附表1,上海規(guī)范,,,,,,,,,附表2,上海規(guī)范,,,,,,
樓梯間的機械加壓送風量計算表(合用前室送風),,,,,,,,,,前室、合用前室的機械加壓送風量計算表(樓梯間送風),,,,,,,
,,,,,,,,,,,,,,,,,,
機械加壓送風量(m3/h)L=L1+L2+L3,,,,,,,,,,機械加壓送風量(m3/h)L=L1+L2+L3,,,,,,,
1:保持正壓值所需的風量:L1=0.827×A×△P1/n×1.25×N1×3600,,,,,,,,,,1:保持正壓值所需的風量:L1=0.827×A×△P1/n×1.25×N1×3600,,,,,,,
疏散門種類:,單開,長度(m):,1.0,高度(m):,2.1,數(shù)量:,1,,,疏散門種類:,單開,長度(m):,1.0,高度(m):,2.1,數(shù)量:,2
疏散門種類:,雙開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0,,,疏散門種類:,雙開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0
電梯門種類:,單開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0,,,電梯門種類:,單開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0
電梯門種類:,雙開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0,,,電梯門種類:,雙開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0
疏散門縫寬度(M):,,0.002,,電梯門縫寬度(M):,,0.005,,,,疏散門縫寬度(M):,,0.002,,電梯門縫寬度(M):,,0.005,
疏散門縫總長度(M):,,6.2,,電梯門縫總長度(M):,,0,,,,疏散門縫總長度(M):,,12.4,,電梯門縫總長度(M):,,0,
A——每層電梯門及疏散門總有效漏風面積:,,,,,,0.0124,,,,A——每層電梯門及疏散門總有效漏風面積:,,,,,,0.0248,
△P——壓力差Pa,,,,,,45,,,,△P——壓力差Pa,,,,,,30,
n——指數(shù)一般取2,,,,,,2,,,,n——指數(shù)一般取2,,,,,,2,
N1——漏風門數(shù)量,常開風口時取樓層數(shù),常閉風口時取1,,,,,,19,,,,N1——漏風門數(shù)量,常開風口時取樓層數(shù),常閉風口時取1,,,,,,1,
保持正壓值所需的風量(m3/h):L1=,,,,,,5881.66,,,,保持正壓值所需的風量(m3/h):L1=,,,,,,505.51,
2:著火層疏散門為保持門洞處風速的風量(m3/h):L2=3600×F×V×N2,,,,,,,,,,2:著火層疏散門為保持門洞處風速的風量(m3/h):L2=3600×F×V×N2,,,,,,,
F——每檔開啟門的斷面積:,,,,,,2.1,,,,F——每檔開啟門的斷面積:,,,,,,2.1,
V——門洞端面風速:,,,,,,0.8,,,,V——門洞端面風速:,,,,,,0.8,
N2——開啟門的數(shù)量(常開風口20層及以下取2;20層以上取3;常閉風口取1),,,,,,2,,,,N2——開啟門的數(shù)量(常開風口20層及以下取2;20層以上取3;常閉風口取1),,,,,,2,
開啟著火層疏散門為保持門洞處風速的風量(m3/h):L2=,,,,,,12096,,,,開啟著火層疏散門為保持門洞處風速的風量(m3/h):L2=,,,,,,12096,
3:送風閥門總漏風量(m3/s):L3=0.083×AF×N3×3600,,,,,,,,,,3:送風閥門總漏風量(m3/s):L3=0.083×AF×N3×3600,,,,,,,
AF——每層送風閥門的總面積,,,,,,0.16,,,,AF——每層送風閥門的總面積,,,,,,1.00,
"N3——漏風閥門的數(shù)量(常開風口取0,常閉風口取樓層數(shù))",,,,,,0,,,,"N3——漏風閥門的數(shù)量(常開風口取0,常閉風口取樓層數(shù))",,,,,,19,
送風閥門總漏風量(m3/h):L3=,,,,,,0.00,,,,送風閥門總漏風量(m3/h):L3=,,,,,,5677.20,
機械加壓送風量(m3/h)L=L1+L2+L3=,,,,,,17978,,,,機械加壓送風量(m3/h)L=L1+L2+L3=,,,,,,18279,
"按規(guī)范""DGJ08-88-2006""表3.3.7加壓風量取值L=",,,,,,20000,,,,加壓送風管最大風速(m/s):,,,,,,10.00,
L與L表兩者取大值,,,,,,20000,,,,加壓送風井道最小截面積(m2):,,,,,,0.56,
加壓送風管最大風速(m/s):,,,,,,10.00,,,,各層加壓送風風口尺寸(mmxmm):,,,,,,1000,1000
加壓送風井道最小截面積(m2):,,,,,,0.61,,,,各層加壓送風口風量(m3/h):,,,,,,18279,
各層加壓送風風口尺寸(mmxmm):,,,,,,400,400,,,加壓送風口數(shù)量:,,,,,,1,
各層加壓送風口風量(m3/h):,,,,,,2000,,,,加壓送風口遮擋系數(shù):,,,,,,0.80,
加壓送風口數(shù)量:,,,,,,10,,,,加壓送風口風速(m/s):,,,,,,6.35,
加壓送風口遮擋系數(shù):,,,,,,0.80,,,,,,,,,,,
加壓送風口風速(m/s):,,,,,,4.34,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,
