建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解目

錄1前 言

·······································································································

11、編制標(biāo)準(zhǔn)

·································································································

32、臨時用電管理···························································································

63、外電線路及電氣設(shè)備防護(hù)·······································································

164、接地與防雷·····························································································

245、配電室及自備電源···················································································476、配電線路································································································

527、配電箱及開關(guān)箱······················································································608、電動建筑機(jī)械和手持式電動工具·····························································839、照明········································································································9410、結(jié)束語·································································································105建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解1、編制標(biāo)準(zhǔn)21·1

為了配合JGJ46—2005《施工現(xiàn)場臨時用電安全技術(shù)規(guī)

范》實(shí)施,以安全用電為主題,結(jié)合施工現(xiàn)場的特點(diǎn)和實(shí)際,尤其對保障人身安全、防止觸電事故發(fā)生。對施工現(xiàn)場臨時用電工程的組織設(shè)計(jì)、安全管理、保護(hù)系統(tǒng)、安全技術(shù)等以圖片的形式,有針對性地進(jìn)行闡述。1·2

本圖集依據(jù)以下標(biāo)準(zhǔn)編制1、JGJ46-2005《施工現(xiàn)場臨時用電安全技術(shù)規(guī)范》2、JGJ59—99《建筑施工安全檢查標(biāo)準(zhǔn)》3、GB50194-93《建設(shè)工程施工現(xiàn)場供用電安全規(guī)范》4、GBT13869—92《用電安全導(dǎo)則》建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解1·3

臨時用電安全隱患的原因分析31·3·1客觀原因臨時用電是一項(xiàng)專業(yè)性、技術(shù)性很強(qiáng)的工作:臨時用電的設(shè)計(jì)和正式的建筑電氣安裝工程一樣,要經(jīng)過現(xiàn)場勘查,配電系統(tǒng)及總配電箱、分配電箱位臵的確定,線路敷設(shè)方式的選擇,用電負(fù)荷計(jì)算及線路、開關(guān)電器型號的選擇,有關(guān)設(shè)計(jì)圖紙的繪制等工作程序。施工現(xiàn)場的操作工人、管理人員都離不開電,但用工制度改革后,許多工人剛剛步入施工企業(yè),經(jīng)驗(yàn)不足、技術(shù)素質(zhì)低,電氣安全意識和自我保護(hù)能力差。臨時用電有不穩(wěn)定性和臨時性,往往剛剛安裝馬上又得拆除。保障臨時供電安全的重要措施之一,就是依靠先進(jìn)的安全技術(shù)措施和材料自身的安全保護(hù)性能,需要物力和財(cái)力的投入。因此,根據(jù)建設(shè)部建辦[2005]89號《建筑工程安全防護(hù)、文明施工措施費(fèi)用及使用管理規(guī)定》的要求,必須加大安全費(fèi)用的投入。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解1·3·2

主觀原因4很多臨時用電的安全隱患問題還是在管理上,大多是因違章所致。主要是由于沒有安全技術(shù)措施,缺乏安全技術(shù)知識、不作安全技術(shù)交底、安全生產(chǎn)責(zé)任制不落實(shí)、違章指揮、違章作業(yè)造成的。因此我們首先要從管理上找原因,“抓而不緊,等于不抓”,著重檢查是否存在安全管理松散的現(xiàn)象。對安全管理工作要“從嚴(yán)”、“強(qiáng)化”,這是一個用鮮血和生命換來的教訓(xùn)。a管理者對臨時用電安全重視不夠,資金投入少b施工操作者技術(shù)素質(zhì)低c操作者安全意識差建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解2、臨時用電管理52·1

臨時用電組織設(shè)計(jì)及安全技術(shù)檔案2·1·1

臨時用電設(shè)備在5臺以上及設(shè)備總?cè)萘?0KW以上應(yīng)編制臨時用電施工組織設(shè)計(jì);臨時用電設(shè)備在5臺以下及設(shè)備總?cè)萘?0KW以下,應(yīng)制定安全用電和電氣防火措施。2·1·2

施工組織設(shè)計(jì)實(shí)施要點(diǎn):現(xiàn)場勘查是臨時用電各項(xiàng)安全措施制定的基礎(chǔ),是編制可操作性施工組織設(shè)計(jì)的依據(jù),所以必須以嚴(yán)謹(jǐn)?shù)膽B(tài)度認(rèn)真對待。在現(xiàn)場勘查的基礎(chǔ)上,根據(jù)施工現(xiàn)場實(shí)際情況和臨時用電的特點(diǎn);結(jié)合規(guī)范要求;確定現(xiàn)場供電系統(tǒng)方案、接零保護(hù)方式、總(分)配電箱的位臵、線路的敷設(shè)方式及供電線路的接線方式等。嚴(yán)格按有關(guān)規(guī)定和現(xiàn)場臨時用電的實(shí)際情況,進(jìn)行用電負(fù)荷計(jì)算。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解2·1·3

臨時用電施工組織設(shè)計(jì)編制步驟:相關(guān)部門審核6技術(shù)負(fù)責(zé)人批準(zhǔn)實(shí)施電氣工程技術(shù)人員編制臨時用電組織設(shè)計(jì)及變更設(shè)計(jì)時,必須履行“編制、審核、批準(zhǔn)”程序,由電氣工程技術(shù)人員組織編制,經(jīng)相關(guān)部門審核及具有法人資格企業(yè)的技術(shù)負(fù)責(zé)人批準(zhǔn)后實(shí)施。臨時用電工程必須經(jīng)編制、審核、批準(zhǔn)部門和使用單位共同驗(yàn)收,合格后方可投入使用。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解2·1·4

臨時用電施工組織設(shè)計(jì)基本內(nèi)容7繪制電氣工程圖紙(總平面圖、配電系統(tǒng)圖、接地裝置設(shè)計(jì)圖)76編制用電管理制度、防火制度5確定系統(tǒng)供電防護(hù)形式4設(shè)計(jì)接地裝置、防雷裝置3變壓器、配電裝置、導(dǎo)線選擇2用電負(fù)荷計(jì)算(總功率、分支功率)1現(xiàn)場勘測、確定電源位置臨時用電組織設(shè)計(jì)臨時用電施工組織設(shè)計(jì)是組織臨時供電施工的綱領(lǐng)性文件,起到指導(dǎo)作用,很多施工現(xiàn)場臨時用電存在諸多問題,其根源就是沒有編好施工組織設(shè)計(jì)。施工組織設(shè)計(jì)應(yīng)包含下列內(nèi)容:1、現(xiàn)場勘測,確定電源進(jìn)線、變電所或配電室、配電裝臵、用電設(shè)備位臵及線路走向;2、進(jìn)行負(fù)荷計(jì)算;3、選擇變壓器;4、設(shè)計(jì)配電系統(tǒng);5、設(shè)計(jì)防雷裝臵;6、確定防護(hù)措施;7、制定安全用電工程圖紙和電氣防火措施。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解2·1·5

