版權(quán)說(shuō)明:本文檔由用戶提供并上傳,收益歸屬內(nèi)容提供方,若內(nèi)容存在侵權(quán),請(qǐng)進(jìn)行舉報(bào)或認(rèn)領(lǐng)
文檔簡(jiǎn)介
1、高壓二氧化碳?xì)怏w滅火使用說(shuō)明CO2 fire extinguishing system一、簡(jiǎn) 介I. Introduction原蘇聯(lián)在50年代就開(kāi)始幫助我國(guó)在工程建設(shè)中使用二氧化碳滅火系統(tǒng),1977年國(guó)產(chǎn)二氧化碳自動(dòng)滅火系統(tǒng)通過(guò)國(guó)家鑒定。自此,我國(guó)二氧化碳自動(dòng)滅火技術(shù)開(kāi)始快速發(fā)展,如今二氧化碳自動(dòng)滅火系統(tǒng)在國(guó)內(nèi)不論在產(chǎn)品生產(chǎn)還是在產(chǎn)品應(yīng)用方面都屬于非常成熟的一種滅火技術(shù)。Since 1950s, with the help of former Soviet Union, China has begun to use CO2 fire extinguishing systems in engin
2、eering construction. In 1977, domestically made automatic CO2 fire extinguishing systems passed national verification, since then, the technology of CO2 fire extinguishing systems in China has rapidly developed. Nowadays, no matter in production or in application, this fire fighting technique has be
3、come very mature in China.二氧化碳是一種不導(dǎo)電、惰性、低毒性、滅火后不留污染物良好的滅火劑,且來(lái)源廣泛、生產(chǎn)容易、價(jià)格低廉。二氧化碳滅火主要是窒息作用,并有少量的冷卻降溫作用。廣泛應(yīng)用于電廠、電站、軋機(jī)、印刷機(jī)、浸漬油槽、造漆、制藥等易發(fā)生火災(zāi)的重要部位的消防保護(hù),以及計(jì)算機(jī)房、圖書(shū)館、檔案館、珍品庫(kù)、電訊中心等場(chǎng)所。CO2 is a non-conductive, inert and low-toxicity extinguishing agent, without any pollutants left after fire suppression, which
4、is widely sourced, easily produced, inexpensive. With its significant suffocation performance suffocation and the associated cooling effect, CO2 is widely applied to the fire protection for power plants, power stations, mills, presses, dip tanks, paint making, pharmacies and other fire-prone locatio
5、ns, and computer rooms, libraries, archives, treasures libraries, telecommunications centers and other places.ZF型二氧化碳自動(dòng)滅火系統(tǒng)主要由:氣體滅火報(bào)警控制系統(tǒng)、火災(zāi)探測(cè)系統(tǒng)、滅火劑貯存瓶、容器閥、選擇閥、單向閥、氣路控制閥、壓力開(kāi)關(guān)、噴嘴、管路等主要設(shè)備組成??山M成單元獨(dú)立系統(tǒng)或組合分配系統(tǒng)等多種形式。實(shí)施對(duì)單區(qū)或多區(qū)的消防保護(hù)。ZF CO2 fire extinguishing system contains gas fire alarm control systems, fi
6、re detection systems, extinguishing agent bottles, container valves, selector valves, check valves, gas circuit control valves, pressure switches, nozzles, pipelines and other major components, forming unit independent systems, combined distribution systems and other models to provide fire protectio
7、n for individual areas or multiple areas. 本系統(tǒng)具有自動(dòng)滅火,應(yīng)急電氣手動(dòng)滅火、現(xiàn)場(chǎng)機(jī)械開(kāi)啟滅火三種方式供用戶自行選擇。This system provides three options for users: automatic fire extinguishing, electrically emergency manual fire extinguishing, on-site mechanically initiated fire extinguishing.本系統(tǒng)經(jīng)國(guó)家固定滅火系統(tǒng)和耐火建筑構(gòu)件質(zhì)量監(jiān)督檢驗(yàn)中心的檢測(cè)合格,符合國(guó)標(biāo)GB1666