消防電梯井加壓送風量=層數(shù)×1350=19×1350=,,,,25650,28215,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,
附表3,上海規(guī)范,,,,,,,,,,,,,,,,
樓梯間的機械加壓送風量計算表(合用前室不送風),,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,
機械加壓送風量(m3/h)L=L1+L2+L3,,,,,,,,,,,,,,,,,
1:保持正壓值所需的風量:L1=0.827×A×△P1/n×1.25×N1×3600,,,,,,,,,,,,,,,,,
疏散門種類:,單開,長度(m):,1.0,高度(m):,2.1,數(shù)量:,1,,,,,,,,,,
疏散門種類:,雙開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0,,,,,,,,,,
電梯門種類:,單開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0,,,,,,,,,,
電梯門種類:,雙開,長度(m):,0.0,高度(m):,0.0,數(shù)量:,0,,,,,,,,,,
疏散門縫寬度(M):,,0.002,,電梯門縫寬度(M):,,0.005,,,,,,,,,,,
疏散門縫總長度(M):,,6.2,,電梯門縫總長度(M):,,0,,,,,,,,,,,
A——每層電梯門及疏散門總有效漏風面積:,,,,,,0.0124,,,,,,,,,,,
△P——壓力差Pa,,,,,,45,,,,,,,,,,,
n——指數(shù)一般取2,,,,,,2,,,,,,,,,,,
N1——漏風門數(shù)量,常開風口時取樓層數(shù),常閉風口時取1,,,,,,19,,,,,,,,,,,
保持正壓值所需的風量(m3/h):L1=,,,,,,5881.66,,,,,,,,,,,
2:著火層疏散門為保持門洞處風速的風量(m3/h):L2=3600×F×V×N2,,,,,,,,,,,,,,,,,
F——每檔開啟門的斷面積:,,,,,,2.1,,,,,,,,,,,
V——門洞端面風速:,,,,,,0.8,,,,,,,,,,,
N2——開啟門的數(shù)量(常開風口20層及以下取2;20層以上取3;常閉風口取1),,,,,,2,,,,,,,,,,,
開啟著火層疏散門為保持門洞處風速的風量(m3/h):L2=,,,,,,12096,,,,,,,,,,,
3:送風閥門總漏風量(m3/s):L3=0.083×AF×N3×3600,,,,,,,,,,,,,,,,,
AF——每層送風閥門的總面積,,,,,,0.16,,,,,,,,,,,
"N3——漏風閥門的數(shù)量(常開風口取0,常閉風口取樓層數(shù))",,,,,,0,,,,,,,,,,,
送風閥門總漏風量(m3/h):L3=,,,,,,0.00,,,,,,,,,,,
機械加壓送風量(m3/h)L=L1+L2+L3=,,,,,,17978,,,,,,,,,,,
"按規(guī)范""DGJ08-88-2006""表3.3.7加壓風量取值L=",,,,,,20000,,,,,,,,,,,
L與L表兩者取大值,,,,,,20000,,,,,,,,,,,
加壓送風管最大風速(m/s):,,,,,,10.00,,,,,,,,,,,
加壓送風井道最小截面積(m2):,,,,,,0.61,,,,,,,,,,,
各層加壓送風風口尺寸(mmxmm):,,,,,,400,400,,,,,,,,,,
各層加壓送風口風量(m3/h):,,,,,,2000,,,,,,,,,,,
加壓送風口數(shù)量:,,,,,,10,,,,,,,,,,,
加壓送風口遮擋系數(shù):,,,,,,0.80,,,,,,,,,,,
加壓送風口風速(m/s):,,,,,,4.34,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,,
消防電梯井加壓送風量=層數(shù)×135
溫馨提示
- 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯(lián)系上傳者。文件的所有權益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
- 4. 未經(jīng)權益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫網(wǎng)僅提供信息存儲空間,僅對用戶上傳內(nèi)容的表現(xiàn)方式做保護處理,對用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對任何下載內(nèi)容負責。
- 6. 下載文件中如有侵權或不適當內(nèi)容,請與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。
最新文檔
- 教育工作者的先進事跡(13篇)
- 會計類實習報告5篇
- 七夕節(jié)超市促銷方案(5篇)
- DB12T 490.1-2013 社區(qū)管理和服務信息化規(guī)范 第1部分:總則
- 校園演講稿合集十篇
- 學習委員競選演講稿集合5篇
- 主題教學課件教學課件
- 美術課件寫生教學課件
- 春雨課件教學課件
- 葫蘆育種合同(2篇)
- 應急預案與應急能力建設
- 廻轉窯揮發(fā)法生產(chǎn)氧化鋅作業(yè)指導書
- 急性呼吸窘迫綜合征(ARDS)-公開課課件
- 二年級上冊科學課件-《8.形狀改變了》蘇教版 (共15張PPT)
- 創(chuàng)三甲資料盒(新)
- 《四季是怎樣形成的》課件1
- 年產(chǎn)100萬米預應力混凝土管樁生產(chǎn)項目可行性研究報告
- 浙江省工程建設標準《普通幼兒園建設標準》
- 參賽魚躍前滾翻-完整版PPT
- 新版現(xiàn)代西班牙語第二冊課后答案
- 光明化大理巖礦詳查報告
評論
0/150
提交評論