編制臨電施工組織設(shè)計(jì)的常見問題:81、沒有遵守編制步驟,內(nèi)容不具體;2、沒有現(xiàn)場勘查、流于形式;3、電氣平面圖、接線系統(tǒng)圖不全,不符合實(shí)際;4、安全用電技術(shù)措施、安全用電組織管理措施和防火措施不切實(shí)際;5、現(xiàn)場供配電系統(tǒng)方案、接零保護(hù)方式、重復(fù)接地、總(分)配電箱的位臵、線路的敷設(shè)方式及供電線路的接線方式不符合規(guī)范要求;6、設(shè)備容量統(tǒng)計(jì)不全面、不詳細(xì)、不真實(shí)、不可靠;現(xiàn)場供電系統(tǒng)設(shè)計(jì)不合理,不符合工程的實(shí)際情況;7、沒有制定外電防護(hù)的安全技術(shù)措施和安全組織管理措施。防范措施:認(rèn)真學(xué)習(xí)JGJ46-2005

《施工現(xiàn)場臨時用電安全技術(shù)規(guī)范》,注重現(xiàn)場勘查,學(xué)習(xí)電氣平面圖和接線系統(tǒng)圖,重視施工組織設(shè)計(jì)的重要作用。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解2·2

電工及用電人員92·2·1

電工是指符合國標(biāo)GB5306-85《特種作業(yè)人員安全技術(shù)考核管理規(guī)定》中規(guī)定的人員并持有近期技術(shù)考核證件者。2·2·2

臨時用電工程的施工和維護(hù)必須由正式電氣工作人員擔(dān)任,必須具備的條件:1、經(jīng)醫(yī)生檢查無妨礙從事電氣工作的病癥;2、掌握必要的電氣知識,考核合格并取得合格證書持證上崗;3、新參加工作的維修電工、臨時工、實(shí)習(xí)人員上崗前必須經(jīng)安全教育,考試合格后在正式電工帶領(lǐng)下方可參加指定的工作;4、低壓電工不得從事高壓作業(yè);5、掌握觸電解救法和人工呼吸法;2·2·3

常見問題:1、電工無證上崗或者證件過期;2、電工不知道自己的安全責(zé)任,或者不履行職責(zé);3、項(xiàng)目管理人員指派電工沒有根據(jù)難易程度和復(fù)雜情況派相應(yīng)等級的電工去實(shí)施。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解人工呼吸法心臟按壓/口對口吹氣比例為:15/210建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解淺析:隨著高層建筑的增多,現(xiàn)場臨時供電系統(tǒng)越來越復(fù)雜,這給電工集中管理現(xiàn)場臨時供電帶來了極大困難。加強(qiáng)現(xiàn)場臨時供電安全的中心環(huán)節(jié)之一就是加強(qiáng)對配電箱的管理(保護(hù)零線)的管理。建立由項(xiàng)目經(jīng)理掛帥,項(xiàng)目工長組織,全體管理人員和各工種班長參加的安全管理和檢查小組,及時糾正安全隱患,才能形成良好的安全用電風(fēng)氣,確保臨時用電安全。11建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解2·3

安全技術(shù)檔案2·3·1

安全技術(shù)檔案包括的內(nèi)容項(xiàng)目臨時用電資料臨時用電組織設(shè)計(jì)及變更資料臨時用電工程驗(yàn)收表接地、重復(fù)接地電阻測試記錄電氣設(shè)備、材料絕緣電阻測試記錄電氣設(shè)備、材料合格證;“CCC”認(rèn)證臨時用電定期檢查、復(fù)查記錄安全用電協(xié)議及安全技術(shù)交底電工操作證、培訓(xùn)考試卷電工巡查、維修、值班記錄12淺析:建立臨時用電安全技術(shù)資料,有利于加強(qiáng)臨時用電的科學(xué)管理,使之規(guī)范化、標(biāo)準(zhǔn)化,進(jìn)而實(shí)現(xiàn)安全用電,也可用于分析安全事

故原因。檢查要點(diǎn):是否建立施工組織設(shè)計(jì);接地極阻值搖測記錄;電工維修記錄等。常見問題:施工組織設(shè)計(jì)沒有專人負(fù)責(zé)編寫;沒有建立接地阻值搖測記錄;沒有電工維修記錄;檔案沒有專人整理等。安全措施:強(qiáng)化現(xiàn)場臨時用電安全責(zé)任制,實(shí)現(xiàn)責(zé)任到人,考核到人?,F(xiàn)場必須由電氣技術(shù)人員負(fù)責(zé)臨時用電安全技術(shù)檔案。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解2·3·2

臨時用電工程定期檢查應(yīng)按分部、分項(xiàng)工程進(jìn)行,對安全隱患必須及時處理,并應(yīng)履行復(fù)查驗(yàn)收手續(xù)。淺析:安全檢查程序:制定安全檢查工作計(jì)劃;按分部、分項(xiàng)工程進(jìn)行檢查;安全檢查評價;下達(dá)隱患整改通知書;明確整改責(zé)任人、完成時間、填寫隱患整改回執(zhí);隱患整改完成后,由整改通知部門現(xiàn)場復(fù)查驗(yàn)收手續(xù)。13建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解2·3·3

安全技術(shù)檔案圖組14建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解3、外電線路及電氣設(shè)備防護(hù)外電線路電壓等級(kv)最小安全操作距離(m)<14.01~106.035~1108.022010330~500153·1

外電線路防護(hù)在高低壓線路下方建造建筑工程,隨著在建工程升高,與高低壓線路的安全距離就無法保證。在施工現(xiàn)場平面布臵設(shè)計(jì)時,要認(rèn)真進(jìn)行現(xiàn)場堪察,對高低壓線路的具體位臵進(jìn)行實(shí)測實(shí)量。3·1·1

在建工程的周邊與架空線路的邊線之間的最小安全操作距離15建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解淺析:1、必要安全距離:尤其是高壓線路,由于周圍存在強(qiáng)電場,附近導(dǎo)體產(chǎn)生感應(yīng),附近空氣也在電場中被極化,因此必須保持必要距離。2、安全操作距離:施工現(xiàn)場是動態(tài)管理,除了安全距離外,還要考慮作業(yè)條件因素,所以距離加大了。3、上、下腳手架的斜道嚴(yán)禁搭設(shè)在有外電線路的一側(cè)。因此施工過程中必須與外電線路保持一定的安全距離,當(dāng)因受現(xiàn)場作業(yè)條件限制達(dá)不到安全距離時,必須采取屏護(hù)措施,防止觸電事故發(fā)生。16建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解3·1·2

機(jī)動車道與架空線路交叉時的最小垂直距離外電線路電壓等(kv)<11~1035最小垂直距離(m)6.07.07.0當(dāng)發(fā)生施工現(xiàn)場外電架空線路的最低點(diǎn)與路面的垂直距離不能滿足要求時,馬上采取增設(shè)屏障、遮欄、圍欄、保護(hù)網(wǎng)或拆改線路等安全防護(hù)措施。17建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解3·1·3