8、91996二氧化碳滅火系統(tǒng)及部件通用技術(shù)條件。This CO2 fire extinguishing system has been qualified by China National Center for Quality Supervision and Test of Fixed Fire-fighting Systems and Fire-resisting Building Components, and in line with the requirements of GB16669-1996 “General Technical Specification for Compone
9、nts of Carbon Dioxide Fire Extinguishing Systems”.二氧化碳?xì)怏w滅火系統(tǒng)是目前所知?dú)怏w滅火系統(tǒng)中唯一可以進(jìn)行局部保護(hù)的一種特殊滅火方式The CO2 fire extinguishing system is a special fire-fighting method available for local protection among a variety of gas fire extinguishing systems which are known currently.產(chǎn)品型號(hào)ZE40-SAZE70-SA公稱工作壓力(MPa)5.175
10、.17噴射時(shí)間(s)6060充裝量Kg/瓶22.542儲(chǔ)存容器容積(L)4070工作溫度范圍049049噴嘴公稱工作壓力(MPa)1.41.4儲(chǔ)存裝置檢漏界限10%10%噴嘴的保護(hù)高度(m)0.36.50.36.5系統(tǒng)啟動(dòng)方式自動(dòng)、手動(dòng)、應(yīng)急操作自動(dòng)、手動(dòng)、應(yīng)急操作系統(tǒng)滅火技術(shù)方式全淹沒(méi),局部淹沒(méi)全淹沒(méi),局部淹沒(méi)系統(tǒng)啟動(dòng)電源24V,1A24V,1A集流管安全泄放裝置動(dòng)作壓(MPa)15±0.7515±0.75儲(chǔ)存容器安全泄放裝置動(dòng)作壓(MPa)7.0±0.357.0±0.35系統(tǒng)延時(shí)啟動(dòng)時(shí)間(s)3030ModelZE40-SAZE70-SANomina
11、l Working Pressure (MPa)5.175.17Injection Time (s)6060Charging Capacity Kg/Bottle22.542Storage Container Volume (L)4070Working Temperature Range049049Nominal Nozzle Working Pressure (MPa)1.41.4Storage Device Leak Detection Limit10%10%Nozzle Protection Height (m)0.36.50.36.5System Initiating MethodAu
12、to, Manual, Emergency OperationAuto, Manual, Emergency OperationSystem Fire Extinguishing Technique Total Flooding, Local FloodingTotal Flooding, Local FloodingInitial Power Supply24V,1A24V,1AOperating Pressure of Header Pipe Safety Release Device (MPa)15±0.7515±0.75Operating Pressure of S
13、torage Container Safety Release Device (MPa)7.0±0.357.0±0.35Time Delay of System Startup (s)3030二、系統(tǒng)組成及工作原理II. System Configuration and Working Principles2.1系統(tǒng)組成:二氧化碳?xì)怏w滅火系統(tǒng)應(yīng)用于全淹沒(méi)系統(tǒng)和局部淹沒(méi)系統(tǒng),按組成方式不同又可分為組合分配系統(tǒng)和單元獨(dú)立系統(tǒng)。組合分配系統(tǒng)(combined distribution systems)即用一套氣體滅火劑儲(chǔ)存裝置通過(guò)管網(wǎng)的選擇分配,保護(hù)兩個(gè)或兩個(gè)以上防護(hù)區(qū)的滅火系統(tǒng)
14、。如果是用一套滅火劑貯存裝置單獨(dú)保護(hù)一個(gè)防護(hù)區(qū),就稱為單元獨(dú)立系統(tǒng)。2.1 System Configuration: CO2 fire extinguishing systems are applicable to total flooding systems and local flooding systems, and divided into combined distribution systems and unit-independent systems by configuration method. A combined distribution system refers t
15、o a fire extinguishing system using one gas extinguishing agent storage device to protect two or more protection areas in the manner of distribution through pipe network. If one gas extinguishing agent storage device is used for a separate protection area only, it is called unit-independent system.2
