píng)論

0/150

提交評(píng)論