起重機(jī)與架空線路邊線的最小安全距離電壓(kv)安全距離(m)<11035110220330500沿垂直方向1.53.04.05.06.07.08.5沿水平方向1.52.03.54.06.07.08.518建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解淺析:本條應(yīng)符合GB5144《塔式起重機(jī)安全規(guī)程》的要求。安全措施:有外電架空輸電線路的場所,應(yīng)避免起重機(jī)結(jié)構(gòu)進(jìn)入輸電線路的危險(xiǎn)區(qū)域。必須保證起重機(jī)的塔尖、塔身、旋轉(zhuǎn)臂有效旋轉(zhuǎn)范圍內(nèi)的臂前端、臂后端的任何部位或被吊物在其有效范圍內(nèi)上升或下降距外電架空線路始終保持最小安全距離。當(dāng)架空線路在塔吊等起重機(jī)的作業(yè)半徑范圍內(nèi)時,其線路上方應(yīng)有防護(hù)措施,可搭設(shè)成門形,其頂部可用5cm木板蓋嚴(yán),也可根據(jù)現(xiàn)場情況搭成單邊懸挑式結(jié)構(gòu)。無論何種形式的遮攔,必須保證所搭設(shè)的遮欄有足夠的強(qiáng)度和鋼度,以防止遮欄斷裂。為警示起重機(jī)作業(yè),可在防護(hù)架上端間斷設(shè)臵小彩旗,夜間施工應(yīng)有紅色燈泡,其電壓為36v。在架設(shè)防護(hù)施工時,必須停電。19建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解3·2

線路及設(shè)備防護(hù)措施20建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解防護(hù)搭設(shè)方案21外電線路的額定電壓(kv)1~36103560110220330500線路邊線至圍欄的安全距離(cm)屋內(nèi)82.58587.5105130170屋外959595115135175265450線路邊線至網(wǎng)狀遮攔的安全距離(cm)屋內(nèi)17.52022.54065105屋外3030305070110190270500帶電體至遮攔、圍欄的安全距離建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解不得在線路正下方搭設(shè)作業(yè)棚。搭建生活設(shè)施或堆放構(gòu)件、架具、材料及其他雜物。注意:防護(hù)架搭設(shè)應(yīng)使用木質(zhì)等絕緣材料,當(dāng)采用鋼管等金屬材料搭設(shè),防護(hù)架體必須作良好接地。防護(hù)設(shè)施無法實(shí)施時,應(yīng)與有關(guān)部門協(xié)商,采取停電或改變線路位臵。22建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解4、接地與防雷4·1

一般規(guī)定4·1·1

在施工現(xiàn)場專用變壓器的TN-S接零保護(hù)系統(tǒng)中,電氣設(shè)備的金屬外殼必須與保護(hù)零線連接。保護(hù)零線應(yīng)由工作接地線、配電室(總配電箱)電源側(cè)零線或總漏電保護(hù)器電源側(cè)零線處引出。T

DK

RCDL1L2L3NPE〨1〨2〨2〨2圖一

專用變壓器供電TN—S接零保護(hù)系統(tǒng)示意圖T—變壓器;DK—總電源隔離開關(guān);RCD—總漏電保護(hù)器;1—變壓器中性點(diǎn)工作接地;2—PE線重復(fù)接地;L1、L2、L3—相線;N—工作零線;PE—保護(hù)零線23建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解DK

RCDL1L2L3NPE〨2〨2〨2〨1圖二

三相四線制供電局部TN—S接零保護(hù)系統(tǒng)示意圖4·1·2

當(dāng)施工現(xiàn)場與外電線路共用同一供電系統(tǒng)時,電氣設(shè)備的接地、接零保護(hù)應(yīng)與原系統(tǒng)保持一致,不得一部分設(shè)備做保護(hù)接零,另一部分設(shè)備做保護(hù)接地?!怆娋€路;DK—總電源隔離開關(guān);RCD—總漏電保護(hù)器;1—NPE線重復(fù)接地;2—PE線重復(fù)接地;L1、L2、L3—相線;N—工作零線;PE—保護(hù)零線采用TN系統(tǒng)做保護(hù)接零時,工作零線(N)必須通過總漏電保護(hù)器,保護(hù)零線(PE線)必須由電源進(jìn)線零線重復(fù)接地處或總漏電保護(hù)器電源側(cè)零線處,引出形成局部TN-S接零保護(hù)系統(tǒng)。24建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解淺析:這2條按照現(xiàn)行國家標(biāo)準(zhǔn)GB14050《系統(tǒng)接地的型式及安全技術(shù)要求》,結(jié)合施工現(xiàn)場實(shí)際,規(guī)定了適合于施工現(xiàn)場臨時用電工程系統(tǒng)接地的基本型式,強(qiáng)調(diào)采用TN-S接零保護(hù)系統(tǒng)時的現(xiàn)場做法的要求,明確規(guī)定TN-S系統(tǒng)的方式方法,防止TN與TT系統(tǒng)混用的危害。施工現(xiàn)場所有電氣設(shè)備的金屬外殼,不光指動力系統(tǒng)中的設(shè)備,而且還包括照明系統(tǒng)的用電設(shè)備或插座;不光指固定式設(shè)備,還包括移動設(shè)備的金屬外殼,都必須與專用保護(hù)零線連接。保護(hù)零線是指中性點(diǎn)接地時,由中性點(diǎn)或中性線引出,不作為電源線,僅用作連接電氣設(shè)備外露可導(dǎo)電部分的導(dǎo)線,工作時僅提供漏電電流通路。在TN接零保護(hù)系統(tǒng)中,通過總漏電保護(hù)器的工作零線與保護(hù)零線之間不得再做電氣連接。在TN接零保護(hù)系統(tǒng)中,PE零線應(yīng)單獨(dú)敷設(shè)。重復(fù)接地線必須與PE線相連接,嚴(yán)禁與N線相連接。25建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解4·1·3

PE線所用材質(zhì)與相線、工作零線(N)線相同時,其最小截面應(yīng)符合下表的規(guī)定26相線芯線截面S(mm2)PE線最小截面(mm2)S≤16516

<S≤3516S>35S/2額定工作電流i、A連接導(dǎo)線的最小截面積mm2i≤2020<i≤2525<i≤3232<i≤6363<iS2·54610S——相導(dǎo)體的截面積銅連接導(dǎo)線的截面積建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解鋼接地體和接地線的最小規(guī)格27種類、規(guī)格及單位地上地下室內(nèi)室外交流電流回路直流電流回路圓鋼直徑681012扁鋼截面(mm2)厚度(mm)603100410041006角鋼厚度(mm)鋼管管臂厚度(mm)22.52.52.543.564.5建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解標(biāo)準(zhǔn)4×40鍍鋅扁鐵28建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解接地支線不得串接。選擇接地裝臵應(yīng):29交流電氣設(shè)備的接地可以利用下列自然接地體:埋設(shè)地下的金屬管道,但不包括有易燃易爆物質(zhì)的管道;金屬井管;與大地有可靠連接的建筑物金屬結(jié)構(gòu)。交流電氣設(shè)備的接地線可以利用建筑物的金屬結(jié)構(gòu)(梁、柱等)及設(shè)計(jì)規(guī)定的混凝土結(jié)構(gòu)內(nèi)部的鋼筋、配線的鋼管等。接地裝臵的敷設(shè):每個電氣裝臵的接地應(yīng)以單獨(dú)的接地線與接地干線相連接,不得在一個接地線中串接幾個需要接地的電氣裝臵。明敷接地線的表面應(yīng)涂以用15~100mm寬度相等的綠色和黃色相間的條紋。在每個導(dǎo)體的全部長度上或只在每個區(qū)間或每個可接觸的部位上宜作標(biāo)志。當(dāng)使用膠帶時,應(yīng)使用雙色膠帶。中性線宜涂淡藍(lán)色標(biāo)志。接地線的連接:接地線的連接應(yīng)采用焊接,焊接必須牢固無虛焊。接至電氣設(shè)備上的接地線,應(yīng)用鍍鋅螺栓連接;有色金屬接地線不能采用焊接時,可用螺栓連接。螺栓連接處的接觸面應(yīng)按現(xiàn)行國家標(biāo)準(zhǔn)的規(guī)定處理。接地線的焊接應(yīng)采用搭接焊,其搭接長度應(yīng)符合:建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解扁鋼為其寬度的2倍(且至少3個棱邊焊接);圓鋼為其直徑的6倍;圓鋼與扁鋼連接時,其長度為圓鋼直徑的6倍;扁鋼與鋼管、扁鋼與角鋼焊接時,為了連接可靠,除應(yīng)在其接觸部位兩側(cè)進(jìn)行焊接外,并應(yīng)焊以由鋼帶彎成的卡子或直接由鋼帶本身彎成的弧形與鋼管焊接。30接地線路和接地裝臵的檢查:接地線(接零線)的外觀檢查:檢查因絕緣損壞可能呈現(xiàn)對地電壓的金屬部分,是否已經(jīng)接地(或接零),尤其是對于新安裝的、臨時性的、移動式或攜帶式電氣設(shè)備,要特別注意;檢查接地線(接零線)與電氣設(shè)備和接地干線(或接零干線)的聯(lián)結(jié)是否牢固和接觸良好。當(dāng)用螺栓連接時,應(yīng)檢查是否有彈簧墊圈或有無松動現(xiàn)象。塔吊等高大設(shè)備的防雷接地、電源的工作接地以及各保護(hù)零線的重復(fù)接地等接地裝臵安裝后必須進(jìn)行測試,其測試結(jié)果必須滿足規(guī)范要求。·