16、.2控制方式:2.2 Control Modes:本系統(tǒng)主要有自動(dòng)、手動(dòng)、機(jī)械應(yīng)急手動(dòng)和緊急啟動(dòng)/停止四種控制方式,控制過(guò)程參見(jiàn)控制流程圖: This system is provided with auto mode, manual mode, mechanically emergency manual mode and emergency start/stop mode. For the control processes, please see the control flow chart:控制流程圖Control Flow Chart火 災(zāi)火 災(zāi) 探 測(cè) 器目 視機(jī) 械 應(yīng) 急 操 作
17、火 災(zāi) 報(bào) 警 控 制 器延 時(shí) 0-30s開(kāi)啟氮?dú)怛?qū)動(dòng)裝置容 器 閥火警顯示聲光報(bào)警設(shè) 備 聯(lián) 動(dòng)打開(kāi)滅火劑瓶組釋 放滅 火噴 放 顯 示電 氣 手 動(dòng)人員撤離保護(hù)區(qū) FireFire DetectorVisual CheckEmergency Mechanical OperationFire Alarm ControllerTime Delay 0-30sStart Nitrogen Driving DeviceFire Alarm Indication Acousto-optic AlarmDevice LinkageOpen Extinguishing Agent Bottle Gro
18、up Fire ExtinguishingDischarge DisplayElectrically Manual ModeProtection Area for Evacuation(1)自動(dòng)控制方式:滅火控制系統(tǒng)可以配置感煙火災(zāi)探測(cè)器、感溫火災(zāi)探測(cè)器、火焰探測(cè)器或其它種類探測(cè)器,控制器本身有“自動(dòng)”和“手動(dòng)”控制方式選擇功能,當(dāng)選擇成“自動(dòng)”方式時(shí),控制器處于自動(dòng)控制狀態(tài)。(1) Automatic Control Mode: The fire control system can be equipped with smoke fire detectors, heat fire detec
19、tors, flame detectors, or other types of detectors, and the controller itself has “automatic” and “manual” control modes for selection. When in “auto” mode, the controller is in automatic control status.自動(dòng)控制方式時(shí),當(dāng)同一個(gè)保護(hù)區(qū)內(nèi)只有一種探測(cè)器檢測(cè)到火災(zāi)跡象時(shí),控制系統(tǒng)發(fā)出火警聲和光信號(hào),通知有異常情況發(fā)生,而不啟動(dòng)滅火裝置釋放滅火劑。如工作人員確認(rèn)火災(zāi)確實(shí)發(fā)生,確需啟動(dòng)滅火裝置滅火時(shí),可
20、按下“緊急啟動(dòng)按鈕”,即可啟動(dòng)滅火裝置實(shí)施滅火;當(dāng)有兩種探測(cè)器同時(shí)檢測(cè)到火災(zāi)跡象時(shí),控制系統(tǒng)發(fā)出聲音信號(hào),通知有火災(zāi)發(fā)生,有關(guān)人員應(yīng)立即撤離現(xiàn)場(chǎng),并發(fā)出聯(lián)動(dòng)指令,關(guān)閉風(fēng)機(jī)、防火閥等聯(lián)動(dòng)設(shè)備,經(jīng)過(guò)030s延時(shí)后,控制器發(fā)出滅火信號(hào),電動(dòng)開(kāi)啟氮?dú)怛?qū)動(dòng)裝置,驅(qū)動(dòng)氣體會(huì)打開(kāi)對(duì)應(yīng)的二氧化碳滅火瓶組實(shí)施滅火;如在控制器延時(shí)過(guò)程中發(fā)現(xiàn)并不需要啟動(dòng)滅火裝置,此時(shí)可按下保護(hù)區(qū)外的或控制器操作面板上的“緊急停止按扭”,即可終止控制滅火指令的發(fā)出。Under the automatic control mode, when only one type of detector detects fire in a pr
21、otection area, the control system will send out fire alarm sound and a light signal notifying unusual circumstance, without initiating the extinguishing agent release device. If the staff confirm a fire does occur which requires the fire extinguishing device, please press the “emergency start button
22、” to start the fire extinguishing device; when there are two types of detectors simultaneously detect signs of fire, the control system will send out a sound signal notifying the fire, and relevant personnel should immediately evacuate from the site and issue an linkage command to turn off fans, fir
23、e dampers and other devices linked, and after a time delay of 0 30s, the controller will send out a fire extinguishing signal, upon which, the motor will start the nitrogen driving device to use the driving gas to open CO2 extinguishing agent bottle group; if, during the time delay, the fire extingu
24、ishing is found not needed, please press the “emergency stop button” outside the protection area or on the controller panel to stop the command.(2)手動(dòng)控制方式:當(dāng)選擇成“手動(dòng)”控制方式時(shí),滅火控制器處于手動(dòng)控制狀態(tài)。無(wú)論那類探測(cè)器檢測(cè)到火情或誤報(bào)警,控制器只發(fā)出火災(zāi)聲光報(bào)警信號(hào),而不啟動(dòng)滅火裝置,需經(jīng)人員觀察后確認(rèn)火災(zāi)已發(fā)生,方可按下保護(hù)區(qū)外或控制器操作面板上的“緊急啟動(dòng)按鈕”,即可啟動(dòng)滅火裝置實(shí)施滅火。無(wú)論裝置處于自動(dòng)或手動(dòng)狀態(tài),按下任何緊急啟動(dòng)
25、按扭,都可啟動(dòng)滅火裝置實(shí)施滅火。同時(shí)控制器立即進(jìn)入滅火報(bào)警狀態(tài)。(2) Manual Control Mode: Under the manual control mode, the fire controller will be manual operated. No mater which type of detector detects a fire or makes any false alarm, the controller will send out an acousto-optic fire alarm signal only, rather than starting the
26、 fire extinguishing device, and do not pressure the “emergency start button” outside the protection area or on the controller panel to implement fire extinguishing until the fire is confirmed by the staff. Regardless of the control mode, the fire extinguishing device can be initiated by pressing any
27、 emergency start button, and the controller will enter into the fire alarm status immediately.(3)應(yīng)急機(jī)械啟動(dòng)工作方式:用于控制器失效時(shí),當(dāng)職守人員確認(rèn)火災(zāi)已經(jīng)發(fā)生,應(yīng)立即通知現(xiàn)場(chǎng)所有人員撤離現(xiàn)場(chǎng),并停止一切有可能影響滅火效果的設(shè)備,在確定所有人員撤離現(xiàn)場(chǎng)后,方可按以下步驟實(shí)施應(yīng)急機(jī)械啟動(dòng):拔掉氮?dú)怛?qū)動(dòng)裝置電磁鐵手動(dòng)柄上的保險(xiǎn)銷,用力向下拍擊手動(dòng)柄,氮?dú)饧纯舍尫?,氮?dú)鈺?huì)按事先設(shè)置好的路徑打開(kāi)滅火劑儲(chǔ)存瓶組是防滅火劑。(3) Emergency Mechanical Mode: This mode i
28、s applied at the controller failure. When the person on duty confirms a fire has occurred, he/she shall immediately notify all personnel on site to evacuate and turn off all equipment that may affect fire extinguishing. After all personnel evacuate from the site, take the following steps to make an
29、emergency mechanical start: Pull the safety pin out from the electromagnet manual handle of the nitrogen driving device, and then firmly slap down the manual handle to release the nitrogen which will open the extinguishing agent storage bottles to release extinguishing agent as preset.三、系統(tǒng)主要部件III. M