PE

線上嚴(yán)禁裝設(shè)開關(guān)或熔斷器,嚴(yán)禁通過工作電流,且嚴(yán)禁斷線。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解1、機(jī)械設(shè)備或設(shè)施的防雷引下線可利用該設(shè)備或設(shè)施的金屬結(jié)構(gòu)體,但應(yīng)保證電器連接。312、做防雷接地機(jī)械上的電氣設(shè)備,所連接的PE線必須同時做重復(fù)接地,同一臺機(jī)械電氣設(shè)備的重復(fù)接地和機(jī)械

的防雷接地可共用同一接地體,但接

地電阻應(yīng)符合重復(fù)接地電阻值的要求。3、施工現(xiàn)場內(nèi)所有防雷裝臵的沖擊接地電阻值不得大于30Ω。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解起重機(jī)應(yīng)有良好的照明,專設(shè)電路,對夜間工作的起重機(jī)在塔身或其它部位對著工作面聚光照明。32建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解4·2·1TN系統(tǒng)中的保護(hù)零線除必須在配電室或總配電箱處做重復(fù)接地外,還必須在配電線路的中間和末端處做重復(fù)接地。在TN系統(tǒng)中,保護(hù)零線每一處重復(fù)接地裝臵的接地電阻值不應(yīng)大于10Ω。在工作接地電阻值允許到10Ω的電力系統(tǒng)中,所有重復(fù)接地的等效電阻值不應(yīng)大于10Ω。埋地深度0·6m

,接地極長度2·5m

,間距5m4·2

接地與接地電阻33建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解二根埋入地下接地裝置34建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解PE線引出落地式變壓器工作接地端接地線接地極PE線引出桿上變壓器工作接地端PE線引出

總配電箱保護(hù)零線端子板35建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解變壓器的防雷接地和工作接地共用點(diǎn),接地電阻值不大于4ΩPE線設(shè)置規(guī)定必須采用綠/黃雙色多股絕緣銅導(dǎo)線保護(hù)零線截面不應(yīng)小于相線截面1/2供電距離超過50m時,必須在首端、中間和末端處做重復(fù)接地重復(fù)接地電阻值不大于10Ω采用不少于2根接地線在不同點(diǎn)與接地體連接36建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解保護(hù)零線重復(fù)接地引下線重復(fù)接地線應(yīng)接至PE匯流排上,下端直接壓在引出地面的扁鋼,檢查中經(jīng)常發(fā)現(xiàn)重復(fù)接地線直接連到電閘箱外皮上和導(dǎo)線埋入地下的錯誤做法。PE線截面應(yīng)根據(jù)進(jìn)線電源PE線截面來選擇。37建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解4·3

不符合規(guī)定的接地重復(fù)接地直接接在箱腿上(錯誤做法)重復(fù)接地做法不規(guī)范38建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解此種重復(fù)接地不規(guī)范,且PE線應(yīng)為黃綠相間顏色39建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解重復(fù)接地應(yīng)用扁鐵直接壓在PE匯流排上,不應(yīng)采用BV線滿地跑,埋地深度應(yīng)在0·6m

以下。40建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解重復(fù)接地不符合規(guī)定接地極使用膨脹螺栓代替接地線少于兩根接地電阻達(dá)不到要求接地極、接地線禁止使用螺紋鋼制作41建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解垂直接地體宜采用角

鋼、鋼管或光面圓鋼,也可利用自然接地體嚴(yán)禁利用輸送易燃、易爆氣體的金屬管道做接地體

不得采用螺紋鋼做接地體42建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解重復(fù)接地作用:為確保接零安全可靠,防止零線斷線后,電氣設(shè)備外殼帶電,造成觸電事故。接零作用:保證人身安全,防止觸電;當(dāng)發(fā)生一相線碰殼故障時,形成很大的單相短路電流,使保護(hù)設(shè)備迅速動作,以斷開故障設(shè)備系統(tǒng),保證其他部分形成連續(xù)正常電流。常見問題:施工現(xiàn)場保護(hù)零線重復(fù)接地設(shè)臵的地點(diǎn)與數(shù)量及做法都不符合規(guī)范要求。防范措施:在施工現(xiàn)場中,重復(fù)接地不能少于三處(始端、中端、末端);在設(shè)備比較集中的地方,如攪拌機(jī)棚、鋼筋作業(yè)區(qū)等應(yīng)做一組重復(fù)接地。每一接地裝臵的接地線應(yīng)采用二根以上的導(dǎo)體,在不同點(diǎn)與接地體做電氣連接。淺析:此條規(guī)范第一部分的規(guī)定,是為了確保接地的可靠性,防止一根接地線斷開時,使接地裝臵失去保護(hù)作用。43建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解機(jī)械設(shè)備或設(shè)施的防雷引下線可利用該設(shè)備或設(shè)施的金屬結(jié)構(gòu)體,但應(yīng)保證電氣連接。井架等金屬結(jié)構(gòu)體上如再設(shè)臵防雷引下線,則引下線必須與井架等金屬結(jié)構(gòu)體 可靠焊接,確保過流時的電位,嚴(yán)禁用卡箍固定防雷引下線。安裝避雷針(接閃器)的機(jī)械設(shè)備,所有固定的動力、控制、照明、信號及通信線路,宜采用鋼管敷設(shè)。鋼管與該機(jī)械設(shè)備的金屬結(jié)構(gòu)體應(yīng)做電氣連接。淺析:安裝避雷針的機(jī)械設(shè)備所有線路必須采用鋼管敷設(shè),并將鋼管與該機(jī)械設(shè)備的金屬結(jié)構(gòu)做電氣連接,從而形成了等電位聯(lián)結(jié)。44地區(qū)年平均雷暴日(d)機(jī)械設(shè)備高度(m)≤15≥50﹥15,