30、ain System Components系統(tǒng)主要組件有:儲(chǔ)氣鋼瓶、容器閥、單向閥、選擇閥、驅(qū)動(dòng)裝置、集流管、金屬軟管、噴嘴、壓力反饋裝置、控制盤(pán)、系統(tǒng)的管路附件、滅火劑輸送管路附件和儲(chǔ)氣瓶支架等。The system mainly contains: steel gas bottles, container valves, check valves, selector valves, header pipes, metal hoses, nozzles, pressure feedback devices, control panels, system pipeline fittings,
31、extinguishing agent pipeline fittings and gas bottle racks.3.1 滅火劑儲(chǔ)存鋼瓶3.1 Extinguishing Agent Storage Bottles 滅火劑儲(chǔ)存鋼瓶由高壓無(wú)縫鋼瓶、瓶頭閥(含安全閥)、虹吸管、氣驅(qū)動(dòng)裝置組成。充裝介質(zhì)為CO2充裝壓力為5.17MPa。Every extinguishing agent bottle is made of a high-pressure seamless bottle, a bottle valve (with safety valve), a siphon tube, and
32、a gas-driven device. They are filled with CO2 at a pressure of 5.17MPa.滅火劑儲(chǔ)存鋼瓶主要技術(shù)參數(shù)Main Technical Parameters of Extinguishing Agent Bottles 型號(hào)Model容積Capacity凈重Net WeghtH設(shè)計(jì)壁厚Design Wall Thickness工作壓力Working Pressure材料MateralZF40-1540L49Kg1330mm219mm5.7mm15MPa37MnZF70-1570L78Kg1500mm267mm6.3mm15MPa37
33、Mn容器閥主要技術(shù)參數(shù)Main Technical Parameters of Container Valves 型號(hào)Model通徑Diameter工作壓力Working Pressure使用介質(zhì)Medium聯(lián)接螺紋Connection Thread出口螺紋Outlet Thread當(dāng)量長(zhǎng)度Equivalent Length泄放壓力Relief PressurePF/1513mm 15MPaCO2PZ39G5/8“6.5m 19±0.95MPa機(jī)構(gòu)執(zhí)行要求Requirement手動(dòng)操作力:60N, 手動(dòng)位移:35mmManual Force: 60N; Manual Displace
34、ment: 35mm3.2 高壓軟管3.2 High-pressure Hoses 高壓軟管主要技術(shù)參數(shù)Main Technical Parameters型號(hào)Model通徑Diameter工作壓力Working Pressure使用介質(zhì)Medium聯(lián)接螺紋Connection Thread長(zhǎng)度Length當(dāng)量長(zhǎng)度Equivalent LengthGR12/1512mm15MPaCO2G 5/8“450mm3.4m3.3 液流單向閥3.3 Fluid Check Valves安裝于集流管與高壓軟管之間,用于防止滅火時(shí)集流管中的二氧化碳滅火藥劑流向儲(chǔ)存瓶組的止回裝置。This is a check
35、 device installed between the header pipe and the high-pressure hose to prevent the CO2 in the header pipe from flowing back to the storage bottle.液流單向閥主要技術(shù)參數(shù)Main Technical Parameters型號(hào)Model通徑Diamter工作壓力Working Pressure開(kāi)啟壓力Opening Pressure使用介質(zhì)Medium聯(lián)接螺紋Connection Thread材料Material當(dāng)量長(zhǎng)度Equivalent Lengt
36、hYFD12/1512mm 15MPa0.15MPaCO2M27/G 5/8HPb59-13.8m 3.4 稱重檢漏裝置3.4 Weighting Leak Detection Devices安裝在鋼瓶架上,用來(lái)監(jiān)測(cè)二氧化碳滅火劑泄露情況,在泄漏量超過(guò)10%時(shí)發(fā)出泄露報(bào)警信號(hào)。It is installed on the bottle rack to detect the leakage of CO2 extinguishing agent. When the leakage exceeds 10%, it will issue a leak alarm signal.稱重檢漏裝置主要技術(shù)參數(shù)
37、Main Technical Parameters型號(hào)Model檢漏級(jí)別Leak Detection Level輸出信號(hào)類型Typle of Output Signals輸出電壓Output Voltage額定電流Current RatingCZ4Kg開(kāi)關(guān)量Switching ValueDC24V1.5A3.5 集流管3.5 Header Pipes 安裝在鋼瓶架上,用來(lái)匯集保護(hù)區(qū)所需各儲(chǔ)存瓶組的二氧化碳滅火藥劑。It is installed on the bottle rack to collect required CO2 extinguishing agent