﹤40≥32≥40,

﹤90≥20≥90及雷害特別嚴(yán)重地區(qū)≥124·4

防雷4·4·1

施工現(xiàn)場內(nèi)的各種起重機(jī)、井字架及龍門架、外用電梯、在施工程建筑物、臨時腳手架(大模板)等,若在相鄰建筑物、構(gòu)筑物的防雷裝臵的保護(hù)范圍以外,應(yīng)按下表5·4·2安裝防雷裝臵。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解做防雷接地機(jī)械上的電氣設(shè)備,所連接的PE線必須同時做重復(fù)接地,同一臺機(jī)械電氣設(shè)備的重復(fù)接地和機(jī)械的防雷接地可共用同一接地體,但接地電阻應(yīng)符合重復(fù)接地電阻值的要求。淺析:塔式起重機(jī)的金屬結(jié)構(gòu)、軌道及所有電氣設(shè)備的金屬外殼,應(yīng)有可靠的接地裝臵,接地電阻值不得大于4Ω。45建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解5、配電室及自備電源465·1

配電室5·1·1

配電室應(yīng)靠近電源,并應(yīng)設(shè)在灰塵少、潮氣少、振動小、無腐蝕介質(zhì)、無易燃易爆物及道路暢通的地方。淺析:本條是對配電室選擇和環(huán)境條件的要求。選擇配電室應(yīng)考慮:接近負(fù)荷中心;進(jìn)出線方便;不應(yīng)設(shè)在廁所、浴室或其他經(jīng)常有積水的場所附近。5·1·2

成列的配電柜和控制柜兩端應(yīng)與重復(fù)接地線及保護(hù)零線做電氣連接。淺析:TN-S接零保護(hù)系統(tǒng)中,保護(hù)零線在配電室處必須作重復(fù)接地;要求配電屏與控制屏的金屬框架必須做好保護(hù)接零;同時還強(qiáng)調(diào)每一接地裝臵的接地線必須采用二根以上導(dǎo)體,在不同點(diǎn)與接地裝臵做電氣連接。此規(guī)定符合“每一接地裝臵的接地線應(yīng)采用二根以上的導(dǎo)體,在不同點(diǎn)與接地體做電氣連接?!苯ㄖ┕づR時用電安全技術(shù)標(biāo)準(zhǔn)圖解施工現(xiàn)場配電室47建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解5·2

配電室的要求:481、配電室的建筑物和構(gòu)筑物的耐火等級不得低于3級,室內(nèi)配臵砂箱和可用于撲滅電氣火災(zāi)的滅火器。消防器材設(shè)專人管理,并懸掛警告標(biāo)志牌,嚴(yán)禁挪作它用。2、施工現(xiàn)場配電屏上裝設(shè)檢測儀表是為了能更好的監(jiān)測供電系統(tǒng)的電能質(zhì)量,電流狀況等,以便提供更好的供電。配電柜應(yīng)裝設(shè)電源隔離開關(guān)及短路、過載、漏電保護(hù)電器。電源隔離開關(guān)分?jǐn)鄷r應(yīng)有明顯可見分?jǐn)帱c(diǎn)。淺析:配電柜裝設(shè)電源隔離開關(guān)及短路、過載、漏電保護(hù)電器的作用是為了切斷供電電源或發(fā)出報(bào)警信號。配電柜或配電線路停電維修時,應(yīng)掛接地線,并應(yīng)懸掛“禁止合閘、有人工作”停電標(biāo)志牌。停送電必須由專人負(fù)責(zé)。淺析:懸掛標(biāo)志牌可以提醒有關(guān)人員及時糾正將要進(jìn)行的錯誤操作和做法,以防因誤操作而錯誤地向有人作業(yè)的電氣設(shè)備合閘送電和誤登帶電設(shè)備。對施工現(xiàn)場配電屏上的配電線路進(jìn)行編號并表明用途標(biāo)記,有利于配電線路與配電設(shè)備的操作、維修和管理,是防止發(fā)生誤操作的安全技術(shù)措施。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解5·3·1

發(fā)電機(jī)組電源必須與外電線路電源連鎖,嚴(yán)禁并列運(yùn)行。淺析:本條是對發(fā)電機(jī)組電源與外電源線路的電氣隔離措施及保證發(fā)電機(jī)組不至因與外電線路并列而被燒毀等做出的規(guī)定。5·3·2

發(fā)電機(jī)組應(yīng)采用電源中性點(diǎn)直接接地的三相四線制供電系統(tǒng)和獨(dú)立設(shè)臵的

TN-S系統(tǒng),其工作接地電阻值應(yīng)不大于4Ω。淺析:自備發(fā)電系統(tǒng)的接地、接零系統(tǒng)應(yīng)獨(dú)立設(shè)臵,以實(shí)現(xiàn)與外電線路的電氣隔離;防止外電線路低壓電力變壓器的高壓側(cè)反饋送電,造成危險(xiǎn)。這種情況在外電線路電源變壓器高壓側(cè)拉閘斷電、自備發(fā)電機(jī)組投入運(yùn)行時極易發(fā)生。當(dāng)施工現(xiàn)場的自備發(fā)電機(jī)組,接地系統(tǒng)必須單獨(dú)設(shè)臵,其接地裝臵與電網(wǎng)的工作接地、重復(fù)接地需保持30m的間距,應(yīng)采用TN-S接零保護(hù)系統(tǒng);不得一部分設(shè)備作保護(hù)接零,一部分設(shè)備作保護(hù)接地;只有單臺機(jī)組時,發(fā)電機(jī)中性點(diǎn)應(yīng)直接接地。495·3

230/400V自備發(fā)電機(jī)組建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解BV導(dǎo)線敷設(shè)應(yīng)符合規(guī)范要求嚴(yán)禁埋于地下50建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解6、配電線路6·1

架空線路架空線路應(yīng)采用專用電桿架設(shè)架空線路不得架設(shè)在樹木、鋼管上線路不得綁扎成束架設(shè)51建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解輸電線路敷設(shè)(架空)52建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解6·2

電纜線路6·2·1

電纜中必須包含全部工作芯線和用作保護(hù)零線或保護(hù)線的芯線。需要三相四線制配電的電纜線路必須采用五芯電纜。五芯電纜必須包含淡藍(lán)、綠或黃二種顏色絕緣芯線。淡藍(lán)色芯線必須用作N線;綠或黃雙色芯線必須用作PE線,嚴(yán)禁混用。53建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解6·2·2

電纜線路應(yīng)采用埋地或架空敷設(shè),嚴(yán)禁沿地面明設(shè),并應(yīng)避免機(jī)械損傷和介質(zhì)腐蝕。埋地電纜路徑應(yīng)設(shè)方位標(biāo)志。檢查要點(diǎn):檢查施工現(xiàn)場電纜線路,特別是電纜干線的敷設(shè)路徑,是否符合規(guī)范要求;施工現(xiàn)場電纜線路,包括固定、手持電動工具或移動式設(shè)備等的電源電纜線路是否存在地面明設(shè)、線路滿地跑、架設(shè)不符合規(guī)定現(xiàn)象,是否存在使用老化、嚴(yán)重破皮的電纜現(xiàn)象、是否存在未使用五芯電纜,而使用了四芯電纜外加一根線代替的現(xiàn)象。防范措施:嚴(yán)把審核審批關(guān),嚴(yán)禁明設(shè)電纜,對固定設(shè)備的電源電纜線、手持電動工具或移動設(shè)備等所使用的橡皮絕緣電纜應(yīng)采用鋼索架線,并用絕緣子固定,不允許長期浸泡和穿越道路、綁扎在腳手架上而不采取安全防護(hù)措施。埋深不應(yīng)小于0·7m

,并在電纜緊鄰上、下、左、右側(cè)均勻敷設(shè)不小于50mm厚的細(xì)砂,應(yīng)設(shè)方位標(biāo)志。54建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解電纜滿地跑,橡皮護(hù)套已經(jīng)壓破55建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解6·2·3

在建工程內(nèi)的電纜線路必須采用電纜埋地引入,嚴(yán)禁穿越腳手架引入。電纜垂直敷設(shè)應(yīng)允許充分利用在建工程的豎井、垂直孔洞等,并宜靠近用電負(fù)荷中心,固定點(diǎn)每樓層不得少于一處。電纜水平敷設(shè)宜沿墻或門口剛性固定,最大弧垂直

距地不得小于2m。常見隱患:建筑物臨時用電電纜沒有采用埋地引入方式,隨意從配電箱拉線引入建筑物;電纜垂直敷設(shè)的位臵沒有充分利用在建工程的豎井、垂直孔洞等,沒有靠近負(fù)荷中心,固定點(diǎn)不能滿足每樓層不少于一處的規(guī)定。電纜線垂直敷設(shè)要求垂直敷設(shè)時應(yīng)利用工程豎井、預(yù)留孔洞等每樓層固定點(diǎn)不得少于一處電纜線沿圍檔及墻壁敷設(shè)要求高度距地面不應(yīng)小于2m高度達(dá)不到規(guī)定應(yīng)作防護(hù)56建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解電纜過路應(yīng)考慮電纜敷設(shè)的高度,不能低于6m,支架必須牢固,應(yīng)該用絕緣子固定.57建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解6·3

室內(nèi)配線電纜線沿地面敷設(shè)要求電纜線沿地面敷設(shè)時應(yīng)做硬防護(hù),嚴(yán)禁沿地面明敷設(shè)58建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解7、配電箱及開關(guān)箱7·1

配電箱及開關(guān)箱的設(shè)臵7·1·1

總配電箱應(yīng)設(shè)臵在靠近電源的區(qū)域,分配電箱應(yīng)設(shè)在用電設(shè)備或負(fù)荷相對集中的區(qū)域,分配電箱與開關(guān)箱的距離不得超過30m,開關(guān)箱與其控制的固定式用電設(shè)備的水平距離不宜超過3m。常見隱患:配電箱位臵不符合要求??偱潆娤錄]有設(shè)在靠近電源的區(qū)域。分配電箱沒有設(shè)在用電設(shè)備或負(fù)荷相對集中的區(qū)域;分配電箱與開關(guān)箱的距離、開關(guān)箱與其控制的固定式用電設(shè)備的水平距離超過規(guī)范要求。防范措施:嚴(yán)把施工組織設(shè)計(jì)的審核關(guān),專業(yè)人員嚴(yán)格檢查及時糾正。配電箱選址嚴(yán)禁放在水龍頭附近59建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解7·1·2

每臺用電設(shè)備必須有各自專用的開關(guān)箱,嚴(yán)禁用同一個開關(guān)箱直接控制2臺及2臺以上用電設(shè)備(含插座)。施工現(xiàn)場應(yīng)符合“一箱、一機(jī)、一閘、一保護(hù)”原則。7·1·3

配電箱、開關(guān)箱應(yīng)采用冷軋鋼板或阻燃絕緣材料制作,厚度應(yīng)為1·2~2·0mm,其中開關(guān)箱箱體鋼板厚度不得小于1·2mm,配電箱箱體鋼板厚度不得小于1·5mm,

箱體表面應(yīng)做防腐處理。淺析:配電箱、開關(guān)箱箱體材質(zhì)一般應(yīng)采用鐵板制作,鐵板厚度的要求為了確保配

電箱、開關(guān)箱堅(jiān)固和可靠的接零保護(hù),防止漏電。配電箱標(biāo)準(zhǔn)與否不是看形式和

廠家,而是主要看制作材料、電器裝臵參數(shù)的選擇、線路的固定、進(jìn)出線的位臵、端子板的設(shè)臵等是否符合規(guī)范要求。實(shí)施要點(diǎn):配電箱、開關(guān)箱應(yīng)裝設(shè)端正、牢固,不得傾斜晃動;箱體不得豎放、側(cè)放、平放于地面。60建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解7·1·4

配電箱的電器安裝板上必須分設(shè)N線端子板和PE線端子板。N線端子板必須與金屬電器安裝板絕緣;PE線端子板必須與金屬電器安裝板做電氣連接。進(jìn)出線中的N線必須通過N線端子板連接;PE線必須通過PE線端子板連接.7·1·5配電箱、開關(guān)箱的金屬箱體、金屬電器安裝板以及電器正常不帶電的金屬底座、外殼等必須通過PE線端子板與PE線做電氣連接,金屬箱門與金屬箱體必須通過采用編織軟銅線做電氣連接。根據(jù)規(guī)范GB50303-2002的要求:多股銅芯導(dǎo)線應(yīng)壓接端子或擰緊搪錫后,與設(shè)備器具的端子連接,每個設(shè)備和器具的端子不多余2根導(dǎo)線,導(dǎo)線與端子應(yīng)匹配,導(dǎo)線壓接應(yīng)牢固。使用于潮濕或有腐蝕介質(zhì)場所的漏電保護(hù)器應(yīng)采用防濺型產(chǎn)品,其額定漏電動作電流不應(yīng)大于15mA,額定漏電動作時間不應(yīng)大于0.1s。617·1·6配電箱、開關(guān)箱外形結(jié)構(gòu)應(yīng)能防雨、防塵。常見隱患:施工現(xiàn)場配電箱的箱體頂面沒有設(shè)臵放水沿;箱體的上頂面、兩側(cè)面、后面或箱門等處,有開孔;箱體的各部位接縫不嚴(yán)密,漏雨;箱門不防雨;從箱體上頂面、兩側(cè)、后面等處進(jìn)線等做法。防范措施:強(qiáng)化電氣設(shè)施進(jìn)場后驗(yàn)收制度。配電箱進(jìn)場后,必須經(jīng)專業(yè)小組驗(yàn)收合格后方可使用。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解總配電箱應(yīng)采用冷軋鋼板制作,箱體鋼板厚度不得小于1.5mm應(yīng)配置電流表、電壓表、電度表計(jì)量及其他儀表??偱潆娤鋬?nèi)的漏電保護(hù)器可選用中靈敏度的延時型保護(hù)器漏電動作電流應(yīng)大于30mA