38、from each storage bottle group for the protection area.集流管主要技術(shù)參數(shù)Main Technical Parameters型號(hào)Model通徑Diamter最大工作壓力Max. Working Pressure使用介質(zhì)Medium聯(lián)接螺紋Connection Thread材料Material當(dāng)量長(zhǎng)度Equivalent LengthDG/15DN15MPaCO2M27/M1620鋼 20# Steel3.0m 3.6 安全泄壓閥 3.6 Safety Relief Valves安裝在集流管上,用以實(shí)現(xiàn)集流管的超壓泄放功能。It is ins
39、talled on the header pipe to achieve the over-pressure relief function. 安全閥主要技術(shù)參數(shù)Main Technical Parameters型號(hào)Model通徑Diameter泄放壓力Relief Pressure使用介質(zhì)Medium聯(lián)接螺紋Connection Thread材料MaterialAF7/157.115±0.75MPaCO2M16HPb59-13.7 選擇閥3.7 Selector Valves安裝在集流管上用于實(shí)現(xiàn)組合分配的功能,選擇閥含氣啟動(dòng)裝置。該部件僅用于組合分配系統(tǒng)中。It is insta
40、lled on the header pipe to achieve combined distribution function, and provided with a gas initiating device. This component is for combined distribution systems only.選擇閥主要技術(shù)參數(shù)Main Technical Parameters 型 號(hào)Model公稱通徑Nominal Diameter工作壓力Working Pressure開(kāi)啟壓力Opening Pressure當(dāng)量長(zhǎng)度Equivalent Length進(jìn)出口螺紋尺寸In
41、let and Outlet Thread進(jìn)出口法蘭特征尺寸Inlet and Outlet FlangemmMPaMPaMZG法蘭外徑DOutside Diameter DSAXZ 25/1225121.04.4ZG 1"140SAXZ 32/12325.1ZG 1 1/4"155SAXZ 40/12405.82ZG 1 1/2"170SAXZ 50/12506.4ZG 2"195SAXZ 65/12657.3ZG 2 1/2"220SAXZ 80/12805.5ZG 3 "230SAXZ 100/121004.9ZG 4"
42、;265SAXZ 125/121254.1ZG 5"315手動(dòng)操作要求Manual Operation Requirement手動(dòng)操作力40N,操作位移35mmManual Force: 40N; Manual Displacement: 35mm3.8 壓力信號(hào)發(fā)生器3.8 Pressure Signal Generators安裝在選擇閥的出口部位(單元獨(dú)立系統(tǒng),安裝在集流管上)。當(dāng)選擇閥開(kāi)啟釋放藥劑時(shí),壓力信號(hào)發(fā)生器動(dòng)作送出工作信號(hào)給滅火控制系統(tǒng)。It is installed at the outlet of the selector valve (on the header
43、pipe in the event of a unit-independent system). When the selector valve opens to release extinguishing agent, this generator will send out a working signal to the fire control system. 壓力信號(hào)發(fā)生器主要參數(shù)Main Parameters 型號(hào)Model啟動(dòng)壓力Opening Pressure輸出信號(hào)類型Type of Output Signals輸出電壓Output Voltage額定電流Curren
44、t RatingELQ-1/20.2MPa開(kāi)關(guān)量Switching ValveDC24V1.5A 3.9 藥劑噴放管路及管配件噴放管路3.9 Extinguishing Agent Discharge Pipeline and Pipe Fitting Discharge Pipeline 安裝在鋼瓶間至保護(hù)區(qū)噴頭之間,用于實(shí)現(xiàn)藥劑噴放的功能。They are arranged between bottles and the protection areas nozzles for the discharge of extinguishing ag
45、ent. 噴放管路主要參數(shù)Main Parameters 通徑Diameter1520253240外徑×壁厚Outside Diameter × Wall Thickness22×427×434×4.542×548×5通徑Diameter506580100125外徑×壁厚Outside Diameter × Wall Thickness60×5.576×789×7.5114×8.5140×9.5注:以上管路的材料均為20#高壓無(wú)縫鋼管內(nèi)外熱鍍鋅,并符合GB