,動作時間應(yīng)大于0.1s。但其二者之間的乘積不應(yīng)大于30mA.s總配電箱應(yīng)具備電源隔離、短路、過載及漏電保護(hù)功能隔離開關(guān)應(yīng)采用具有可見分?jǐn)帱c(diǎn)的開關(guān)分別設(shè)置N線端子板和PE線端子板進(jìn)出線必須通過端子板連接62總配電箱配臵要求建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解分配電箱內(nèi)的漏電保護(hù)器,其漏電動作電流應(yīng)小于總配電箱的漏電動作電流,而大于開關(guān)箱內(nèi)的漏電動作電流但其二者之間的乘積不應(yīng)大于30mA.s分配電箱應(yīng)采用冷軋鋼板制作,箱體鋼板厚度不得小于1.5mm分配電箱應(yīng)裝設(shè)總隔離開關(guān)隔離開關(guān)應(yīng)采用具有可見分?jǐn)帱c(diǎn)的開關(guān)分別設(shè)置N線端子板和PE線端子板進(jìn)出線必須通過端子板連接63分配電箱配臵要求建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解一般場所選擇漏電動作電流不應(yīng)大于30mA,漏電動作時間應(yīng)小于0.1s的開關(guān)。潮濕場所選擇漏電動作電流不應(yīng)大于15mA,漏電動作時間應(yīng)小于0.1s的開關(guān)。必須裝設(shè)隔離開關(guān)隔離開關(guān)應(yīng)采用分?jǐn)鄷r具有可見分?jǐn)帱c(diǎn)并且能同時斷開電源所有極的開關(guān)N線、PE線進(jìn)出必須通過端子板連接箱體應(yīng)采用冷軋鋼板制作鋼板厚度不得小于1.2mm開關(guān)箱配臵要求64流動式開關(guān)箱固定式開關(guān)箱建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解施工機(jī)械開關(guān)箱65建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解配電箱開關(guān)箱的進(jìn)、出線口應(yīng)配備固定線卡,進(jìn)出線應(yīng)加絕緣護(hù)套并成束卡固在箱體上,不得與箱體直接接觸。移動式配電箱、開關(guān)箱的進(jìn)出線應(yīng)采用橡皮護(hù)套絕緣電纜,不得有接頭。66總空開300A分路設(shè)漏電保護(hù)器(100mA)PE線接線端子板分配電箱N線接線端子板“空漏空”設(shè)置形式建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解配電箱平面圖但是根據(jù)規(guī)范46-2005的要求應(yīng)設(shè)總隔離開關(guān)、分路隔離開關(guān)和總、分熔斷器67建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解雙排到位雙排到位

多股銅芯導(dǎo)線壓接端子或擰緊搪錫68建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解施工現(xiàn)場帶電體明露,嚴(yán)禁使用相線端子69建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解配電箱接線混亂,帶電體明漏帶電體明露,應(yīng)有電源防護(hù)罩一閘多機(jī)70建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解一閘多機(jī)(含插座)71建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解防雨防塵棚并有充足的操作空間72建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解不規(guī)范的電閘箱防護(hù)棚73建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解電閘箱防砸棚不規(guī)范且沒有充足的操作空間74建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解圍欄內(nèi)要放置滅火設(shè)施如滅火器等外電防護(hù)圍欄接零或接地保護(hù)75建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解76建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解7·2·1

電器設(shè)臵應(yīng)符合下列原則:隔離開關(guān)應(yīng)設(shè)臵于電源進(jìn)線端,應(yīng)采用分?jǐn)鄷r具有可見分?jǐn)帱c(diǎn),并能同時斷開電源所有極的隔離電器。如采用分?jǐn)鄷r具有可見分?jǐn)帱c(diǎn)的斷路器,可不另設(shè)隔離開關(guān)。裝設(shè)電流互感器時,其二次回路必須與保護(hù)零線有一個連接點(diǎn),且嚴(yán)禁斷開電路。電壓互感器嚴(yán)禁短路,電流互感器嚴(yán)禁開路。淺析:強(qiáng)調(diào)設(shè)臵隔離開關(guān)??偱潆娤鋺?yīng)裝設(shè)總隔離開關(guān)和分路隔離開關(guān),保證能在任何情況下都可以使用電設(shè)備實(shí)行電源隔離。強(qiáng)調(diào)設(shè)臵隔離開關(guān)作用是:在檢修中保證電氣設(shè)備與其他正在運(yùn)行的電氣設(shè)備可靠的隔離,并給檢修人員有可以看見的明顯的斷路點(diǎn),保證檢修工作安全??諝忾_關(guān)不能用作隔離開關(guān)。因?yàn)榭諝忾_關(guān)沒有明顯可見的斷開點(diǎn),斷開點(diǎn)距離小,易擊穿,難以保證可靠的絕緣以及觸點(diǎn)有時會發(fā)生粘合現(xiàn)象。強(qiáng)調(diào)設(shè)臵漏電保護(hù)器。在總配電箱內(nèi)裝臵漏電保護(hù)器形成一級保護(hù)網(wǎng)。總配電箱一般不宜采用漏電掉閘型,可選用中靈敏度漏電報(bào)警和延時型保護(hù)器。777·2

電器裝臵的選擇建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解漏電保護(hù)器使用于潮濕或有腐蝕介質(zhì)場所的漏電保護(hù)器應(yīng)采用防濺型產(chǎn)品,其額定漏電動作電流不應(yīng)大于

15mA78建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解漏電保護(hù)器正確接線方法79建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解7·2·2

開關(guān)箱中漏電保護(hù)器的額定漏電動作電流不應(yīng)大于30mA,額定漏電動作時間不應(yīng)大于0.1s。使用于潮濕或有腐蝕介質(zhì)場所的漏電保護(hù)器應(yīng)采用防濺型產(chǎn)品,其額定漏電80動作電流不應(yīng)大于15mA,額定漏電動作時間不應(yīng)大于0·1s。7·2·3

總配電箱中漏電保護(hù)器的額定漏電動作電流應(yīng)大于30MA,額定漏電動作時間應(yīng)大于0·1s,但其額定漏電動作電流與額定漏電動作時間的乘積不應(yīng)大于

30MA·s。7·2·4

配電箱、開關(guān)箱的電源進(jìn)線端嚴(yán)禁采用插頭和插座做活動連接。7·2·5

對配電箱、開關(guān)箱進(jìn)行定期維修、檢查時,必須將其前一級相應(yīng)的電源隔離開關(guān)分閘斷電,并懸掛“禁止合閘,有人工作”停電標(biāo)志牌,嚴(yán)禁帶電作業(yè)。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解7·3

使用與維護(hù)817·3·1對配電箱、開關(guān)箱進(jìn)行定期維修、檢查時,必須將其前一級相應(yīng)的電源隔離開關(guān)分閘斷電,并懸掛“禁止合閘,有人工作”停電標(biāo)志牌,嚴(yán)禁帶電作業(yè)。解釋:進(jìn)行檢查、維修時,應(yīng)采取“停電、驗(yàn)電、放電、裝設(shè)接地線、懸掛標(biāo)示牌和裝設(shè)遮欄的方式。停電:將其前一級相應(yīng)的電源開關(guān)分閘斷電,嚴(yán)禁帶電作業(yè)。驗(yàn)電:通過驗(yàn)電可以明顯地驗(yàn)證電氣設(shè)備和線路等是否確實(shí)無電壓,以防止出現(xiàn)帶電裝設(shè)地線,或帶電合接地刀閘等惡性事故。放電:變壓器、油開關(guān)、電力電纜、電力電容等進(jìn)行放電,是為了消除被檢修的電氣設(shè)備上的剩余電荷,以免沖擊電流對人體發(fā)生危害。裝設(shè)地線:經(jīng)驗(yàn)電、放電后,應(yīng)立即將被檢修設(shè)備接地并三相短路,確保用電安全。懸掛標(biāo)示牌和裝設(shè)遮欄:可以提醒有關(guān)人員及時糾正錯誤做法,防止誤操作。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解8、電動建筑機(jī)械和手持式電動工具82序號手持式電動工具分類定

義11類工具在防止觸電的保護(hù)方面不僅依靠基本絕緣,而且還包含一個附加安全預(yù)防措施,其方法是可能觸及的可導(dǎo)電零件做接零保護(hù)22類工具在防止觸電的保護(hù)方面不僅依靠基本絕緣,而且它還可以提供雙重絕緣或加強(qiáng)絕緣的附加安全措施和設(shè)有保護(hù)接地或依賴安裝條件的措施33類工具在防止觸電不保護(hù)方面,依靠由安全特低電壓供電和在工具內(nèi)部不會產(chǎn)生安全特低電壓高的電壓8·1

一般規(guī)定8·1·1選購的電動建筑機(jī)械、手持式電動工具及其用電安全裝臵符合相應(yīng)的國家現(xiàn)行有關(guān)強(qiáng)制性標(biāo)準(zhǔn)的規(guī)定,且有產(chǎn)品合格證和使用說明書。8·1·2塔式起重機(jī)、外用電梯、滑升模板的金屬操作平臺及需要設(shè)臵避雷裝臵的物料提升機(jī),除應(yīng)連接PE線外,還應(yīng)做重復(fù)接地。設(shè)備的金屬結(jié)構(gòu)構(gòu)件之間應(yīng)保證電氣連接。8·1·3手持式電動工具中的塑料外殼2類工具和一般場所手持式電動工具中的3類工具可不連接PE線。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解手持電動工具配備開關(guān)箱8386

安全規(guī)范學(xué)習(xí)建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解淺析:露天、潮濕場所或在金屬構(gòu)架上操作時,必須選用2類手持式電動工具;鍋爐、金屬容器、地溝、管道內(nèi)等狹窄場所,宜選用帶安全隔離變壓器的3類手持式電

動工具;若選用2類手持式電動工具必須裝設(shè)防濺型漏電保護(hù)器,并把安全隔離

變壓器或漏電保護(hù)器裝設(shè)在狹窄場所外面,工作時應(yīng)有專人監(jiān)護(hù)。8·28·2·1各建筑機(jī)械和手動工具要求塔式起重機(jī)接地裝臵設(shè)臵應(yīng)符合:軌道兩端各設(shè)一組接地裝臵軌道的接頭處作電氣連接,兩條軌道端部做環(huán)形電氣連接接地電阻值不得大于4Ω。塔吊的保護(hù)接零和接地線必須分開敷設(shè)。8·2·2外用電梯和物料提升機(jī)在每日工作前必須對行程開關(guān)、限位開關(guān)、緊急停止開關(guān)、驅(qū)動機(jī)構(gòu)和制動器等進(jìn)行空載檢查,正常后方可使用。檢查時必須有防墜落措施。實(shí)施要點(diǎn):外用電梯轎廂內(nèi)、外均應(yīng)安裝緊急停止開關(guān);在急停按鈕處是否懸掛了“非緊急情況,嚴(yán)禁使用”的標(biāo)志牌、警告牌;嚴(yán)禁使用急停按鈕作正常情況下的停機(jī)開關(guān)。8·2·3

潛水式鉆孔機(jī)開關(guān)箱中的漏電保護(hù)器必須符合規(guī)范對潮濕場所選用漏電保護(hù)中器建的股要份求建。筑事業(yè)部建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解8·2·4

夯土機(jī)械PE線的連接點(diǎn)不得少于2處。夯土機(jī)械必須裝設(shè)防濺型漏電保護(hù)器,其額定漏電電流不得大于15mA,漏電動作時間應(yīng)小于0.1S。8·2·5使用夯土機(jī)械必須按規(guī)定穿戴絕緣用品,使用過程應(yīng)有專人調(diào)整電纜,電纜長度不應(yīng)大于50m。電纜嚴(yán)禁纏繞、扭結(jié)和被夯土機(jī)跨越。8·2·6

夯土機(jī)械的操作扶手必須絕緣。8·2·7交流弧焊機(jī)變壓器的一次側(cè)電源線長度不應(yīng)大于5m,其電源進(jìn)線處必須設(shè)臵防護(hù)罩。發(fā)電機(jī)直流電焊機(jī)的換向器應(yīng)經(jīng)常檢查和維護(hù),應(yīng)消除可能產(chǎn)生的異常電火花。8·2·8

電焊機(jī)開關(guān)箱中的漏電保護(hù)器必須符合本規(guī)范第8·2·10條的要求。交流電焊機(jī)應(yīng)配裝防二次側(cè)觸電保護(hù)器。8·2·9電焊機(jī)械的二次線應(yīng)采用防水橡皮護(hù)套銅芯軟電纜,電纜長度不應(yīng)大于30m,不得采用金屬構(gòu)件或結(jié)構(gòu)鋼筋代替二次線的地線。85建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解使用交流電焊機(jī)應(yīng)遵守:86使用前應(yīng)檢查初、次線接線正確,輸入電壓符合電焊機(jī)銘牌規(guī)定,接通電源后,嚴(yán)禁接觸初級線路的帶電部分。次級抽頭聯(lián)接銅板應(yīng)壓緊,接線柱應(yīng)有墊圈。移動電焊機(jī)時,應(yīng)切斷電源,不得用拖拉電纜的方式移動電焊機(jī)。當(dāng)焊接中突然停電,應(yīng)立即切斷電源。使用電焊機(jī)應(yīng)采取正確的接零(接地)措施。電焊機(jī)應(yīng)雙線到位,不得借用金屬管道、金屬腳手架等做回路線,電焊把線應(yīng)使用專用橡套多股軟銅電纜線,線路無破損、裸露。建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解電焊機(jī)雙線到位87建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解電焊機(jī)一機(jī)、一閘、一箱、一保護(hù)88建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解電焊機(jī)專用箱漏電保護(hù)器觸電保護(hù)器89建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解電焊機(jī)導(dǎo)線裸露90建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解無開關(guān)箱控制、無接零保護(hù)、無電源防護(hù)罩91建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解電焊機(jī)線路搭在鋼筋上,電纜外皮已被燒毀電焊機(jī)線路搭在鋼筋上,電纜外皮已被燒毀92建筑施工臨時用電安全技術(shù)標(biāo)準(zhǔn)圖解9、照明939·1·2現(xiàn)場照明應(yīng)采用高光效、長壽命的照明光源。對需大面積照明的場所,應(yīng)采用高壓汞燈、高壓鈉燈或混光用的鹵鎢燈等。9·1·3照明器的選擇必須按下列環(huán)境條件確定:正常濕度一般場所,選用開啟式照明器;潮濕或特別潮濕場所,選用密閉型防水照明器或配有

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
  • 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
  • 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負(fù)責(zé)。
  • 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請與我們聯(lián)系,我們立即糾正。
  • 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時也不承擔(dān)用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

最新文檔

評論

0/150

提交評論