46、8163-87。Note: The material for these pipelines shall be 20# high-pressure seamless steel pipes which are hot-dip galvanized on both inside and outside surfaces and conform to GB8163-87.3.10 噴嘴3.10 Nozzles噴嘴安裝在滅火系統(tǒng)管網(wǎng)末端,按設(shè)計(jì)要求將滅火劑噴灑到被保護(hù)區(qū)域內(nèi),或者直接噴灑到被保護(hù)的物質(zhì)表面上,將火災(zāi)撲滅。It is installed on the end of the system
47、 pipe network to spray extinguishing agent to the protection area as designed or directly spray it to the surface of protected materials to put out the fire. 噴嘴有全淹沒(méi)無(wú)噴罩噴嘴,全淹沒(méi)帶罩噴嘴,局部應(yīng)用架空型噴嘴,局部應(yīng)用槽邊型噴嘴、防塵噴嘴。分別見(jiàn)圖Nozzles are divided into total flooding nozzles without a shield, total flooding nozzles with
48、 a shield, overhead nozzles for local application, notched nozzles for local application and dust-proof nozzles. Please refer to their pictures. 有噴罩噴嘴主要技術(shù)參數(shù)Main Technical Parameters 標(biāo)準(zhǔn)號(hào)Standard Number n5678910111213141414NA23.533.543.54444.545.145.746.346.847.347.848.3噴孔面積Hole Area mm219.2328.8538.4
49、750.2463.5981.67102124.63145.19167.3191.04216.31Rc3/8”3/8”3/8”1/2”1/2”1/2”3/4”3/4”3/4”3/4”3/4”3/4”L145145145145145145150150150150150150DN1010101515152020202020203.11 氮?dú)怛?qū)動(dòng)裝置3.11 Nitrogen Driving Devices用途:氮?dú)怛?qū)動(dòng)裝置用以儲(chǔ)存啟動(dòng)氣體,提供打開(kāi)容器閥和選擇閥的氣體壓力,充裝介質(zhì)為氮?dú)猓溲b壓力為46.0MPa,主要由氮?dú)馄?、電磁鐵、安全閥、操作手柄、壓力表等組成?;馂?zāi)時(shí),滅火控制器發(fā)出電信號(hào)DC
50、24V,1.5A,電磁鐵動(dòng)作從而開(kāi)啟氮?dú)馄款^閥,驅(qū)動(dòng)氣體通過(guò)低壓軟管(即驅(qū)動(dòng)氣體管路)打開(kāi)相應(yīng)的選擇閥和滅火劑瓶頭閥,釋放滅火劑Purpose: The nitrogen driving device consists of a nitrogen bottle, an electromagnet, a safety valve, an operating handle, a pressure gauge, etc., used to store initiating gas to provide gas pressure for opening the container valve and
51、selector valve. It is filled with nitrogen at a pressure of 46.0MPa. In the case of a fire, the controller will send out an electrical signal of DC24V, 1.5A, upon which, the electromagnet will acts and open the bottle valve. The driving gas will flow through the low-pressure hose to open the appropr
52、iate selector valve and extinguishing agent bottle valve, releasing extinguishing agent.在緊急狀態(tài)下,由工作人員拔掉氮?dú)怛?qū)動(dòng)裝置電磁鐵手動(dòng)柄上的保險(xiǎn)銷,用力向下拍擊手動(dòng)柄,氮?dú)饧纯舍尫牛獨(dú)鈺?huì)按事先設(shè)置好的路徑打開(kāi)滅火劑儲(chǔ)存瓶組釋放滅火劑。In the state of emergency, the staff shall pull the safety pin out from the electromagnet manual handle of the nitrogen driving device,
53、and then firmly slap down the manual handle to release the nitrogen which will open the extinguishing agent storage bottles to release extinguishing agent as preset.產(chǎn)品型號(hào)ModelFL-QD4FL-QD10公稱工作壓力(MPa)Nominal Working Pressure (MPa)66最大工作壓力(MPa)Max. Working Pressure (MPa)6.66.6儲(chǔ)存容器容積(L)Storage Container
54、 Volume (L)410工作溫度范圍Working Temperature Range049049充裝介質(zhì)MediumN2N2儲(chǔ)存裝置檢漏方式Storage Device Leak Detection Method目測(cè)壓力表Visual Pressure Gauge目測(cè)壓力表ual Pressure Gauge氮?dú)忾_(kāi)啟方式Nitrogen Initiating Method電動(dòng)、手動(dòng)Electrical, Manual電動(dòng)、手動(dòng)Electrical, Manual系統(tǒng)啟動(dòng)電源Initial Power SupplyDC24V,1.5A24V,1.5A電磁驅(qū)動(dòng)力Electromagnetic
55、 Driving Force90N90N需要的最小驅(qū)動(dòng)力Min. Required Driving Force 18N18N鋼瓶接口螺紋Bottle Connection ThreadPZ27.8 14牙/英寸 錐度3:25PZ27.8 14 Teeth/Inch Taper: 3:25四、維護(hù)與保養(yǎng)IV. Repair and Maintenance 1、二氧化碳系統(tǒng)是一種高效的滅火裝置,自動(dòng)化程度高,密封性能要求嚴(yán)。為了確保工作的可靠性,應(yīng)按規(guī)定建立完善的系統(tǒng)檢查和維護(hù)保養(yǎng)制度,制定操作規(guī)程。對(duì)系統(tǒng)應(yīng)定期檢查并做好記錄,檢查員簽名。1. CO2 fire extinguishing system is a highly efficient device of high degree of automation and requiring high sealing performance. In order to ensure the reliability of the system, it is required to establish a sound inspection and maintenance system, and develop operating procedures. Record shall be maintained for regular
溫馨提示
- 1. 本站所有資源如無(wú)特殊說(shuō)明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
- 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
- 3. 本站RAR壓縮包中若帶圖紙,網(wǎng)頁(yè)內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒(méi)有圖紙預(yù)覽就沒(méi)有圖紙。
- 4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
- 5. 人人文庫(kù)網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
- 6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
- 7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。
最新文檔
- 班級(jí)戶外策劃方案
- 石河子大學(xué)《園林工程制圖》2021-2022學(xué)年第一學(xué)期期末試卷
- 房屋維修協(xié)議書(shū)范本(11篇)
- 石河子大學(xué)《跨文化傳播》2023-2024學(xué)年第一學(xué)期期末試卷
- 沈陽(yáng)理工大學(xué)《數(shù)字圖像處理》2022-2023學(xué)年期末試卷
- 沈陽(yáng)理工大學(xué)《俄羅斯文學(xué)史》2022-2023學(xué)年第一學(xué)期期末試卷
- 沈陽(yáng)理工大學(xué)《超精密制造工程》2023-2024學(xué)年第一學(xué)期期末試卷
- 國(guó)家工商總局 建設(shè)工程勘察合同
- 合伙人招募合同
- 2024高考政治一輪復(fù)習(xí)第三單元發(fā)展社會(huì)主義民主政治第六課我國(guó)的人民代表大會(huì)制度課時(shí)作業(yè)含解析必修2
- 2024年企業(yè)數(shù)據(jù)存儲(chǔ)與安全服務(wù)合同
- 2022年北京市公務(wù)員錄用考試《行測(cè)》真題及答案解析
- 江蘇省泰興市2024-2025學(xué)年高三上學(xué)期期中考試語(yǔ)文試題(含答案)
- 家長(zhǎng)會(huì)教學(xué)課件
- 律師事務(wù)所律師事務(wù)所風(fēng)險(xiǎn)管理手冊(cè)
- 2024版中國(guó)航天發(fā)展歷程
- 2024年消防宣傳月知識(shí)競(jìng)賽考試題庫(kù)500題(含答案)
- 國(guó)開(kāi)2024年秋《機(jī)電控制工程基礎(chǔ)》形考任務(wù)1答案
- 2024年典型事故案例警示教育手冊(cè)15例
- 高一歷史(中外歷史綱要上冊(cè))期中測(cè)試卷及答案
- 20K607 防排煙及暖通防火設(shè)計(jì)審查與安裝
評(píng)論
0/150
提交評(píng)論